Wiring Procedure
Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm
2
–3.31 mm
2
).
1. Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
Wiring Guidelines
In order to ensure that the device will operate properly and to avoid electromagnetic
interference:
Use a metal cabinet. Make sure the cabinet and its doors are properly earthed.
Use wires that are properly sized for the load.
Connect the 0V point of the UAG-XKPxxx directly to the power supply 0V terminal.
Connect the functional ground point ( ) to the earth of the system (preferably to the
metal cabinet chassis).
Use the shortest and thickest wires possible: less than 1m (3.3’) in length, minimum
thickness 14 AWG (2 mm2).
Connect the power supply 0V to the earth of the system.
N
OTE
For detailed information, refer to the document System Wiring Guidelines, located in
the Technical Library in the Unitronics’ website.
13B
Wiring the Power Supply (UAG-XKPxxx)
The UAG-XKPxxx requires an external 12 or 24VDC power supply.
The 0V of the UAG-XKPxxx end unit must be connected to the HMI Panel’s 0V.
Ignoring this directive may damage the device.
In the event of voltage fluctuations or non-conformity to voltage power supply
specifications, connect the device to a regulated power supply.
Connect the +V and 0V terminals as shown in the
accompanying figure.
7B
Removing the Expansion Cable
1.
Turn off the system power.
2.
Unplug the cable from the Base Unit.
3.
To remove the Base unit, pull the top clip up and the bottom clip down; and pull it
slowly away until the plug disengages.
4.
To remove the End unit:
•
Locate the Bus connector lock of the Uni-I/O™ module connected to the End Unit
and slide it to the right.
•
Pull the End Unit’s top DIN-rail clip up and the bottom clip down.
•
Pull the End Unit out of its place (away from the DIN rail).
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice,
to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the
market.All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability,
fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall
Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of
this information. The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third
parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them
[DOC27006-A1] 04/13