Setting
Display
Set Heat Room
Set the room heating
temperature for the
event.
Access Level:
Installer, User
Range: 40 to 95°F
(4.5 to 35.0°C)
Conditions: Room
Sensor On or Sensor
1 or 2 is set to Room.
Default: 70°F (21.0°C)
Set Heat
Room
Set the room heating
temperature
for the event.
Access Level:
Installer, User
Range: 40 to 95°F
(4.5 to 35.0°C)
Conditions: Room
Sensor On or Sensor
1 or 2 is set to Room
and Schedule is set
to On.
Default: 65°F (18.5°C)
Set Cool Room
Set the room cooling
temperature for the
event.
Access Level:
Installer, User
Range: 50 to 100°F
(10.0 to 38.0°C)
Conditions: Room
Sensor On or Sensor
1 or 2 is set to Room.
Default: 78°F (25.5°C)
Set Cool Room
Set the room cooling
temperature for the
event.
Access Level:
Installer, User
Range: 50 to 100°F
(10.0 to 38.0°C)
Conditions: Room
Sensor On or Sensor
1 or 2 is set to Room
and Schedule is set
to On.
Default: 85°F (29.5°C)
Setting
Display
Set Floor
Set the floor heating
temperature for the
event.
Access Level:
Installer, User
Range: OFF, 40 to
122°F (OFF, 4.5 to
50.0°C)
Conditions:
Sensor 1 or 2 is set
to Floor.
Default: 72°F (22.0°C)
Set Floor
Set the floor heating
temperature for the
event.
Access Level:
Installer, User
Range: OFF, 40 to
122°F (OFF, 4.5 to
50.0°C)
Conditions: Sensor
1 or 2 is set to Floor
and Schedule is set
to On.
Defaults: Air & floor
sensors: 65°F (18.5°C)
Floor sensor only: OFF
Set Floor
Maximum
Set the maximum
floor heating tem-
perature.
MAX
Access Level: Installer Range: 40 to 122°F,
OFF (4.5 to 50.0°C,
OFF)
Conditions:
Sensor 1 or 2 is set to
Floor.
Default: 85°F (29.5°C)
Set Temperature Menu
16
uponorpro.com