1.3
95-8574
6
SPECIFICATIONS
A partial list of system specifications is provided here.
For detailed specifications, refer to the applicable
manual for the device or contact the factory.
POweR SUPPly/BAtteRy ChARgeR—
Input: 120 volts ac, 60 Hz.
Output: 18 to 36 vdc (24 vdc, nominal), 10 amperes.
Refer to Table 1 for specifications of the EQ21XXPS
Series power supplies.
NOTe
Although components are rated 18 to 38 vdc,
the system output voltage has been rated at 18
to 36 vdc for maintaining ground fault monitoring
capabilities.
RelAy COntACt RAtIngS—
28 vdc or 120 vac at 5 amperes.
CeRtIFICAtIOn—
FM Approved per ANSI/NFPA 72-1996, National Fire
Alarm Code. Reference Figure 5 for FM Approval system
details. (Reference the specific product manuals for
detailed specifications.)
CURRent ReqUIReMentS—
Use Tables 2 and 3 to determine current requirements
at +24 vdc.
BACk-UP BAtteRy ReqUIReMentS—
Use Table 4 or Table 5 to determine the backup battery
amp hour requirement.
enClOSURe DIMenSIOnS—
See specific System Drawings for mounting
dimensions.
INSTALLATION
A set of System Drawings is supplied with each
system and is specific to that system. These
drawings detail system wiring, terminal assignments,
enclosure dimensions, standard symbols and wiring
specifications. Refer to these drawings when installing
the system. Dashed lines within the System Drawings
indicate wiring that must be completed in the field.
Installation of the Flame Detection/Releasing System
involves:
1. Mounting the enclosure that contains the prewired
system - mounting dimensions are included in the
System Drawings - Enclosure Mechanical Layout
sheet.
2. Installing and wiring the detector - system wiring
details are included in the System Drawings -
Detector Field Wiring sheet. Refer to the appropriate
Instruction Manual for detailed instructions on
locating, mounting and wiring the detectors:
X2200 UV Flame Detector with Pulse Output
95-8552
X9800 IR Flame Detector with Pulse Output
95-8555
X5200 UV/IR Flame Detector with Pulse Output 95-8547
X3301 IR Flame Detector with Pulse Output
95-8528
3. Installing and/or wiring other field devices (manual
pull stations, valves, annunciating/indicating/alarm
response devices, fire panels, etc.) - wiring details
are included in the System Drawings - UV System
R7404/R7494, R6006, R1425 Wiring sheets.
Characteristic
Power Supply
eq2110PS
(A36DAn-10A-24V-A1)
eq2130PS
(A36DAn-30A-24V-ABD1)
eq2175PS
(A36DAn-75A-24V-ABD1)
Input Voltage
120 vac
120/208/240 vac
120/208/240 vac
Input Current
4 Amps
11/5/6 Amps
26/13/15 Amps
Input Frequency
60 hz
60 or 50 hz
60 or 50 hz
Output Voltage Rating
24 vdc
24 vdc
24 vdc
Output Current Rating
10 Amps
30 Amps
75 Amps
Maximum Alarm Current
10 Amps
30 Amps
75 Amps
Maximum Standby Current
3.33 Amps
10 Amps
25 Amps
Battery Recharge Current
6.67 Amps
20 Amps
50 Amps
Maximum Battery Capacity
100 Amphours
300 Amphours
750 Amphours
Maximum Deluge Standby Current
1 Amp
3 Amps
7.5 Amp
table 1—Specifications of eq21xxPS Series Power Supplies