SAFETY PRECAUTIONS
The boiler must be connected to a chimney in accordance with the specifications specified in the
operating instructions and the relevant regulations. The chimney must provide the draft value required
by the connected boiler. Your boiler should not be operated without a chimney connection and there
must be enough draft to burn. In chimneys where sufficient draft is not ensured, the boiler must never
be operated. Any installation in the place where the boiler is installed should not be installed.
In case of boiler changing in the boiler room, the old boiler must be removed or disconnected from the
chimney and the insulation must be sealed and insulation should be made. In no case should more
than one boiler be connected to the same chimney. The cylindrical chimney can be passed through the
chimney in the figure.
Smoke chimneys should not be placed on the outer
wall of the building unless it is a technical
requirement. The wall thickness of the chimney
walls should not be less than a brick thickness. For
chimney
construction,
hollow
bricks
and
briquettes should never be used. It should be
plastered inside and outside of the rectangular
chimney.
It should be ensured that fresh air is continuously introduced into the area where the boiler is installed.
Reference must be made to the dimensions specified in this manual. The boiler should never be
installed in living spaces or in a place directly connected to such a place. In order to reduce the risk of
scaling and corrosion in old and new installations, the instructions given in the relevant section of this
manual should be applied by the installer who installs the boiler. In particular, if the boiler is connected
to an old installation, it is necessary to clean the waste completely before installation. The installation
must be cleaned and cleaned several times.
Avoid overloading fuel into the boiler and check the suitability of combustion frequently. For any
reason, direct cold water should not be added to the overheated boiler for cooling. This can cause
noise in the installation, excessive thermal stresses in the boiler and thus permanent damage. The
water in the installation must not be drained unless there is a risk of maintenance or freezing. The
system design should ensure that the ratio between the water flow rate and the boiler capacity is not
exceeded and the difference between the boiler inlet and outlet water temperatures of 20ºC is not