Unitronics UAG-XK series Installation Manual Download Page 4

Short-Range Local Expansion Kit Installation Guide  

 

 

Unitronics 

 

Wiring Procedure 

Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm

2

 –3.31 mm

2

). 

1.  Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).  
2.  Unscrew the terminal to its widest position before inserting a wire.  
3.  Insert the wire completely into the terminal to ensure a proper connection. 
4.  Tighten enough to keep the wire from pulling free. 

 

Wiring Guidelines 

In order to ensure that the device will operate properly and to avoid electromagnetic 

interference: 

 

Use a metal cabinet. Make sure the cabinet and its doors are properly earthed. 

 

Use wires that are properly sized for the load. 

 

Connect the 0V point of the UAG-XKPxxx directly to the power supply 0V terminal. 

 

Connect the functional ground point ( ) to the earth of the system (preferably to the 

metal cabinet chassis). 

Use the shortest and thickest wires possible: less than 1m (3.3’) in length, minimum 

thickness 14 AWG (2 mm2). 

 

Connect the power supply 0V to the earth of the system. 

N

OTE

 

For detailed information, refer to the document System Wiring Guidelines, located in 

the Technical Library in the Unitronics’ website. 

 

13B

Wiring the Power Supply (UAG-XKPxxx)

 

The UAG-XKPxxx requires an external 12 or 24VDC power supply. 

 

 

 

The 0V of the UAG-XKPxxx end unit must be connected to the HMI Panel’s 0V. 

Ignoring this directive may damage the device. 

 

In the event of voltage fluctuations or non-conformity to voltage power supply 

specifications, connect the device to a regulated power supply. 

Connect the +V and 0V terminals as shown in the 

accompanying figure. 

 

 

7B

Removing the Expansion Cable  

1.

 

Turn off the system power. 

2.

 

Unplug the cable from the Base Unit. 

3.

 

To remove the Base unit, pull the top clip up and the bottom clip down; and pull it 

slowly away until the plug disengages. 

4.

 

To remove the End unit:  

 

Locate the Bus connector lock of the Uni-I/O™ module connected to the End Unit 

and slide it to the right. 

 

Pull the End Unit’s top DIN-rail clip up and the bottom clip down. 

 

Pull the End Unit out of its place (away from the DIN rail). 

 

The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, 

to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the 

market.All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, 

fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall 

Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of 

this information. The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third 

parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them 

[DOC27006-A1] 04/13

 

 

Summary of Contents for UAG-XK series

Page 1: ...ied danger causes physical and property damage Warning The identified danger could cause physical and property damage Caution Caution Use caution All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product according to local and national standard...

Page 2: ...tion Space Considerations Allocate space for the Base Unit and End Unit according to the dimensions in the kit s technical specifications Also consider the space required to install and connect them as shown in the following Installation instructions Installation Turn off system power before connecting or disconnecting any modules or devices Use proper precautions to prevent Electro Static Dischar...

Page 3: ...e 4 UAG XKxxx without power supply earth it Do not connect the cable to any device other than the Base Unit Do not connect the Base Unit s cable port to any other cable or device Wiring This equipment is designed to operate only at SELV PELV Class 2 Limited Power environments All power supplies in the system must include double insulation Power supply outputs must be rated as SELV PELV Class 2 Lim...

Page 4: ... shown in the accompanying figure 7BRemoving the Expansion Cable 1 Turn off the system power 2 Unplug the cable from the Base Unit 3 To remove the Base unit pull the top clip up and the bottom clip down and pull it slowly away until the plug disengages 4 To remove the End unit Locate the Bus connector lock of the Uni I O module connected to the End Unit and slide it to the right Pull the End Unit ...