background image

Section 3 

Navigating the Menus

View Menu

ROOM TARGET

This displays the current desired air temperature

for the space (one active air sensor required). This

is only available when in the Installer access level. 

(See 

Figure 10

.) 

ROOM

This displays the current air temperature for the 

space that is the average of all active air sensors

(one active air sensor required). (See 

Figure 11

.)

OUTDOOR (501s Only)

This displays the current temperature at the 

outdoor sensor. An outdoor sensor must be 

installed for this menu to function. 

(See 

Figure 12

.)

Note:

SENS must be set to OUT.

SLAB (501s Only)

This displays the current slab or floor temperature

(one active air sensor required). If two slab or 

floor sensors are present, this is the average 

temperature. MIN is displayed when the slab or 

floor minimum temperature is calling for heat. 

The slab or floor sensor may call for heat even 

though the room setpoint temperature is satisfied.

(See 

Figure 13

.)

Adjust Menu

MODE

This displays the current mode of operation of 

the thermostat. (See 

Figure 14

.)

OFF, HEAT

9

Section 3 — Navigating the Menus

Figure 10

Figure 11

Figure 12

Figure 13

Figure 14

Sequence of Operation

Air Sensor Only Operation

When operating with only an air sensor, the on time for the Heat relay is

calculated to satisfy the requirements of the air sensor.

Slab or Floor Sensor Only Operation (501s Only)

When operating with only a slab or floor sensor, the on time for the Heat

relay is calculated to satisfy the requirements of the slab or floor sensor.

The controller operates to maintain the slab at the minimum slab 

temperature setting.

Note:

Using only a slab or floor sensor may cause overheating or 

underheating of the space.

Air and Slab or Floor Sensor Operation (501s Only)

When operating with both air and slab or floor sensors, the controller 

calculates an on time for the Heat relay to satisfy the slab or floor sensor’s

requirements and an on time to satisfy the air sensor’s requirements. The

Heat relay operates for the longer of these two on times.

During light heating loads, overheating can occur due to the minimum slab

or floor temperature requirements.

During heavy heating loads, the maximum slab or floor temperature 

setting limits the on time of the Heat relay. In this situation, underheating

can occur.

Mode

Heat

In the heat mode, the Heat relay satisfies the temperature requirement of

the zone.

Off 

The Heat relay does not operate in the Off mode.

Note:

If an air, slab or floor sensor is active in the Off mode, a freeze-

protection function enables, allowing the Heat relay to operate 

and keep the zone above 35°F (2°C).

8

Summary of Contents for SetPoint 501

Page 1: ...739 Fax 952 891 1409 Web www uponor usa com E mail learnmore uponor usa com Uponor Ltd 655 Park Street Regina SK S4N 5N1 Tel 888 994 7726 Fax 800 638 9517 Web www uponor ca E mail info uponor ca INSTA...

Page 2: ...ration 8 Mode 8 Section 3 Navigating the Menus View Menu 9 Adjust Menu 9 Section 4 Troubleshooting Error Messages 11 Section 5 Technical Data SetPoint 501 13 SetPoint 501s 14 SetPoint 501 and 501s Con...

Page 3: ...lers are microprocessor based controls that are designed to sense the air temperature in a specific area and increase the comfort level of that area as well as increase the energy efficiency of the he...

Page 4: ...tic tab and pull the top of the front cover so that it pivots around the bottom edge of the base See Figure 1 Mounting the Base 1 Install the controller on an interior wall of the desired zone approxi...

Page 5: ...e controller 1 Connect the 24VAC power to the R and C terminals on the controller This connection provides power to the microprocessor and display of the controller 2 When wiring an optional sensor to...

Page 6: ...settings in the controller including those required to match the controller to the mechanical system and devices The User access level allows the end user to adjust the temperature settings 7 Section...

Page 7: ...an air sensor the on time for the Heat relay is calculated to satisfy the requirements of the air sensor Slab or Floor Sensor Only Operation 501s Only When operating with only a slab or floor sensor...

Page 8: ...rrecting the fault press any button to clear the error message See Figure 25 11 Section 4 Troubleshooting Figure 22 Figure 23 Figure 24 Figure 25 ROOM HEAT This displays the desired temperature for he...

Page 9: ...31 F 30 to 55 C 90 RH non condensing Power Supply 24VAC 10 50 60 Hz 1 VA Relay 24VAC 2 A 13 Section 5 Technical Data SENS Shr The optional sensor has a short circuit Locate and repair the problem as d...

Page 10: ...21mm Approvals CSA C US meets ICES and FCC regulations for EMI RFI Ambient Conditions Indoor use only 22 to 131 F 30 to 55 C 90 RH non condensing Adjustment Range 34 to 122 F 1 to 50 C for Slab or Fl...

Reviews: