Appendix A: Unit Vent Network Points List
Unit Ventilator
CARRIER CORPORATION ©2019
Integration Guide
All rights reserved
28
Commanded Points
Control Points
Display Name
Type /
Instance
Object Name
Display Name
Type /
Instance
Object Name
†System
Fire/Smoke
bv:1907
fire_shutdown
Fire/Smoke
Shutdown
bv:7007
fire_alarm
†System
Pressurization
bv:1906
press_override
Pressurization
bv:7038
press_alarm
BAS On/Off
[Occupancy]
msv:1001
keypad_ovrde
Occupancy Status
bv:2008
occ_status
†
Points do not apply to multi-protocol controllers.
Network points list for BACnet and Modbus
BACnet
Modbus
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet Object
ID
Modbus
Register
Type
Modbus
Register #
Return Air
Temperature
R
°F
ra_temp
AV:1010
Input
Register
(Float)
65
Setpoint
R/W
°F
occ_cl_stpt
AV:3001
Holding
Register
(Float)
9
Setpoint
R/W
°F
occ_ht_stpt
AV:3002
Holding
Register
(Float)
19
Setpoint
R/W
°F
unocc_cl_stpt
AV:3003
Holding
Register
(Float)
15
Setpoint
R/W
°F
unocc_ht_stpt
AV:3004
Holding
Register
(Float)
17
Supply Fan
Status
R
Off
On
sfan_status
BV:1003
Discrete
Input
24
Supply Air
Temperature
R
°F
sa_temp
AV:1008
Input
Register
(Float)
109
Cooling Lockout
Temperature
R/W
°F
45
oat_cl_lockout
AV:9002
Holding
Register
(Float)
43
Cooling Output
R
%
clg_output
AV:2025
Input
Register
(Float)
21
Damper Lockout
Temp
R/W
°F
63
oatlecon
AV:4004
Holding
Register
(Float)
23
Damper Output
R
%
oa_dpr_pos
AV:2022
Input
Register
169