RECOMMENDED LOCATION OF ALARMS

• Locate the first smoke alarm in the immediate area of the bedrooms. Try to protect the escape

route as the bedrooms are usually farthest from an exit. If more than one sleeping area exists,
locate additional smoke alarms in each sleeping area. If a hall is more than 40 feet (12 meters)
long, install a smoke alarm at each end.

• Locate additional smoke alarms to protect any stairway as stairways act like chimneys for

smoke and heat.

• Locate at least one smoke alarm on every floor level.
• Locate a smoke alarm in any area where a smoker sleeps or where electrical appliances are

operated in sleeping areas.

• Smoke, heat and other combustion products rise to the ceiling and spread horizontally. Mounting

the smoke alarm on the ceiling in the center of the room places it closest to all points in the room.
Ceiling mounting is preferred in ordinary residential construction. However, in mobile homes, wall
mounting on an inside partition is preferred to avoid the thermal barrier that may form at the
ceiling.

• When mounting smoke alarm on the ceiling, locate it a minimum of 4" (10cm) from a side wall

or corner (see Diagram A).

• When mounting smoke alarm on a wall, if local codes allow, use an inside wall with the top edge

of the smoke alarm a minimum of 4" (10cm) and a maximum of 12" (30.5cm) below the ceiling/
wall intersections (See Diagram A).

Sloped Ceilings (Peaked Ceilings):
Smoke alarms or smoke detectors mounted on a peaked ceiling shall be located within 36 in. (914 mm) horizontally
of the peak, but not closer than 4 in. (102 mm) vertically to the peak.

Sloped Ceilings (Shed Ceilings):
Smoke alarms or smoke detectors mounted on a sloped ceiling having a rise greater than 1 ft. in 8 ft. (1 m in 8
m) horizontally shall be located within 36 in. (914 mm) of the high side of the ceiling, but not closer than 4 in. (102
mm) from the adjoining wall surface.

Tray-Shaped Ceilings:
Smoke Alarms or smoke detectors shall be installed on the highest portion of the ceiling or on the sloped portion
of the ceiling within 12 in. (305 mm) vertically down from the highest point.

Mobile Home Installation:
For minimum protection, smoke alarms  should be installed in compliance with H.U.D. Manufactured Home
Construction Safety Standards, Title 24 CFR, Section 3280.208 and Section 3282. For additional protection, see
Single Story Residence smoke alarm requirements/recommendations for Existing Homes and New Construction
Homes.

Note: For mobile homes built before 1978, install smoke alarms on inside walls between 4” and 12” from the
ceiling (older mobile homes have little or no insulation in the ceiling). This is especially important if the ceiling
is unusually hot or cold.

Install a smoke alarm inside each bedroom and in the hallway outside each separate sleeping area.

Existing Homes:
The NFPA requires a smoke alarm on every level and outside each sleeping area in existing construction. An
existing household with one level and one sleeping area is required to have one smoke alarm.

New Construction Homes and Manufactured Homes:
The NFPA requires AC-powered, interconnected smoke alarms to be installed inside each bedroom, outside each
bedroom area, and on every level of the home. They also require a minimum of two AC-powered, interconnected
smoke alarms in any new construction home.

Summary of Contents for SS-785

Page 1: ...R INSURANCE Homeowners and renters alike should continue to insure their lives and properties SMOKE ALARMS CANNOT WORK WITHOUT POWER Battery operated units cannot work if the batteries are missing disconnected or dead if the wrong type of batteries are used or if the batteries are not installed correctly AC only powered units cannot work if the AC power is cut off for any reason If you are concern...

Page 2: ...102 mm vertically to the peak Sloped Ceilings Shed Ceilings Smoke alarms or smoke detectors mounted on a sloped ceiling having a rise greater than 1 ft in 8 ft 1 m in 8 m horizontally shall be located within 36 in 914 mm of the high side of the ceiling but not closer than 4 in 102 mm from the adjoining wall surface Tray Shaped Ceilings Smoke Alarms or smoke detectors shall be installed on the high...

Page 3: ...e beginning installation Failure to turn off the power before installation may result in serious electrical shock injury or death TAMPER LOCKING PIN To make your smoke alarm somewhat tamper resistant a locking pin has been provided Using this pin will deter children and others from removing the alarm from the mounting ring To use the pin insert it into the hole in the side of the alarm after it ha...

Page 4: ... alarm event initiates the alarm The yellow wire is used only for multiple station operation with UNIVERSAL models only Connecting this yellow wire to any other circuits may result in damage When smoke alarms are interconnected all units must be powered from a single AC branch circuit If local codes do not permit be sure the neutral wire is common to both phases The maximum wire run distance betwe...

Page 5: ...witch accurately tests the unit s operation as required by Underwriters Laboratories Inc UL BACKUP BATTERY REPLACEMENT Model SS 790 only Disconnect AC power before changing battery Shock hazard exists if AC power is miswired The smoke alarm uses a 9 Volt carbon zinc battery The battery should last for at least one year under normal operating conditions The smoke alarm has a low battery indicator a...

Page 6: ...is all right to do so NATIONAL FIRE PROTECTION ASSOCIATION REQUIRED PROTECTION For your information the National Fire Protection Association s Standard 72 reads as follows 11 5 1 One and Two Family Dwelling Units 11 5 1 1 Smoke Detection Where required by applicable laws codes or standards for the specified occupancy approved single and multiple station smoke alarms shall be installed as follows 1...

Page 7: ...repaid with a payment of 5 00 to cover the costs of return postage and handling You must include a proof of purchase receipt along with the returned product UNIVERSAL DOES NOT WARRANTAND SPECIFICALLY DISCLAIMSANY WARRANTY WHETHER EXPRESS OR IMPLIED OF FITNESS FOR A PARTICULAR PURPOSE OTHER THAN THE WARRANTY CONTAINED HEREIN NOIMPLIEDWARRANTYONTHISPRODUCT CREATEDBYSTATE LAW SHALLEXTEND BEYOND THE T...

Reviews: