background image

This document is based on NEC installation requirements for equipment installed in hazardous locations in the United States of 
America.

Description

Conduit seals prevent explosions from spreading through conduit systems and igniting outside atmospheres. When properly installed

and filled with a UL-listed sealing compound, they prevent the passage of gases, vapors, or flames from spreading from a hazardous 
location to a nonhazardous location.

The information describes the main purposes for seal fittings:

Restrict the passage of gases, vapors, or flames from one part of the conduit system to another area of the system.

Limit explosions to the sealed enclosure.

Prevent precompression, or “pressure piling,” in conduit systems.

WARNING:  Failure to follow safety instructions may cause ignition of hazardous 

atmosphere resulting in serious personal injury and/or property damage.

EXPLOSIONPROOF
SWITCH

IGNITABLE GASES OR VAPORS 
IGNITED BY SPARK OF SWITCH

EXPLOSION CONFINED 
WITHIN SEALED AREA

SF SEAL WITH DRAIN VALVE

SEALING CEMENT

POURING OPENING

FIBER DAM

Figure 1.

How Gases,  Vapors,  and 
Flames Are Contained

INSTALLATION

Conduit Sealing Instructions for

Equipment in Hazardous Locations

1

Nipples (supplied with enclosure)

2

Sealing fittings (supplied with enclosure)

3

Explosionproof nipple

4

Explosionproof elbow

5

Explosionproof flexible conduit, for Class 2 wiring

6

Explosionproof flexible conduit, for Class 1 wiring

7

Explosionproof J-box, for connection of pan/tilt and 
Class-1 camera; for ease of wire pulls, locate as close to 
the pan/tilt as possible

8

Sealing fitting, for separation of hazardous and 
nonhazardous locations

Summary of Contents for EV3000-PT-EXIR

Page 1: ...d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d V V V V V V V V V V V V V V V V V V V V V V V V...

Page 2: ...Specifications 3 Installation 4 Operation 5 Dimensional diagram 6 Communications Protocol Part B FLIR IR Cameras Part C Conduit Sealing Instructions for Equipment in Hazardous Locations SSHQGL I IR c...

Page 3: ...I Divisions I and II Groups A B C and D Class II Divisions I and II Groups E F G T5 Class I Zone 1 AEx d IIC Ex d IIC T5 The electro polished Aluminumstainless steel construction makes the EV3000 PT...

Page 4: ...II Groups E F G T5 Class I Zone 1 AEx d IIC Ex d IIC T5 0DWHULDOV Aluminum Stainless Steel 5RWDWLQJ DQJOH 3DQ a 7LOW a 5RWDWLQJ VSHHG Pan 0 1 12 sec Tilt 0 1 6 sec Motor PRWRU Temperature WR Preset 0...

Page 5: ...t leave the unit in a location near heat sources or humidifier Be careful of electric overload on the electric terminal or extension cable otherwise there can be risk of permanent damage You must stop...

Page 6: ...3000 PT within 20 ft and the DC24V should be supplied using AWG16 wires 3 1 2 The built in receiver address is set to 1 and Baud rate is set to 2400 bps the unit controlled using any Pelco D keyboard...

Page 7: ...it systems WARNING Failure to follow safety instructions may cause ignition of hazardous atmosphere resulting in serious personal injury and or property damage EXPLOSIONPROOF SWITCH IGNITABLE GASES OR...

Page 8: ...ures Figure 2 Seals Within Conduit Smaller Than 2 Inches If the conduit is 2 inches or larger a seal must be placed within 18 inches of the enclosure Figure 3 Seals Within Conduit Larger Than 2 Inches...

Page 9: ...kes a dam that keeps the sealing compound in the chamber of the sealing fitting while it cures and hardens The fiber dam is also used to separate the individual conductors so the sealing compound seal...

Page 10: ...fications are subject to change Check website www unitedvisionsolutions com Contact us For repair service or if problem s still exist after troubleshooting Call Customer Service 1 413 592 8477 tech un...

Reviews: