Local Expansion Adapter Kits allow you to increase the number of I/Os connected to a 

single UniStream

®

 by enabling you to link the controller to additional Uni-I/O™ modules. 

This guide provides specifications for Unitronics’ Short Range and Long Range Local 

Expansion Adapter Kit for Uni-I/O™. 
All Kits comprise a Base unit, an End unit, and a connecting cable. The cable length varies 

according to kit model.  

 

Short-range adapter Kits 

Up to 3 meters 

 

Long-range adapter Kits 

3 meters and up 

Kits whose models contain the letter 'P' include a built-in power supply; a powered adapter 

module supports a greater number of I/O modules. 
There are two main classes of adapters:  

 

UAG-XK 

Both the Base and End units of these adapters have DIN-rail clips. You can: 

 

Snap the base onto the DIN-rail type structure on the back of 

UniStream

 

Modular

 HMI  

 

Snap the base directly onto a 

UniStream PLC

 

 

UAG-CX  

The base unit of these adapters has a plug; the end unit has DIN-rail clips. You can plug 

the base unit only into the 

I/O Expansion Jack

 offered by the 

UniStream Built-in 

series

 

Note that the maximum number of modules supported by a single controller is provided in 

the controller’s technical specifications. 
Technical specifications are available in Unitronics’ Technical Library at 

www.unitronicsplc.com

. 

 

Adapter Models 

The ‘x’s in the model numbers are placeholders for the cable lengths. 

Model 

Installation 

Options 

Integrated 

Power Supply 

Module Support 

UAG-XKxxx 

DIN-rail structure 

 

DIN-rail  

No 

8, 

includes

 any modules 

directly connected to the 

controller 

UAG-XKxxx 

Yes 
 

16, in 

addition

 to any 

modules directly connected 

to the controller 

UAG-XKxxxx 

UAG-CX-XKPxxx, 

UAG-CX-XKPLxxxx 

Plug into controller 

Jack 

Yes 

16 

UAG-CX-XKPLxxxx 

 

 

 

Summary of Contents for UniStream UAG-XK Series

Page 1: ...the Base and End units of these adapters have DIN rail clips You can Snap the base onto the DIN rail type structure on the back of UniStream Modular HMI Snap the base directly onto a UniStream PLC UAG CX The base unit of these adapters has a plug the end unit has DIN rail clips You can plug the base unit only into the I O Expansion Jack offered by the UniStream Built in series Note that the maximu...

Page 2: ... should be installed only by qualified personnel Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels Do not connect disconnect the device when power is on Environmental Considerations Ventilation 10mm 0 4 of space is required between the device top bottom edges and the enclo...

Page 3: ...AG CX XKPLxxx Assembly Diagram Short range Adapters UAG XKxxx and UAG XKPxxx UniStream Modular UniStream PLC 1 Bus connector 2 Base Unit plug 3 Clips 4 Base Unit s cable port 5 Cable with RJ45 connector 6 End Unit LED indicators 7 DIN rail clips top and bottom 8 End Unit I O bus connector 9 I O Bus Left side connector 10 Model dependent UAG XKxxx earth point connector UAG XKPxxx power supply conne...

Page 4: ...or 8 I O Bus Left side connector 9 Power supply connector Assembly Diagram Long range Adapters UAG XKPLxxxx UniStream Modular UniStream PLC 1 Bus connector 2 Base Unit plug 3 Clips 4 Base Unit s cable port blue RJ45 5 Cable with RJ45 connectors 6 End Unit LED indicators 7 DIN rail clips top and bottom 8 End Unit I O bus connector 9 I O Bus Left side connector 10 Power supply connector Caution Plea...

Page 5: ...proper precautions to prevent Electro Static Discharge ESD This kit enables you to connect a UniStream controller to a row of Uni I O modules located on a DIN rail To do this you must Connect the Base Unit to the controller Connect the End Unit to the first module in a row of Uni I O modules Link the End Unit into the Base Unit via the connecting cable If you are using a UAG XKPxxx UAG CX XKPxxx U...

Page 6: ...ing figure and plug it into the I O Expansion Jack in the rear of the device Connecting the Adapter End Unit 1 Push the End Unit onto the DIN rail until the clips located at the top and bottom of the unit have snapped onto the DIN rail 2 Install Uni I O modules to the right of the End unit Please refer to the specific Installation Guide of each Uni I O module 3 Slide the Bus Connector Lock of the ...

Page 7: ...distance from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure a proper connection 4 Tighten enough to keep the wire from pulling free Wir...

Page 8: ...t and slide it to the right Pull the End Unit s top DIN rail clip up and the bottom clip down Pull the End Unit out of its place away from the DIN rail The information in this document reflects products at the date of printing Unitronics reserves the right subject to all applicable laws at any time at its sole discretion and without notice to discontinue or change the features designs materials an...