Uponor SetPoint 501 Installation And Operation Manual Download Page 8

Section 4 

Troubleshooting

Error Messages

E01

The controller was unable to read a piece of 

information stored in its memory and was required

to load the factory settings. The controller will

stop operation until all settings are checked. To

clear this error, select the Installer access level 

and check all of the settings in the Adjust menu.

(See 

Figure 22

.)

E02

There are no active sensors selected on the 

controller. Either turn on the internal sensor or 

set the auxiliary sensor to INDR or SLAB. After

correcting the fault, press any button to clear 

the error message. (See 

Figure 23

.)

ROOM Shr

The controller’s internal air sensor has a short 

circuit. This error cannot be repaired in the field.

Replace or return the controller for repair. 

(See 

Figure 24

.)

ROOM OPN

The controller’s internal air sensor has an open 

circuit. This cannot be repaired in the field. 

Either turn off the internal sensor and set an 

auxiliary sensor to INDR, or replace the controller

and return the faulty controller for repair. After

correcting the fault, press any button to clear 

the error message. (See 

Figure 25

.)

11

Section 4 — Troubleshooting

Figure 22

Figure 23

Figure 24

Figure 25

ROOM HEAT

This displays the desired temperature for heating

(must set active air sensor to Heat or Auto). 

(See 

Figure 15

.)

35 to 100°F (2 to 38°C)

SLAB MIN (501s Only)

This displays the minimum slab or floor 

temperature (one active slab sensor required). 

(See 

Figure 16

.)

OFF, 34 to 122°F (OFF, 1 to 50°C)

SLAB MAX (501s Only)

This displays the maximum slab or floor 

temperature (one active air sensor required). 

This is only available when in the Installer access

level. (See 

Figure 17

.)

34 to 122°F, OFF (1 to 50°C, OFF)

SENS (501s Only)

This selects the type of optional sensor present

(only available in the Installer access level). 

(See 

Figure 18

.)

OFF, Indr, SLAB, OUT

ROOM SENS (501s Only)

This enables or disables the built-in sensor 

(only available in the Installer access level). 

(See 

Figure 19

.)

OFF, ON

CYC HEAT (501s Only)

This displays the number of cycles per hour 

for heating (only available in the Installer access

level). (See 

Figure 20

.)

AUTO, 2 to 12

UNITS

This displays the units of temperature used. 

(See 

Figure 21

.)

°F, °C

10

Figure 16

Figure 17

Figure 18

Figure 19

Figure 20

Figure 21

Figure 15

Summary of Contents for SetPoint 501

Page 1: ...739 Fax 952 891 1409 Web www uponor usa com E mail learnmore uponor usa com Uponor Ltd 655 Park Street Regina SK S4N 5N1 Tel 888 994 7726 Fax 800 638 9517 Web www uponor ca E mail info uponor ca INSTA...

Page 2: ...ration 8 Mode 8 Section 3 Navigating the Menus View Menu 9 Adjust Menu 9 Section 4 Troubleshooting Error Messages 11 Section 5 Technical Data SetPoint 501 13 SetPoint 501s 14 SetPoint 501 and 501s Con...

Page 3: ...lers are microprocessor based controls that are designed to sense the air temperature in a specific area and increase the comfort level of that area as well as increase the energy efficiency of the he...

Page 4: ...tic tab and pull the top of the front cover so that it pivots around the bottom edge of the base See Figure 1 Mounting the Base 1 Install the controller on an interior wall of the desired zone approxi...

Page 5: ...e controller 1 Connect the 24VAC power to the R and C terminals on the controller This connection provides power to the microprocessor and display of the controller 2 When wiring an optional sensor to...

Page 6: ...settings in the controller including those required to match the controller to the mechanical system and devices The User access level allows the end user to adjust the temperature settings 7 Section...

Page 7: ...an air sensor the on time for the Heat relay is calculated to satisfy the requirements of the air sensor Slab or Floor Sensor Only Operation 501s Only When operating with only a slab or floor sensor...

Page 8: ...rrecting the fault press any button to clear the error message See Figure 25 11 Section 4 Troubleshooting Figure 22 Figure 23 Figure 24 Figure 25 ROOM HEAT This displays the desired temperature for he...

Page 9: ...31 F 30 to 55 C 90 RH non condensing Power Supply 24VAC 10 50 60 Hz 1 VA Relay 24VAC 2 A 13 Section 5 Technical Data SENS Shr The optional sensor has a short circuit Locate and repair the problem as d...

Page 10: ...21mm Approvals CSA C US meets ICES and FCC regulations for EMI RFI Ambient Conditions Indoor use only 22 to 131 F 30 to 55 C 90 RH non condensing Adjustment Range 34 to 122 F 1 to 50 C for Slab or Fl...

Reviews: