INSTALLATION 

&

 

USER’S GUIDE

®

CDMAEX

®

CDMA Primary Cellular

Alarm Communicator

Summary of Contents for CDMAEX

Page 1: ...INSTALLATION USER S GUIDE CDMAEX CDMA Primary Cellular Alarm Communicator...

Page 2: ...ronic or mechanical means such as photocopying recording or information storage and retrieval systems The material in this manual is subject to change without notice Uplink reserves the right to make...

Page 3: ...23 A General Considerations 11 B DIP Switch Settings 11 C LEDs 12 13 D Locating and Installing the CDMAEX 14 15 E Connecting the CDMAEX to the Alarm Panel 16 17 F Configuring Input 1 18 19 G Activatin...

Page 4: ...places the phone line connection The Uplink CDMAEX unit will intercept the alarm panel s digital dialer output when the panel has an event to report and communicate with the panel as if it were a cent...

Page 5: ...ugh the website www uplink com or by calling Uplink Customer Service 1 888 9 UPLINK 1 888 987 5465 D Input The CDMAEX has one programmable input This input can be programmed to one of the following fu...

Page 6: ...te the current operational status and are visible from outside the enclosure These LEDs can be placed into Received Signal Strength Indication mode RSSI to assist in selecting the optimal mounting loc...

Page 7: ...hased the product Distributors dealers and installers with questions about Uplink s warranty and returns process are directed to contact Uplink Order Entry issuance of a Return Merchandise Authorizati...

Page 8: ...PLINK ARISING OUT OF OR RELATED TO AN UPLINK PRODUCT AND OR SERVICE WHETHER ARISING OUT OF OR RELATED TO BREAK OF CONTRACT TORT INCLUDING WITHOUT LIMITATION NEGLIGENCE OR PRODUCT LIABILITY OR OTHERWIS...

Page 9: ...l installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communicat...

Page 10: ...ly set by both U S and international standards bodies The design of this module complies with the FCC guidelines and these international standards The FCC ID of this unit is QIPPHS8 US For more inform...

Page 11: ...8 00 PM ET excluding holidays Before calling technical support please ensure you have read the installation guide completely Technical support requires the caller to provide Login name Password Seria...

Page 12: ...on that gives him the best signal strength b Proximity to the alarm panel and where to route the CDMAEX s relay output that connects to an alarm panel input B DIP Switch Settings The CDMAEX has a four...

Page 13: ...12 CDMA Primary Cellular Alarm Communicator CDMAEX INSTALLATION cont C LEDs Normal Mode Upon initial power up the 5 LEDs on the CDMAEX will begin to function as follows...

Page 14: ...information GOOD UNACCEPTABLE MINIMUM ACCEPTABLE INSTALLATION continued next page RECEIVED SIGNAL STRENGTH OFF FLASH ON LED1 LED2 LED3 LED4 LED5 GREEN 70dBm GREEN LED1 LED2 LED3 LED4 LED5 GREEN 60dBm...

Page 15: ...appropriate for this installation See DIP Switch Settings page 12 4 Place Dipswitch 4 S4 in the ON position The LEDs are now operating in RSSI Mode Locate a good mounting position based on a good Rece...

Page 16: ...ommunicator CDMAEX INSTALLATION cont FIGURE 1 Model CDMAEX PC Board Details STATUS LEDS INPUT OUTPUT DC TERMINAL BLOCK INSTALLATION continued next page CAUTION Incorrect Connections May Result in Dama...

Page 17: ...used to activate a keyswitch zone on the alarm panel for arm disarm with Uplink Remote or for other local purposes Decide on how to use this output see section 6 Programming then wire it from the ter...

Page 18: ...witch Setting Off On Function Normal Operations Load Defaults Off On Off On Off On Allow OTA Config Block OTA Config Reserved Normal Operations Normal Operations RSSI Measurements IN1 IN1 OUT1 OUT1 Up...

Page 19: ...s a fire signal and a steady voltage as a burglary signal It may be necessary to place a 1K Ohm resistor in parallel to prevent false alarms when using panels with supervisory voltage on the bell circ...

Page 20: ...if set for standard input can be tripped by applying 12 V to the input and 0 V to the input A signal must be continuously present for 500 ms FIGURE 4 Wiring example for open collector trip Open Collec...

Page 21: ...terms of the Activation Agreement 4 Enter the device serial number and select Activate 5 If you are offering Remote Services enroll the unit in Uplink Remote 6 You will be directed to the Edit Unit Se...

Page 22: ...ult 1 OUT1 De energized Open The normal state of the Output Relay can be changed from the dealer website 4 Output Relay 1 Mapping Default 1 Unmapped There are 8 trouble states that can be declared by...

Page 23: ...pted the panel s digital dialer output and reported the event to the central monitoring station c If using the Output Relay on the CDMAEX go back to the dealer website and use the Switch Output Relay...

Page 24: ...e voltage 48 V DC On Hook Dial tone 350 440 Hz 0 2 Receive level minimum 45 dBm 20 dBm S N Line impedance 600 ohms Ringer Equivalence 0 3 REN Mode Loop start 26 mA typical POWER REQUIREMENTS Input Vol...

Page 25: ...mmunicator CDMAEX SPECIFICATIONS CONT RADIO Frequencies 850 1900 MHz Sensitivity 106 dB typical ENVIRONMENTAL Temperature Range 30 to 70 C Humidity 0 to 95 non condensing PHYSICAL Height 2 5 inches Wi...

Page 26: ...ail E301 AT 48 AC Restoral R301 AR 49 Alarm generic E140 UA 10 Burglary Alarm E130 BA 10 Burglary Restoral R130 BR 12 Burglary Tamper E137 TA 10 Burglary Tamper Restoral R137 TR 12 Closing R400 CL 32...

Page 27: ...g E400 OP 2F Panic Alarm E120 PA 10 Panic Restoral R120 PR 12 Phone Fail E350 LT 44 Phone Restoral R350 LR 45 Radio Supervision Lost E355 YC 11 Radio Supervision Restoral R355 YK 12 Restoral generic R...

Page 28: ...t event codes sent by the CDMAEX EVENT DESCRIPTION CONTACT ID EVENT CODE SIA DC 03 EVENT CODE MODEM IIE LLLA2 ZONE NO REPORTED Low DC Voltage E302 YT 4B 240 Low DC Restoral R302 YR 4C 240 Cable Superv...