4550-CF
INTRODUCTION
Uplink’s MODEL 4550-CF GSM Alarm Communicator is a UL Listed alarm and
critical event communicator designed to interface with most manufacturers’ alarm
panels that incorporate a digital telephone dialer. The 4550-CF features a “dialer
capture” interface to a Firelite Model MS5UD alarm panel. If the alarm panel’s
TELCO connection is compromised, or if no TELCO connection is present, the
4550-CF will “intercept ” the alarm panel’s digital dialer output when the panel has
an event to report, and communicate with the panel as if it were a central station
alarm receiver. Once the 4550-CF communicates with the alarm panel, it transmits
the alarm information to the central station receiver in Contact ID (SIA-DC05), SIA
(SIA-DC03), Pulse 4+2, DMP, or Modem IIe/IIIa/IIIa
2
formats.
The 4550-CF uses GSM technology to receive programming and send event
information to the central station and can be used as the primary or backup
communications path as a digital dialer (or DACT).