APPLICATION

The Det-Tronics W867 Ultraviolet/Infrared (UV/IR) 
Test Lamp is a portable, battery operated source of 
ultraviolet and infrared radiation that can be used for 
periodic inspection of UV, single frequency IR and 
UV/IR flame detection systems.  It produces UV and 
IR radiation to verify response of the flame detection 
system without the need for an open flame, and is 
suitable for use in hazardous (classified) areas.  (Note:  
Det-Tronics Dual Frequency IR detectors require the 
model W868 Dual Frequency IR Test Lamp for testing.)

SPECIFICATIONS

ENCLOSURE—

Cast aluminum.

CERTIFICATION—

Class I, Division 1, Groups C and D;

Class II, Division 1, Groups E, F and G.
For storage and use in dry or damp 
locations only.

ELECTRICAL RATINGS—

Battery Charger Input Voltage: 

120 volts ac, 60 Hz

    220 

volts 

ac, 

50 

Hz 

    (optional).

TEMPERATURE RANGE—

Operating: 

+5°F to +122°F (–15°C to +50°C).

Charge:   

+32°F to +104°F (0°C to +40°C).

Storage:   

+5°F to +104°F (–15°C to +40°C).

OPERATING TIME—

Approximately 15 minutes continuous between 
recharges.  This will vary with the ambient temperature.

OUTPUT—

Broadband emissions in both UV and IR spectra.

APPROXIMATE OPERATING RANGE—

UV detector (25 cps sensitivity setting):  

>50 feet (15 meters).

IR detector (40 cps sensitivity setting):  

5 feet (1.5 meters).

UV/IR detector (16 cps sensitivity setting):  

5 feet (1.5 meters).

DIMENSIONS—

See Figure 1.

WEIGHT (APPROXIMATE)—

14 pounds (6.2 kg).

INSTRUCTIONS

Ultraviolet/Infrared Test Lamp

W867

F M

APPROVED

5.1

 

©

Detector Electronics Corporation 2007 

9/07 95-8309

Summary of Contents for Det-Tronics W867

Page 1: ... 1 Groups E F and G For storage and use in dry or damp locations only ELECTRICAL RATINGS Battery Charger Input Voltage 120 volts ac 60 Hz 220 volts ac 50 Hz optional TEMPERATURE RANGE Operating 5 F to 122 F 15 C to 50 C Charge 32 F to 104 F 0 C to 40 C Storage 5 F to 104 F 15 C to 40 C OPERATING TIME Approximately 15 minutes continuous between recharges This will vary with the ambient temperature ...

Page 2: ... It may be necessary to decrease the distance between the detector and the test lamp in order to obtain a response Do not operate the test lamp longer than is necessary to actuate the detector Each detector can be checked with less than 30 seconds of operating time It is important to avoid discharging the battery to the point where the battery charge level Indicating LED see Figure 2 is on steady ...

Page 3: ...window is off When the battery reaches a marginal level the Indicating LED will flash on and off The battery should be recharged at this time If the Indicating LED is on continuously the battery is at a very low level and the test lamp should not be operated until the battery has been recharged WARNING The life of the battery is significantly reduced if it is operated when the red LED is on contin...

Page 4: ...equipment transportation prepaid to the factory in Minneapolis ORDERING INFORMATION When ordering specify Part Number Description 004000 003 W867C3001 120 VAC 004000 004 W867C3002 220 VAC 2 pin Euro 004000 005 W867C3003 220 VAC 3 pin UK NOTE Includes test lamp with battery and charger For assistance in ordering please contact Detector Electronics Corporation 6901 West 110th Street Minneapolis Minn...

Reviews: