38
4G CELLULAR
ALARM COMMUNICATOR
UL COMPLIANCE SECTION
PART 1– INSTALLATION
REQUIREMENTS (cont.)
20. Text messaging and emailing for the purposes of notification can only be
used for supplementary service. programmed to display the message “For
trouble see panel” or similar. Furthermore, the Loss of Cellular Service must be
programmed, via the website, to annunciate locally within 2 minutes.
21. The LEDs inside of the unit are for installer use only.
22. The 4550-CF contains no user-serviceable parts. Batteries must be tested
semi-annually and replaced within 5 years of manufacture or more frequently
as needed.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software which can be changed
over the GSM Wireless connection. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm
Systems, UL 864, certain programming features or options must be limited to
specific values.
The list of possible modifiable configuration options, as well as the proper
settings to maintain UL 864 Compliance, is listed in
Section 9: UL Compliance
Section Part 2: Table 90.23 Programming Requirements: Web-configurable parameters for
UL 864 compliance.