34
4G CELLULAR
ALARM COMMUNICATOR
UL COMPLIANCE SECTION
PART 1– INSTALLATION
REQUIREMENTS (cont.)
c. Installers shall interconnect the pull box and 4550-CF with conduit
and wire the supplied ELK TRG1640 Transformer to the 4550-CF in
accordance with local Authorities Having Jurisdiction requirements.
d. Installers shall plug the transformer into the 120VAC receptacle and secure
the transformer as shown in Figure 4 above.
e. Installers shall secure the pull box cover.
f. The AC power cable between the pull box housing and the 4550-CF must
be enclosed in rigid conduit.
(UL COMPLIANCE SECTION PART 1 continued next page)
FIGURE 4:
TRANSFORMER AND TRANSFORMER ENCLOSURE
MOUNTING DIAGRAM.