DS1043-218 

 

Jumpers 

 

JP1: 

Closed

the internal short-circuit isolator of the base is shorted. To be closed when the base is 

power supplied and controlled by a fire alarm signalling circuit of a fire detection control panel. 

Open: default setting. 

Note

:  the  JP1  jumper  must  be  closed  during  the  walk  addressing  procedure  and  at  the  end  it  must  be 

removed. 
 

JP2: 

Closed: default setting. 

Open:

 power off the base. 

Note

: the JP2 jumper must be removed for a few seconds during the walk addressing procedure; see the 

control panel programming manual. 
 

JP3: 

Closed

The  addressable  base  is  used  in  stand-alone  mode.  To  be  closed  when  the  base  is 

power supplied and controlled by a fire alarm signalling circuit of a fire detection control panel. 

Open: default setting. 

The addressable base is used in conjunction with a detector.

 

Note

:  the  JP3  jumper  must  be  closed  during  the  walk  addressing  procedure  and  at  the  end  it  must  be 

removed. 
 

Micro-switches 

 

DS-1 Position 

Connections 

ON 

The base is connected to a fire alarm signalling circuit of a fire 
detection control panel 

OFF (*) 

The base is connected to a detection circuit of an URMET 
1043/5X0 series fire detection control panel 

 

DS-2 Position 

Alarm optical signalling 

ON (*) 

The alarm optical signalling is enabled 

OFF 

The alarm optical signalling is disabled 

 

DS-3 

Position 

DS-4 

Position 

Sound volume 

OFF 

OFF 

Volume 0 - sound disabled (

1

ON 

OFF 

Volume 1 - low 

OFF 

ON 

Volume 2 - medium 

ON (*) 

ON (*) 

Volume 3 - high 

 

DS-5 

Position 

DS-6 

Position 

Tones 

OFF 

OFF 

Tone 1 - frequency sweep 800

970Hz in 1s 

ON 

OFF 

Tone 2 - two tones 610Hz for 0,5s and 920Hz for 0,5s 

OFF 

ON 

Tone 3 - pulsed 920Hz for 0,5s ON and for 0,5s OFF 

ON (*) 

ON (*) 

Tone 4 - continuous 920Hz 

 

DS-7 Position 

Initial synchronization of alarm activation 

ON 

Initial activation synchronized with other bases on the same 
circuit 

OFF (*) 

Initial activation non synchronized 

 

DS-8 Position 

Base configuration 

ON 

Configuration defined by the control panel (from software rev. 13) 

OFF (*) 

Configuration defined by the micro-switches 

(*) Default setting, (

1

) Not compliant with EN54-3 

Summary of Contents for 1043/512

Page 1: ...DS1043 218 LBT20173 DISPOSITIVO SONORO DI ALLARME INCENDIO FIRE ALARM DEVICE SOUNDER Sch Ref 1043 512 INSTALLAZIONE INSTALLATION Mod 1043 1293 16...

Page 2: ...di segnalazione allarme incendio uscita sirena di una centrale rivelazione incendio INDIRIZZAMENTO E PROGRAMMAZIONE L indirizzo della base 1 128 impostato via software tramite la centrale di rivelazio...

Page 3: ...sizione Collegamenti ON La base collegata ad una uscita di segnalazione allarme incendio di una centrale rivelazione incendio OFF La base collegata su una linea rivelazione di una centrale rivelazione...

Page 4: ...latore alla base COLLEGAMENTI Linea rivelazione Utilizzare un cavo schermato collegare lo schermo del cavo solo alla massa della centrale se il collegamento a loop collegare lo schermo di una sola est...

Page 5: ...0 0Hz cadenza 1Hz Continua 920Hz Frequenza di lampeggio 0 5Hz LED bi colore Verde lampeggiante lento 2s stato normale Verde lampeggiante veloce indirizzo duplicato Verde Rosso lampeggiante visualizzaz...

Page 6: ...i Regolazione in loco del comportamento mezzi speciali richiesti impostazioni marcate chiaramente Livello di pressione acustica LpA 65 dB A LpA valore dichiarato in tutti gli angoli misurati Frequenze...

Page 7: ...l panel ADDRESSING AND PROGRAMMING The address of the base 1 128 is configured via software by using the fire control panel with automatic or manual procedure The address is stored into the device in...

Page 8: ...emoved Micro switches DS 1 Position Connections ON The base is connected to a fire alarm signalling circuit of a fire detection control panel OFF The base is connected to a detection circuit of an URM...

Page 9: ...the cap CONNECTIONS Detection circuit A shielded cable must be used connect the shield of the cable one end in a loop mode to the ground in the control panel only and connect the shield between a devi...

Page 10: ...0Hz cadence 1Hz Pulsed 920 0Hz cadence 1Hz Continuous 920Hz Blinking frequency 0 5Hz Bi Colour LED Green blinking slow 2s normal condition Green blinking fast duplicate address Green Red device addres...

Page 11: ...turer s adjustment special means required On site adjustment of behaviour special means required setting clearly marked Sound pressure level LpA 65 dB A LpA declared value at all measured angles Frequ...

Page 12: ...12 DS1043 218 60 72 IN IN OUT OUT JP2 JP1 JP3 DS 1 DS 8 A Dima di foratura e disposizione predisposizioni Drill template and settings position...

Page 13: ...HIELD SCHERMO SHIELD IN IN OUT OUT IN IN OUT OUT LA LA LB LB CENTRALE LINEA RIVELAZIONE CONTROL PANEL DETECTION CIRCUIT SCHERMO SHIELD SCHERMO SHIELD IN IN OUT OUT IN IN OUT OUT Loop Circuito Aperto O...

Page 14: ...PUT IN IN OUT OUT IN IN OUT OUT RESISTORE DI FINE LINEA END OF LINE RESISTOR ULTIMO DISPOSITIVO LAST DEVICE Connessioni elettriche Uscita sirena Electrical connections Siren output Riferimento Referen...

Page 15: ...DS1043 218 15 Montaggio della rivelatore sulla base Detector mounting on the base Montaggio della coperchio sulla base Cap mounting on the base...

Page 16: ...73 DS1043 218 Area tecnica servizio clienti 39 011 23 39 810 http www urmet com e mail info urmet com MADE IN ITALY URMET S p A 10154 TORINO ITALY VIA BOLOGNA 188 C Telef 39 011 24 00 000 RIC AUT Fax...

Reviews: