9.6.5. Evaluation of the external inspection is considered positive, if no leak fume pipes, doors,
cleaning vents lids, irregular and unverified controls and instrumentation, or bad pressure limiting
devices are found during the inspection.
9.7. In case of a negative evaluation of the technical maintenance inspection, boiler operation is
prohibited. The evaluation must be recorded in the boiler certificate.
9.8. After having eliminated the defects, prohibiting the use of the boiler, it shall be allowed to
continue working only after the repeat technical maintenance inspection at the maximum period
provided for in clause 2.3 of the Section.
9.9. Results of technical maintenance inspections on the boiler status, permits to its operation,
and due dates of next inspections must be recorded by an inspection executor to the boiler
certificate. The certificate must also include information about every boiler repairs implemented.
10. STORAGE AND TRANSPORTATION
10.1. Before boiler installation, it must be stored in dry premises. All boiler outlet connections
must be covered, the doors – closed and tightened. Control instrumentation, fittings, pressure
limiting devices (safety valves), a fan, supplied with the boiler, must be stored in a room at a
temperature of at least +5°C.
10.2. Do not load boilers on top of each other during their storage and transportation.
10.3. The upper part of the boiler is fitted with two lifting loops for boiler loading or unloading.
Boiler can be unloaded or loaded with an automatic or electric loader. In this case, the boiler must
rest upon the loader’s lifted part with its supports, located at the bottom of the boiler, but not
with the bottom structure.
10.4. If necessary, a boiler can be transported being placed on its side. In this case, remove a
decorative insulating sheath from the side on which the boiler is placed; as well, remove fire-
grates from the boiler furnace.
10.5. In any case of boiler transportation, it must be protected against atmospheric precipitation;
a fuel loading door, fume cleaning doors, and a boiler outgoing flue pipe must be well fixed and
tightened.
10.6. During boiler transportation, it is recommended to fix it to the vehicle body, in places,
uncovered by the decorative sheath, with special adjusting strips.
10.7. Control and instrumentation, electrical equipment, and other components are transported
being packaged, as provided by the manufacturer.