background image

1.3

95-8574

5

POwER SUPPLy/BaTTERy BaCkUP

The power supply/battery charger and backup batteries 

convert 120 vac supply voltage to +24 vdc (nominal), 

10 or 30 amperes to power the system.  This includes:
• + 24 volts dc, 10 or 30 amperes power supply/battery 

charger

• Two 12 vdc, sealed batteries connected in series.

If the backup batteries are not supplied by Det-Tronics, 

they must meet the requirements of Figure 5 and ANSI/

NFPA-72.

Refer  to  the  “Specifications”  section  for  current  and 

back-up battery requirements.

BaTTERy FaILURE DETECTOR

The  Battery  Failure  Detector  (BFD)  monitors  up  to 

four battery strings in real time.  Batteries can age or 

deteriorate  more  quickly  than  expected  due  to  high 

temperature, over-voltage, deep discharges, and other 

environmental  and  operating  conditions.    As  a  result, 

battery failures can occur, decreasing battery capacity 

and  the  ability  to  provide  the  necessary  system 

operating power.

The BFD monitors the overall battery voltage and the 

mid-point voltage of each battery string in the system.  

It reports an alarm if the monitored voltage is outside 

the acceptable limits, indicating a battery problem.

The front of the BFD has a set of four switches, a series 

of  eight  indicator  LEDs  and  a  4-digit  alphanumeric 

display.  The user interface menu is accessible using 

the switches and display on the front panel.  External 

connections are made at the back of the BFD.

mOUNTINg RaCk

The R7404, R7494, R6006, and R1425 Modules fit into 

a  mounting  rack,  which  is  located  within  the  system 

enclosure.  Two mounting rack types are available:

• Q4004  Universal  Mounting  Cage  -  standard  rack, 

holds all system modules (up to six) 

• Q1020  Wall  Mount  Metal  Enclosure  -  standard 

rack  inside  IP55  rated  enclosure  provides  added 

protection.

SySTEm ENCLOSURE

An  enclosure  is  provided  that  contains  the  external 

wiring  terminal  strip  and  the  mounting  rack  with  all 

R7404(s), R7494(s), the R6006, and the R1425 included.  

Refer to the System Drawings for details and mounting 

dimensions.

SYSTEM OPERATION

A brief description of a typical application is provided 

below.  Refer to the instruction manual for each device 

for more detailed operational information.

In a typical application of the Fire Detection/Releasing 

System,  a  fire  sensed  by  the  flame  detectors  and 

processed  by  the  R7404/R7494  Controller  will  cause 

an assigned R6006 relay to energize, providing a relay 

output to a fire panel.  At the same time, the fire signal 

will also cause the R1425 Detonator module to activate 

a deluge valve. Manual trip stations and heat detectors 

connect directly to the R1425, which will also cause the 

deluge valve to release when those alarms are tripped 

and provide a signal to the R6006, which in turn provides 

a relay output to the fire panel. Because each system is 

custom designed, input and output devices vary.  Refer 

to the System Drawings for further information.

B0640

1C

1B

1F

1A

1E

8

7

6

1D

2C

2B

2F

2A

2E

3

4

5

2D

Figure 4—R1425 Detonator Module Front Panel

Summary of Contents for Det-Tronics FDRS

Page 1: ...elay and detonation output devices into a single system Figure 5 In addition to the Det Tronics flame detectors the FDRS accepts inputs from devices such as heat and smoke sensors and manual trip stations The FDRS provides alarm and fault relay outputs a detonator output that provides high speed output for direct connection to a deluge valve and extinguishing agent release signals for connection t...

Page 2: ...hen used as a field replacement all operating features of the current controller are retained in addition to gaining the advanced features of the X Series detector In typical applications the four wire X Series detector can utilize all existing system wiring X Series Flame Detectors include the following X3301 Multispectrum IR Detector See Figure 1A X2200 UV Detector See Figure 1B X9800 IR Detecto...

Page 3: ...d provides a digital display of system status using a numerical code Other features include individual zone identification and voting capability as well as manual oi testing See Figure 2 Voting of 2 or more UV flame detectors is required for compliance to ANSI NFPA 72 to maintain ground fault monitoring integrity R7494 Controller The R7494 Controller is also used with all X Series Pulse Output Fla...

Page 4: ...T MODE 3 DIGITAL DISPLAY NORMALLY OFF TURNS ON TO INDICATE STATUS CHANGE AND RELAY AFFECTED 4 AMBER SYSTEM FAULT LED NORMALLY OFF ON TO INDICATE SYSTEM FAULT 5 GREEN POWER LED NORMALLY ON WHEN UNIT IS POWERED 6 RED FIRE RELAY LEDS NORMALLY OFF RELAY UN ENERGIZED BLINK WHEN RELAY ENERGIZED ON STEADY WHEN RELAY DE ENERGIZED 7 AMBER FAULT RELAY LED NORMALLY OFF RELAY ENERGIZED BLINKS WHEN RELAY DE EN...

Page 5: ...ack of the BFD Mounting Rack The R7404 R7494 R6006 and R1425 Modules fit into a mounting rack which is located within the system enclosure Two mounting rack types are available Q4004 Universal Mounting Cage standard rack holds all system modules up to six Q1020 Wall Mount Metal Enclosure standard rack inside IP55 rated enclosure provides added protection System Enclosure An enclosure is provided t...

Page 6: ...in the field Installation of the Flame Detection Releasing System involves 1 Mounting the enclosure that contains the prewired system mounting dimensions are included in the System Drawings Enclosure Mechanical Layout sheet 2 Installing and wiring the detector system wiring details are included in the System Drawings Detector Field Wiring sheet Refer to the appropriate Instruction Manual for detai...

Page 7: ...l Solenoid Load Valve Coil Total Signaling Load Total Alarm Current for System in Amperes Table 3 Alarm Current Requirements at 24 vdc Device Type No of Devices x Standby Current Total Current for Device Type X2200 x 0 104 X9800 x 0 087 X5200 x 0 116 X3301 x 0 167 R7404A B x 0 062 R7494 x 0 063 R6006 x 0 104 R1425 x 0 104 W2400 x 0 015 BFD x 0 160 Resistor Network Load x 0 012 Heat Sensor x Manual...

Page 8: ... R1425 Removal Replacement The R7404 R7494 R6006 and R1425 are not designed to be repaired in the field however field replacement can be accomplished by following the instructions below If a problem should develop first carefully check for proper wiring and switch settings If it is determined that the problem is caused by a defect in the module the device must be returned to the factory for repair...

Page 9: ... can be assigned A written statement describing the malfunction must accompany the returned device or component to expedite finding the cause of the failure thereby reducing the time and cost of the repair Pack the controller circuit boards using sufficient packing material in addition to an anti static bag or aluminum backed cardboard as protection from antistatic discharge Return all equipment t...

Page 10: ...NG DATE DATE ANGLE 1 0 0 0 00 0 00 0 000 01 005 CHECKED DRAWN REV DATE DATE ECO NO TOLERANCES ARE DESCRIPTION DETECTOR ELECTRONICS CORP 0 5 SIZE SCALE DRAWING NO MINNEAPOLIS MINNESOTA 55438 0 25 0 13 REV APPROVED DATE BATTERY FAILURE DETR CLARIFY 6458 C X9800 IR FLAME DETECTOR 007399 001 OR FAILURE RELAY BATTERY FAILURE DETECTOR ANSI NFPA 72 1999 CL 1 5 8 X2200 UV FLAME DETECTOR BFD 3 3 4 4 3 MODE...

Page 11: ...9 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 J2 J1 CONTROLLER INPUT MATRIX INPUT VOLTAGE TO DETONA TOR VOLTAGE TO DETONA TOR CONTROLLER INPUT MATRIX INPUT VOLTAGE TO DETONA TOR VOLTAGE TO DETONA TOR 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 6...

Reviews: