Appendix E:  LonWorks Protocol Implementation Conformance Statement

 

 

 

 
 

Unit Ventilator 

 

CARRIER CORPORATION ©2019   

Integration Guide 

 

All rights reserved 

 

39 

 

Product Names: 

Unit Vent

 

LonWorks network points are spawned within the device as a result of downloading graphical control programs. 
The Unit Vent controller speaks the LonWorks Protocol as described by Echelon Protocol Specification. Since the 
controller is custom-programmable it does not conform to LonMark certification. Further details on the LonWorks 
supported implementation are described below. 

The FT 3120 Free Topology Smart Transceiver is fully compatible with the TP/FT-10 channel and can 
communicate with devices using Echelon's FTT-10A Free Topology Transceiver. The free topology transceiver 
supports polarity insensitive cabling using a star bus, daisy-chain, loop, or combination topology. 

 

Serial Transmission Mode 

Supported? 

LonWorks 

Master or Slave (Slave is the Default Dipswitch setting) 

 

Communication Types

 

Baud rates

 

Data Bits

 

Parity

 

Stop Bits

 

2-wire EIA-485 

variable 

None 

 

The controller supports the following SNVT listing as noted by the Echelon Protocol Specification: 

SNVT_abs_humid 

SNVT_elec_whr 

SNVT_mass_kilo 

SNVT_speed 

SNVT_address 

SNVT_elec_whr_f 

SNVT_mass_mega 

SNVT_speed_f 

SNVT_alarm 

SNVT_enthalpy 

SNVT_mass_mil 

SNVT_speed_mil 

SNVT_alarm_2 

SNVT_evap_state 

SNVT_motor_state 

SNVT_state 

SNVT_amp 

SNVT_ex_control 

SNVT_muldiv 

SNVT_state_64 

SNVT_amp_ac  

SNVT_file_pos 

SNVT_multiplier 

SNVT_str_asc 

SNVT_amp_f 

SNVT_file_req 

SNVT_obj_request 

SNVT_str_int 

SNVT_amp_mil 

SNVT_file_status 

SNVT_obj_status 

SNVT_switch 

SNVT_angle 

SNVT_fire_indcte 

SNVT_occupancy 

SNVT_telcom 

SNVT_angle_deg 

SNVT_fire_init 

SNVT_override 

SNVT_temp 

SNVT_angle_f 

SNVT_fire_test 

SNVT_ph 

SNVT_temp_diff_p 

SNVT_angle_vel 

SNVT_flow 

SNVT_ph_f 

SNVT_temp_f 

SNVT_angle_vel_f 

SNVT_flow_f 

SNVT_pos_ctrl 

SNVT_temp_p 

SNVT_area 

SNVT_flow_mil 

SNVT_power 

SNVT_temp_ror 

SNVT_btu_f 

SNVT_flow_p 

SNVT_power_f 

SNVT_temp_setpt 

SNVT_btu_kilo 

SNVT_freq_f 

SNVT_power_kilo 

SNVT_therm_mode 

SNVT_char_ascii 

SNVT_freq_hz 

SNVT_ppm 

SNVT_time_f 

SNVT_char_mega 

SNVT_freq_kilohz 

SNVT_ppm_f 

SNVT_time_hour 

SNVT_chlr_status 

SNVT_freq_milhz 

SNVT_preset 

SNVT_time_min 

SNVT_color 

SNVT_gfci_status 

SNVT_press 

SNVT_time_passed 

SNVT_config_src 

SNVT_grammage 

SNVT_press_f 

SNVT_time_sec 

SNVT_count 

SNVT_grammage_f 

SNVT_press_p 

SNVT_time_stamp 

SNVT_count_f 

SNVT_hvac_emerg 

SNVT_privacyzone 

SNVT_time_zone 

SNVT_count_inc 

SNVT_hvac_mode 

SNVT_ptz 

SNVT_tod_event 

SNVT_count_inc_f 

SNVT_hvac_override 

SNVT_pumpset_mn 

SNVT_trans_table 

SNVT_ctrl_req 

SNVT_hvac_status 

SNVT_pumpset_sn 

SNVT_turbidity 

SNVT_ctrl_resp 

SNVT_hvac_type 

SNVT_pump_sensor 

SNVT_turbidity_f 

SNVT_currency 

SNVT_ISO_7811 

SNVT_pwr_fact 

SNVT_valve_mode 

Appendix E:  LonWorks Protocol Implementation Conformance Statement 

Summary of Contents for Carrier Unit Vent Open

Page 1: ...V Ve en nt ti il la at to or r I In nt te eg gr ra at ti io on n G Gu ui id de e CARRIER CORPORATION 2019 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 11 808 513...

Page 2: ...ur local Carrier office Important changes are listed in Document revision history at the end of this document CARRIER CORPORATION 2019 All rights reserved throughout the world i Vu is a registered tra...

Page 3: ...for LonWorks communication 15 Troubleshooting LonWorks communication 16 Start up 16 Sequence of Operation 17 Scheduling 17 Supply fan 18 Cooling 19 Heating 20 Mixed air damper Modulating 22 Mixed air...

Page 4: ...rnal application programming provides optimum performance and energy efficiency Unit Vent enables the unit to run in 100 stand alone control mode or it can communicate to the Building Automation Syste...

Page 5: ...Contact Fan Status Dry Contact N A Freezestat BI IN 6 1 Gnd Low Limit Thermostat Dry Contact N A OA Damper AO AO 1 2 Gnd Mixed Air Damper 0 10 Vdc 2 10 Vdc N A Valve F B AO AO 2 4 Gnd Face Bypass Damp...

Page 6: ...Cnet MS TP N2 Modbus and through the Option Card port for the LonWorks Option Card NOTES Changing protocol requires no programming or point assignment by the installer or operator Power must be cycled...

Page 7: ...address Set the Tens 10 s switch to the tens digit of the address and set the Ones 1 s switch to the ones digit EXAMPLE If the controller s address is 25 point the arrow on the Tens 10 s switch to 2...

Page 8: ...imizes MS TP network communications by preventing token passes and poll for master requests to non existent Master nodes In the above example MAC address 16 knows to pass the token back to MAC address...

Page 9: ...the Equipment Touch interface navigate to the Properties Menu screen and click Login NOTE The following graphic is generic and not specific to your system 2 Type Touch for the password and click Done...

Page 10: ...tlined in this manual Review all of the steps and use the following list to check your settings Verify accuracy of the following Hardware settings for BACnet MS TP 8 Data bits No Parity and 1 Stop bit...

Page 11: ...it Vent recognizes its address only after power has been cycled 3 Set communications selector for BACnet ARC156 4 Set the both DIP switches 3 and 4 OFF for BACnet ARC156 NOTE The baud rate for BACnet...

Page 12: ...controller recognizes physical changes DIP switches rotary switches and jumpers upon power up If RX LED is solid then the terminations are incorrect If the network has greater than 32 devices or excee...

Page 13: ...00 feet 610 meters or 32 nodes Devices should be daisy chained and not star wired Attach the drain shield wire to both ends of the network segment and through every controller NOTE Use the same polari...

Page 14: ...hes rotary switches and jumpers upon power up Refer to Appendix A for the Network Points list Refer to Appendix D for the Protocol Implementation Conformance Statement Software settings defined throug...

Page 15: ...d 22 AWG shielded twisted pair wire EIA 485 Maximum wire length 2000 feet 610 meters or 32 nodes Devices should be daisy chained and not star wired Attach the drain shield wire to both ends of the net...

Page 16: ...y switches and jumpers upon power up Modbus Exception Codes that might be returned from this controller Codes Name Description 01 Illegal Function The Modbus function code used in the query is not sup...

Page 17: ...ique address Set the Tens 10 s switch to the tens digit of the address and set the Ones 1 s switch to the ones digit EXAMPLE If the controller s address is 25 point the arrow on the Tens 10 s switch t...

Page 18: ...system s network layout diagram This is done using the device s unique Neuron ID A network management tool such as Echelon s LonMaker is used to commission each device as well as to assign addressing...

Page 19: ...nterfaces to start up access information read sensor values and test the controller This interface Provides a Field Assistant application Runs on a laptop that connects to controller s Local Access po...

Page 20: ...source can be changed to one of the following Occupancy Schedules The controller is occupied 24 7 until you configure a time schedule using the Equipment Touch Field Assistant or the i Vu application...

Page 21: ...he space temperature failure alarm condensate overflow alarm or the test mode is active the fan shuts down immediately regardless of occupancy state or demand Automatic Fan Speed Control The Unit Vent...

Page 22: ...Fan Status Option The optional input can be configured as either an occupancy input or a fan status input If configured as fan status the controller compares the status of the fan to the desired comma...

Page 23: ...d Water The control can operate a modulating 0 10 Vdc or 2 10 Vdc type F B damper and an optional 2 position NO or NC chilled water valve to maintain the desired cooling setpoint The damper modulates...

Page 24: ...rolled to maintain the Heating Control Setpoint during heating and will not exceed the Maximum Heating SAT limit If the fan is off or a fan failure alarm occurs the valve modulates to maintain the Sup...

Page 25: ...is Modulating Space temperature reading is valid Supply Fan must be on and not in Alarm OAT is valid Heat mode is not active Fire Smoke Detector FSD is Normal OAT is less than Damper Lockout Temperatu...

Page 26: ...monitors the CO2 level and compares it to the configured setpoints and adjusts the minimum damper position as required The control provides proportional ventilation to meet the requirements of ASHRAE...

Page 27: ...DCV Override These can be adjusted to meet various specifications Demand Limiting The Unit Vent accepts 3 levels of demand limit from the network In response to a demand limit the unit decreases its h...

Page 28: ...interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at h...

Page 29: ...r in the navigation tree and go to Properties BACnet Objects tab When an i Vu Open controller or a third party system writes to any of the system points you must use BACnet Priority Level 16 and the v...

Page 30: ...ned the system point to its default value Therefore a BAS should never read back the system point s value to confirm the commanded value was successfully received To confirm a write refer to the table...

Page 31: ...Default Value BACnet Point Name BACnet Object ID Modbus Register Type Modbus Register Return Air Temperature R F ra_temp AV 1010 Input Register Float 65 Setpoint R W F occ_cl_stpt AV 3001 Holding Reg...

Page 32: ...AV 2026 Input Register Float 37 Occ Override Delay R W min 15 occ_ovr_delay AV 9028 Holding Register Float 63 Outdoor Air Temperature R F oa_temp AV 1003 Input Register Float 87 Override Time Remainin...

Page 33: ...7012 Discrete Input 39 Occupancy Status R Unoccupied Occupied occ_status BV 2008 Discrete Input 18 Outdoor Air Temperature R Normal Alarm oat_alarm BV 7036 Discrete Input 19 Reset Filter Alarm R W Off...

Page 34: ...Float 147 Maximum Heating SAT R W F 105 sat_ht_max AV 83004 Holding Register Float 41 Minimum Cooling SAT R W F 50 sat_cl_min AV 83003 Holding Register Float 61 Space Temp Source R 1 Sensor Failure 2...

Page 35: ...ADF 74 nvoOAVntDmpr Output active default Damper Setpoint Override Value R W F F ADF 19 nviDmpSetOvr Input passive default Economizer Purge Min Pos R W Open Open ADF 5 nviEcnPrgMin Input passive defa...

Page 36: ...Output active default Indoor Air Quality R Normal Alarm BI 33 nvoIAQAlm Output active default Indoor Air Quality Sensor R Normal Alarm BI 37 nvoIAQSensor Output active default Low Space Temperature R...

Page 37: ...default System Mode R 1 Off 2 Fan Only 3 Economize 4 Cooling 5 Heating 6 Cont Fan 7 Test 8 Start Delay 9 Temper SAT 10 Fire Shutdown 11 Shutdown 12 IAQ Override 12 Pre occ Purge ADI 13 nvoOpMode Outp...

Page 38: ...IER CORPORATION 2019 Integration Guide All rights reserved 35 The PIC statements are updated regularly Please refer to the BACnet website http www bacnetinternational net catalog index php m 28 for th...

Page 39: ...Is static device binding supported This is currently necessary for 2 way communication with MS TP slaves and certain other devices XX Yes Networking Options Router Clause 6 List all routing configura...

Page 40: ...Inputs BI Analog Outputs AO Binary Outputs BO Internal Floats ADF Internal Integers ADI Internal Bytes BD Protocol Commands Identify Device Type Write Analog Input Sync Time Write Binary Input Poll W...

Page 41: ...ete Outputs single 00001 09999 06 Preset Single Register Write Holding Registers single 40001 49999 15 Force Multiple Coils Write Discrete Outputs 00001 09999 16 Preset Multiple Coils Write Holding Re...

Page 42: ...SNVT_speed_mil SNVT_alarm_2 SNVT_evap_state SNVT_motor_state SNVT_state SNVT_amp SNVT_ex_control SNVT_muldiv SNVT_state_64 SNVT_amp_ac SNVT_file_pos SNVT_multiplier SNVT_str_asc SNVT_amp_f SNVT_file_...

Page 43: ...fr_mode SNVT_length_micr SNVT_res SNVT_volt_dbmv SNVT_defr_state SNVT_length_mil SNVT_res_f SNVT_volt_f SNVT_defr_term SNVT_lev_cont SNVT_res_kilo SNVT_volt_kilo SNVT_density SNVT_lev_cont_f SNVT_rpm...

Page 44: ...JN E RD 5 22 18 Troubleshooting BACnet MS TP Troubleshooting N2 Troubleshooting ARC156 Corrected BACnet Device Instance number C TS RD F 1 11 18 Sequence of Operation Supply Fan Section added on Conf...

Page 45: ...CARRIER CORPORATION 2019 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 11 808 513 01 11 19 2019...

Reviews: