Specifications 

 

Operating voltage range 

15.20 to 19.95 VDC 

Current 
 

Standby 

 

Activated 

 
310 µA 
135 µA 

Maximum line impedance 

Refer to the control panel installation 
manual 

Ground fault impedance 

10 kΩ 

Output ratings (special 
applications) 
 

24 VDC 

 

25 VRMS audio 

 

70 VRMS audio 

 

EOL resistor value 

 

Circuit resistance  

 
 

Circuit capacitance 

 
 
2 A 
50 W 
35 W 
47 kΩ 
Refer to the control panel installation 
manual 
0.1 µF max. 

EOLR 

47 kΩ (P/N EOL-47) 

Circuit designation 
 

Signaling line circuits 

 

Telephone riser circuits 

 

Notification line circuits 

 
Class A, Style 6 or Class B, Style 4 
Class B, Style 4  
Class B, Style Y  

LPCB/CPR electrical box 

Requirements 
 
Minimum size W × H × D 

 
Plastic box with cover plate, no gaps 
or unused holes 
3.5 × 3.5 × 1.5 in. (85 × 85 × 38 mm) 

Compatible electrical boxes 

2-1/2 in. (64 mm) deep dual-gang box; 
4 in. square box 1-1/2 in. (38 mm) 
deep box with a dual-gang cover 

Wire sizes 

12 to 18 AWG (1.0 to 4.0 mm²) 

Operating environment 
 

Temperature 

 

Relative humidity 

 
32 to 120°F (0 to 49°C) 
0 to 93%, noncondensing 

Storage temperature range 

−4 to 140°F (−20 to 60°C) 

Regulatory information 

 

Manufacturer 

Edwards, A Division of UTC Fire & Security 
Americas Corporation, Inc. 
8985 Town Center Parkway, Bradenton, FL 
34202, USA 

Authorized EU manufacturing representative: 
UTC Fire & Security B.V. 
Kelvinstraat 7, 6003 DH Weert, Netherlands 

Year of manufacture  The first two digits of the DATE MFG number 

(located on the product identification label) are 
the year of manufacture. 

FCC compliance 

This device complies with part 15 of the FCC 
Rules. Operation is subject to the following two 
conditions: (1) This device may not cause 
harmful interference, and (2) this device must 
accept any interference received, including 
interference that may cause undesired operation. 

North American 
standards 

CAN/ULC-S527, UL 864 

EN 54 

EN 54-18: 2005 Input/output devices 

EU compliance 

 

CPR certificates 

0832-CPR-F0840 

 

2002/96/EC (WEEE directive): Products marked 
with this symbol cannot be disposed of as 
unsorted municipal waste in the European Union. 
For proper recycling, return this product to your 
local supplier upon the purchase of equivalent 
new equipment, or dispose of it at designated 
collection points. For more information, see: 
www.recyclethis.info. 

Contact information 

For contact information, see www.est-fire.com. 

 

6 / 6 

 

P/N 387022P-EN • REV 12 • ISS 22JUN15 

Summary of Contents for EST SIGA-CC1

Page 1: ...ate Class B 26 Telephone four state Class B Personality code 5 Signal supervised output Class B Configures the SIGA CC1 module as a riser selector for audible and visible notification appliance circuits or for single channel audio circuits The output circuit is monitored for open or shorted wiring If a short exists the module will not activate in order to prevent shorting the riser The module will...

Page 2: ...nances and regulations General wiring notes Refer to the Signature loop controller installation sheet for SLC wiring specifications Refer to the firefighter phone installation sheet for additional details Each terminal on the module is limited to a single conductor Test resistors are supplied with the SIGA CC1 to prevent trouble signals on unused circuits during installation When connecting field ...

Page 3: ...P or permitted substitute cables provided these power limited cable conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 4 mm space or by a nonconductive sleeve or nonconductive barrier from all other conductors Refer to the NFPA 70 National Electrical Code for more details 4 If using a G1 P Genesis series horn while connected to a compatible fire alarm control panel a CD...

Page 4: ...ower limited source or Use type FPL FPLR FPLP or permitted substitute cables provided these power limited cable conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 4 mm space or by a nonconductive sleeve or nonconductive barrier from all other conductors Refer to the NFPA 70 National Electrical Code for more details 4 Unshielded twisted pair 5 47 kΩ EOLR P N EOL 47 6 Sig...

Page 5: ...titute cables provided these power limited cable conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 4 mm space or by a nonconductive sleeve or nonconductive barrier from all other conductors Refer to the NFPA 70 National Electrical Code for more details 4 Required if the distance from the SIGA CC1 to the phone is greater than 5 ft Shield must be continuous insulated and...

Page 6: ...atory information Manufacturer Edwards A Division of UTC Fire Security Americas Corporation Inc 8985 Town Center Parkway Bradenton FL 34202 USA Authorized EU manufacturing representative UTC Fire Security B V Kelvinstraat 7 6003 DH Weert Netherlands Year of manufacture The first two digits of the DATE MFG number located on the product identification label are the year of manufacture FCC compliance...

Reviews: