background image

1-

 

PRELIMINARY

 

 

 

Check that the gascooler has not been damaged during transport and that no parts are missing. Check if gascooler is under pressure at 
arrival with a charge of nitrogen U 3 Bar +/- 0.5 Bar. 
If gascooler was damaged or if the delivery is incomplete, make remarks on the receipt reservations of transport and confirm them by 
letter with acknowledgment of receipt within 48 hours to the carrier with a copy to PROFROID. 
If the delivery does not correspond to your order, contact PROFROID. 

 

Gascoolers SV (vertical air flow) must be storage as their running positions, or inside a building, in order that water doesn’t go inside 
electrical equipment. 

 

2-

 

DESCRIPTION – OPERATIONS

 

 

Because gascoolers are delivered as a semi-finished product, we are not necessarily aware as a manufacturer of end use. Proper use of 
gascooler is always the responsibility of the end user. 
The use of gascooler is implicitly linked to the PS and TS design. 

 

APPLICATIONS 

Gascoolers in the SOPRANO CO2, ALTO CO2 & TENOR CO2 range are designed for external installation in all refrigeration and air 
conditioning applications. 

 

Fluid : R744 (CO2) 
PS = -1 / 120 bar TS = -40 / 120°C 

 

Transcritical running when P > 73 bar (T > 31°C) or subcritical for others cases. 

 

BODY 

Designed in painted or pre-glazed galvanized sheet metal depending on model. Individual separation of fans in order to optimize the 
circulation of air. 
Hoisting holes on all models. 

COIL 

Gascoolers are fitted with one or many coils with profiled aluminum fins and copper tubes (CuFe2P). Refrigeration joints to be welded 
(stainless steel 304L or copper CuFe2P). 

 

VENTILATION 

Fan motors are EC motors. 
They are equipped with an electronic switch for continuous speed variation and independently for each motor fan. Those engines are 
"synchronous" with higher efficiency than standard motors. 

 

Common characteristics of these motors: 

Standard 
Characteristics 

SOPRANO 60 

SOPRANO 90 – ALTO 91 – TENOR 90 

Ambient Temperature 

- 25 / + 60 °C 

Protection factor with 
purge  holes  sealed 
(CEI 34-5) 

 

IP54 

EC M1 

Min. 155 (1V) / Max. 1140 tr 

Min. 175 (1,4V) / Max. 1000 tr 

EC M2 

Min. 111 (1,4V) / Max. 610 tr 

Electrical supply 

380-480 V / 3 / 50-60 Hz 

Important

: the maximum imbalance between phases is 2% in voltage and 10% in current per motor. 

 

3-

 

INSTALLATION

 

 

 

HANDLING 

During installation, the legs provided separately, are fitted and fixed using the bolts provided. The gascooler is to be firmly fixed to 
flat and level ground. 
If lifting with a crane, a hanging bar must be used. 

 

 

Summary of Contents for Carrier SOPRANO CO2

Page 1: ...ANO CO2 ALTO CO2 TENOR CO2 Groupe de Fluide DESP 2 PED fluid group 2 Il est imp ratif de prendre connaissance de ces instructions d s r ception de l appareil et avant toute intervention sur celui ci N...

Page 2: ...les appareils qui utilisent un caloporteur Veuillez respecter les r gles de l art usuelles au transport et la manutention d appareils sous pression Installez l appareil dans un lieu suffisamment venti...

Page 3: ...rteur Des conduites de d charge chappements des dispositifs limiteurs de pression doivent tre install es de mani re ne pas exposer les personnes et les biens aux chappements de fluidefrigorig ne S ass...

Page 4: ...r le m me mod le et la m me marque que la soupape de s curit d origine S il y a changement de mod le et ou de marque alors le personnel en charge de ce remplacement devra r aliser une note de calcul s...

Page 5: ...sure devices Install device in a space with sufficient ventilation regarding standards and regulations because device is under pressure of nitrogen except dry cooler brine air cooler Very important be...

Page 6: ...of refrigerant Make sure that flexible hoses are not in contact with metalparts The products added for thermal and or acoustic insulation must be neutral with respect to support materials The protect...

Page 7: ...he possible increase of pressure in the part of device which is isolated The periodic technical checks must be made following frequencies determined by standards sound engineering practice end user an...

Page 8: ...nstallations ext rieures dans toutes les applications de r frig ration et de conditionnement d air Fluide R744 CO2 PS 1 120 bar TS 40 120 C Fonctionnement transcritique quand P 73 bar T 31 C ou subcri...

Page 9: ...TION MANUTENTION Lors de cette manutention les pieds livr s s par ment seront mont s et fix s l aide des boulons fournis L ensemble devra tre solidement fix au sol Lors d un grutage un palonnier doit...

Page 10: ...r Raccordement sur refoulement Les diam tres de ces tuyauteries doivent tre d termin s pour assurer un retour correct de l huile et non bas s sur les diam tres des vannes refoulement du collecteur Il...

Page 11: ...t ne jamais d marrer les compresseurs sans avoir introduit au moins 1 bar de pression de fluide en phase gazeuse Cela pour viter un amor age lectrique sous vide VERIFICATION DES MOTO VENTILATEURS STAN...

Page 12: ...tiques peut devenir un facteur aggravant de l encrassement des batteries Il est rappel que Seules les rampes adiabatiques de fourniture PROFROID doivent tre utilis es sur les changeurs PROFROID Tout a...

Page 13: ...frontales l aide d un aspirateur R p ter cette op ration autant que n cessaire jusqu l obtention d une surface ailet e parfaitement propre Utiliser de l air sec une pression maximale de 7 bars Distanc...

Page 14: ...ntre les projections d eau R p ter cette op ration autant que n cessaire jusqu l obtention d une surface ailet e parfaitement propre Dans le cas de l ajout de produits de nettoyage autre que l eau cho...

Page 15: ...s curit particuli res du site Se reporter l INSTRUCTION TECHNIQUE INS TEC 18 de SAKAPHEN ci apr s pour l entretien et le nettoyage des batteries avec rev tement HERESITE Respecter les consignes d asp...

Page 16: ......

Page 17: ...m max Pression Minimale 1 5 bar Le syst me de rampe adiabatique fournit par Profroid comprend une rampe porte buses en cuivre buses en laiton quantit selon mod le ligne d entr e quip e de manom tre le...

Page 18: ...oler Nettoyer le gascooler V rifier les motoventilateurs Installation surcharg e en fluide Vidange du liquide au r servoir Air ou gaz incondensables dans le circuit HP Purger Pression de condensation...

Page 19: ...0 bar TS 40 120 C Transcritical running when P 73 bar T 31 C or subcritical for others cases BODY Designed in painted or pre glazed galvanized sheet metal depending on model Individual separation of f...

Page 20: ......

Page 21: ...he gascooler Connection to discharge The pipe diameters must be determined in advance to ensure correct oil return and should not be based on the diameters of the discharge header valves It is usually...

Page 22: ...ion to a vacuum pump of the HP and LP sides The quality of drying should not be judged by the speed at which the level of vacuum is reached but on the effective time it is held 24 hours at 0 7 mbar is...

Page 23: ...entire unit and secure the unit against unintentional power on Comply with the site s specific safety instructions For heat exchangers with BLYGOLD or HERESITE coating refer to the paragraph specific...

Page 24: ...clogging dry residues leaves it is preferable to carry out a mechanical compressed air cleaning Initially clean with a non metallic brush soft brush Suck the front surfaces with a vacuum cleaner Repe...

Page 25: ...is mandatory to protect the fans against splashing water Repeat this operation as necessary until you obtain a perfectly clean surface When using cleaning agents other than water choose a neutral pH f...

Page 26: ...nstructions For maintenance on heat exchangers coated with HERESITE treatment please refer to SAKAPHEN INSTRUCTION TECHNIQUE INS TEC 18 procedure attached below It is an obligation to respect the spra...

Page 27: ......

Page 28: ...100 ppm Alkalinity CaCO3 250 ppm max Pressure 1 5 bar Water spray option includes Copper pipes with water duct sprayer Brass ducts quantity will be confirmed at the order Water devices Manometer Solen...

Page 29: ...tion overcharged with fluid Drain liquid into reservoir Air or non condensable gas in the HP circuit Purge Condensing Pressure too low Fan cut in incorrectly set Adjust pressure switch Fans not workin...