95-8309

5.1

WARNING

Exposure to ultraviolet radiation from the 
W867 Test Lamp can be damaging to the 
eyes.  Do not look directly into the window of 
the test lamp when it is on.

OPERATION

To operate the W867 Test Lamp, push the “ON” 
button (see Figure 2) and aim the test lamp at the 
detector.  The UV and IR emitting lamp inside the 
W867 will flash on and off at a rate of approximately 
2 times per second.  This flashing operation satisfies 
the “flicker” circuit in the IR detector.  Response of 
the detection system will depend upon the distance 
between the W867 and the detector, and upon the 
sensitivity programmed into the detection system.  It 
may be necessary to decrease the distance between 
the detector and the test lamp in order to obtain a 
response.  

Do not operate the test lamp longer than is necessary 
to actuate the detector.  Each detector can be checked 
with less than 30 seconds of operating time.  It is 
important to avoid discharging the battery to the point 
where the battery charge level Indicating LED (see 
Figure 2) is on steady.  Refer to the Battery Maintenance 
section of these instructions for further information.

CAUTION

Do not remove the shock insulators from the 
lens cap or battery storage compartment.

A1713

4.25

(10.8)

7.38

(18.7)

10.38 (26.4)

7.00

(17.8)

10.625 (27.0)

3.75

(9.5)

TOP VIEW

S

IDE VIEW

Figure 1—W867 Test Lamp Dimensions in inches (cm)

A1714

WINDOWED PLUG

ON PU

S

HBUTTON

HANDLE

INDICATING LED

CHARGER CABLE CONNECTION

Figure 2—Top View of W867 Test Lamp

Summary of Contents for Det-Tronics W867

Page 1: ... 1 Groups E F and G For storage and use in dry or damp locations only ELECTRICAL RATINGS Battery Charger Input Voltage 120 volts ac 60 Hz 220 volts ac 50 Hz optional TEMPERATURE RANGE Operating 5 F to 122 F 15 C to 50 C Charge 32 F to 104 F 0 C to 40 C Storage 5 F to 104 F 15 C to 40 C OPERATING TIME Approximately 15 minutes continuous between recharges This will vary with the ambient temperature ...

Page 2: ... It may be necessary to decrease the distance between the detector and the test lamp in order to obtain a response Do not operate the test lamp longer than is necessary to actuate the detector Each detector can be checked with less than 30 seconds of operating time It is important to avoid discharging the battery to the point where the battery charge level Indicating LED see Figure 2 is on steady ...

Page 3: ...window is off When the battery reaches a marginal level the Indicating LED will flash on and off The battery should be recharged at this time If the Indicating LED is on continuously the battery is at a very low level and the test lamp should not be operated until the battery has been recharged WARNING The life of the battery is significantly reduced if it is operated when the red LED is on contin...

Page 4: ...equipment transportation prepaid to the factory in Minneapolis ORDERING INFORMATION When ordering specify Part Number Description 004000 003 W867C3001 120 VAC 004000 004 W867C3002 220 VAC 2 pin Euro 004000 005 W867C3003 220 VAC 3 pin UK NOTE Includes test lamp with battery and charger For assistance in ordering please contact Detector Electronics Corporation 6901 West 110th Street Minneapolis Minn...

Reviews: