INSTALLATION AND OPERATION

INSTALLATION INSTRUCTIONS: CAUTION!! READ CAREFULLY.
CAUTION: THIS UNIT IS SEALED. THE COVER IS NOT REMOVABLE

!

• A mounting plate is provided on the back of the alarm.
• Remove the mounting plate from the back of the alarm by holding the mounting plate

and twisting the alarm in the direction indicated by the "TURN TO REMOVE" arrow on

the side of the alarm base.

•

Test  alarm  immediately  following  installation

  and  weekly  for  proper  operation  by

pushing the test button. The alarm will then test itself for proper operation and the red

LED indicator will flash on two 4-pulse patterns and the alarm will simultaneously sound

two 4-pulse patterns. The alarm then resumes normal operation.

Installation of this unit must conform to the electrical codes in your area; Article 760

of the National Electrical Code, NFPA 720/CO Alarms, NFPA 101; SBC (SBCCI); UBC

(ICBO); NBC (BOCA): OTFDC (CABO), and any other local or building codes that may

apply. Wiring and installation must be performed by a licensed electrician. Failure to

follow these guidelines may result in injury or property damage.
This unit must be powered by a 24-hour, 120V AC 60Hz circuit. Be sure the circuit

cannot be turned off by a switch, dimmer or ground fault circuit interrupter. Failure to

connect this unit to a 24-hour circuit may prevent it from providing constant protection.

ELECTRICAL SHOCK HAZARD

Turn off power to the area where you will install this unit at the circuit breaker or fuse

box before beginning installation. Failure to turn off the power before installation

may result in serious electrical shock, injury or death.

TAMPER LOCKING PIN:

 To make your alarm somewhat tamper resistant, a locking pin

has been provided. Using this pin will deter children and others from removing the alarm

from the mounting plate. To use the pin, insert it into the hole in the side of the alarm after

it has been installed on the mounting plate. Using long nose pliers, pull the pin out of the

hole. It is now possible to remove the alarm from the mounting plate.
1. Turn the alarm counterclockwise in the direction indicated by the "TURN TO REMOVE"

arrow on the side of the alarm base to remove it from the mounting plate. NOTE: The

alarm is sealed and the cover is not removable.

2. Wiring Instructions:

a. The appropriate power supply is 120 Volt single phase power supplied from a non-

switchable circuit NOT protected by a ground fault circuit interrupter.

b. Turn off main power to the circuit before wiring the alarm.

c. There are three pigtail leads (black, white and yellow) coming from the AC QUICK

CONNECTOR. The proper wire connection is as follows:

WIRES FROM QUICK CONNECTOR

CONNECT TO

BLACK

"HOT" side of AC line

WHITE

"NEUTRAL" side of AC line

YELLOW

Interconnect wires of other units

For units that are used as single  alarms, do not connect the yellow wire to anything.

Insulate this wire (tape it) in place to make certain the yellow wire cannot contact any

metal parts.
Interconnected units can provide earlier warning than stand-alone units, especially if

dangerous CO (carbon monoxide) levels start in a remote area of the dwelling. This

unit will interconnect with ALL USI ELECTRIC AC carbon monoxide alarms, smoke

alarms, heat alarms and relay modules. A maximum of 18 units can be interconnected,

but there can be no more than 12 interconnected smoke alarms.

Page 5

All manuals and user guides at all-guides.com

Summary of Contents for USI-7390

Page 1: ...intended for use in ordinary indoor locations of family living units It is not designed to measure compliance with Occupational Safety and Health Administration OSHA commercial or industrial standards...

Page 2: ...Make sure that motor vehicles are not and have not been operating in an attached garage or adjacent to the residence INSTALLING THE ALARM FOR RESIDENTIAL USE LOCATION One of the most important conside...

Page 3: ...ts are used Excessive spillage or reverse venting of fuel burning appliances caused by outdoor ambient conditions such as Wind direction and or velocity including high gusts of wind Heavy air in the v...

Page 4: ...ral gas propane or butane heat smoke or flames NOTE This CO alarm is designed for use within a single residential living unit only In a multi family building the alarm may not provide early warning fo...

Page 5: ...k injury or death TAMPER LOCKING PIN To make your alarm somewhat tamper resistant a locking pin has been provided Using this pin will deter children and others from removing the alarm from the mountin...

Page 6: ...RESET button and check the LED s for proper operation see TESTING YOUR ALARM After test sequence the green LED lights to indicate AC power and blinks off approximately every 20 seconds to indicate pro...

Page 7: ...attery drawer out While observing polarity push the replacement battery into the battery drawer until it is held securely in place Carefully close and latch the QUICK DRAWTM pull out battery drawer US...

Page 8: ...the costs of return postage and handling You must include a proof of purchase receipt along with the returned product USI DOES NOT WARRANT AND SPECIFICALLY DISCLAIMS ANY WARRANTY WHETHER EXPRESS OR IM...

Reviews: