background image

•  Install an alarm in every family living unit containing a fuel-burning appliance, fireplace, or 

an attached garage.

•  Alarms should be centrally located outside of each separate sleeping area in the immediate vi-

cinity of the bedrooms. Where bedrooms are separated and audibility of the alarm to occupants 

within the bedroom area could be seriously impaired, more than one alarm may be needed.

•  Protect the escape route, as the bedrooms are usually farthest from an exit. If more than 

one sleeping area exists, locate additional alarms in each sleeping area. If a hall is more 

than 40 feet (12 meters) long, install an alarm at each end of the hallway.

•  Add additional alarms to protect any stairway, as stairways may act like chimneys for 

smoke and heat.

•  Locate at least one alarm on every floor level.
•  Locate an alarm in any area where a smoker sleeps or where electrical appliances are 

operated in sleeping areas.

•  Smoke, heat and other combustion products rise to the ceiling and spread horizontally.  

Mounting the alarm on the ceiling in the center of the room places it closest to all points in 

the room. Ceiling mounting is preferred in ordinary residential construction. However, in 

mobile homes, wall mounting on an inside partition is preferred to avoid the thermal barrier 

that may form at the ceiling. 

•  When mounting the alarm on a wall, if local codes allow, use an inside wall with the top 

edge of the smoke alarm a maximum of 6” (15.2cm) below the ceiling/wall intersections 

(See Diagram A).

Existing Homes:

The NFPA requires smoke alarms or combination alarms on every level and outside each 
sleeping area in existing construction. An existing household with one level and one sleeping 
area is required to have one smoke alarm.

New Construction Homes and Manufactured Homes:

The NFPA requires AC-powered, interconnected smoke alarms to be installed inside each 
bedroom, outside each bedroom area, and on every level of the home. They also require  
a minimum of two AC-powered, interconnected smoke alarms or combination alarms in any 
new construction home.

Sloped Ceilings (Peaked Ceilings):

Smoke alarms or combination alarms mounted on a peaked ceiling shall be located within  
36 in. (914 mm) horizontally of the peak, but not closer than 4 in. (102 mm) vertically to the peak.

Sloped Ceilings (Shed Ceilings):

Smoke alarms or combination alarms mounted on a sloped ceiling having a rise greater than 
1 ft. in 8 ft. (1 m in 8 m) horizontally shall be located within 36 in. (914 mm) of the high side of 
the ceiling, but not closer than 4 in. (102 mm) from the adjoining wall surface.

Tray-Shaped Ceilings:

Smoke Alarms or combination alarms shall be installed on the highest portion of the ceiling 
or on the sloped portion of the ceiling within 12 in. (305 mm) vertically down from the highest 
point.

Page 4

Ceiling

Acceptable

Top of detector

acceptable here

Sidewall

12 in.

(300 mm)

maximum

Note: Measurements shown are to 

the closest edge of the detector.

DIAGRAM A 

Summary of Contents for MPC122S

Page 1: ...ere This Alarm Should Not Be Installed 5 Mounting Instructions 6 Tamper Resistant Alarm Locking Feature 6 Wiring Instructions 7 Stand Alone Alarm Installations 7 Interconnected Alarm Installations 8 I...

Page 2: ...a safer greener alternative Quick Find Alarm Origination Feature easily identifies first alarm to sound in an intercon nected system ALARM LIMITATIONS AND FUNCTIONS IMPORTANT ALARMS WILL NOT WORK WITH...

Page 3: ...e who may not be awakened by the alarm sound or to those who may be incapable of safely evacuating the area unassisted ALARMS ARE NOT FOOLPROOF Test alarms weekly to ensure continued protection ALARMS...

Page 4: ...ide wall with the top edge of the smoke alarm a maximum of 6 15 2cm below the ceiling wall intersections See Diagram A Existing Homes The NFPA requires smoke alarms or combination alarms on every leve...

Page 5: ...allation in hazardous locations as defined in the National Elec trical Code To avoid causing damage to this alarm to provide maximum protection and to prevent unnecessary alarms DO NOT LOCATE THIS ALA...

Page 6: ...tions in or unconventional vent pipe designs which can amplify the above situations These placement recommendations are intended to keep alarms at a reasonable distance from a fuel burning source and...

Page 7: ...will damage the alarm Installation of this alarm must conform to the electrical codes in your area Article 760 of the National Electrical Code NFPA 72 101 SBC SBCCI UBC ICBO NBC BOCA OTFDC CABO and an...

Page 8: ...multiple alarms INTERCONNECTED ALARMS INSTALLATION The wiring to be used shall be in accordance with the provisions of Articles 210 and 300 3 B of the National Electrical Code ANSI NFPA 70 NFPA 72 and...

Page 9: ...f the dwelling When alarms are interconnected all alarms will sound when one alarm first sounds To prevent damage do not connect this alarm to any other type of alarm or auxiliary device Connecting in...

Page 10: ...tectors Model 501 A or 501 A Bat Aerosol Generator Manufactured by Gemini Scientific Corp 1122 B Aster Ave Sunnyvale CA 94086 The Equivalent UL 268 Light obscuration ft as measured by this instrument...

Page 11: ...system after all the alarms have stopped sounding 1 Press and release the test silence button on any interconnected alarm After releasing the button the test sequence will sound on all the interconnec...

Page 12: ...alarm You might accidentally damage or set fire to the alarm or to your home CAUTION Continuous exposure to the high sound level of this alarm over an extended period of time may cause hearing loss Du...

Page 13: ...D KNOW ABOUT CO Carbon monoxide CO is an insidious poison It is a colorless odorless tasteless gas It is a cumulative poison Even low levels of CO have been shown to cause brain and other vital organ...

Page 14: ...ur ers instructions or contact the manufacturer s directly for more information about CO safety and this equipment Make sure that motor vehicles are not and have not been operating in an attached gara...

Page 15: ...Check the color of the flame on the burner and pilot lights to ensure they are burning properly They should be blue If the flame is orange or yellow it is a sign the fuel is not burning completely and...

Page 16: ...ian for assistance Test the alarm following installation and weekly thereafter The built in test switch accurately tests the alarm operation as required byANSI UL217 and UL2034 Standards for Safety If...

Page 17: ...utton for 10 15 seconds and then release This will clear the alarm origination and latching LED Be sure to RESET alarms after every alarm event QUICK FIND Alarm Origination Location Feature The QUICK...

Page 18: ...warranty on this product created by state law shall extend beyond the term of this warranty unless such law otherwise provides USI specifically disclaims any liability and shall not be liable for any...

Reviews: