3 Elektrical Installation
CE Advice
The devices adhere to the EU guidelines 89/336/EWG and the technical
standards EN 61000-2 and 61000-4 provided that the following conditions are
observed:
- The device, the power choke, and the filter capacitors are mounted on
a 500x500x2 mm mounting plate.
- The mounting plate must be connected to ground using a 10mm² wire.
- The motor housing must be connected to ground using a 10mm² wire.
- The device ground X1:8 must be connected to the mounting plate
using a 2.5mm² wire.
- Device PE screw must be connected to the mounting plate using
a 4mm² wire, l = 50mm.
Connection:
Power choke type: see technical details
Filter capacitors:
3 x 0.5
m
F/600V
~
3 x 1
m
F (x) + 1 x 0.5
m
F (y)
Conductor length between the device and the power choke <250mm