background image

MASONRY CHIMNEY

Masonry Chimneys have several positive 

attributes: If properly built, they are quite 

durable, and most homeowners consider 

them more attractive perhaps than a non-

enclosed  factory  built  chimney.    And,  if 

the chimney is located within the confines 

of the house (that is, not attached to an 

exterior wall), its mass alone will store heat 

longer and continue to release the heat 

long after the fire has died. Masonry chim-

neys have many disadvantages though.
Masonry  chimneys  constructed  on  an 

exterior wall are exposed to cold outdoor 

temperatures, promoting greater heater 

loss,  higher  accumulations  of  creosote, 

and reduced draft which leads to poorer 

heater or furnace performance.
When  considering  a  masonry  chimney, 

round  tiles  are  preferable  to  square  or 

rectangular,  as  round  tiles  have  much 

better airflow characteristics and are far 

easier to clean. Unfortunately, most North 

American chimneys use square or rectan-

gular tile liners that are really designed for 

open fireplaces, not stoves or furnaces. Of 

most importance, second only to overall 

chimney height, is the diameter of the flue 

liner itself. In most instances, it should be 

sized to the appliance; i.e., 6” flue outlet 

on the appliance requires a 6” flue. The  

inner diameter should never be less than 

the flue outlet diameter and should never 

be  greater  than  50%  of  the  appliance 

flue outlet. For example, do not expect a 

wood burning stove or furnace to function 

properly if installed into a chimney with a 

flue liner greater than 50% the appliance 

outlet -- such as a 6” flue outlet requires 

a 6” diameter for optimum drafting, but 

can function well with an 8”, but becomes 

borderline beyond 8” diameter. 
Masonry chimneys built of concrete blocks 

without flue liners of at least 5/8” fireclay 

do  not  meet  modern  building  codes.  A 

solid  fuel appliance must not be joined 

to a chimney flue which is connected to 

another appliance burning other fuels.
If your chimney has a typically oversized 

flue liner of 8x12 inches or greater, or if it is 

unlined, it will be necessary for you to reline 

the chimney, using many of the modern 

approved and economical methods such 

as  stainless  steel,  castable  refractory,  or 

properly sized fireclay linings.
If you have any question regarding vent-

ing your appliance, feel free to contact 

the  factory  at  the  address  and  phone 

number on this Owner’s Manual. You may 

also contact NFPA (National Fire Protection 

Association) and request NFPA Standard 

211 (1984 Edition). Their address is Battery 

March Park, Quincy, Massachusetts 02269. 

Another helpful publication is NFPA Stan-

dard 908, available at the same address. 

Specify 1984 Edition on either of the above 

publications.

bULLETINE RC454 

continued...

In the unlikely event that your heater “overfires” 

(a condition evidenced by elbows, stove pipes, 

and connectors glowing red in appearance or 

otherwise  discoloring),  then  your  installation 

is subject to excessive draft created by either 

a chimney too tall or too great in diameter in 

conjunction with its height, or some other factor 

of  an  indeterminate  cause.  In  this  event,  you 

should install a barometric draft regulator. Such 

installation  will  preclude  any  over-firing  and/

or  any  hazardous  consequences  of  potential 

overfiring.
Barometric draft regulators are generally avail-

able where you purchased your stove or may 

be  ordered  directly  from  United  States  Stove 

Company at a nominal charge.

DR6 - 6” DRAFT REgULATOR - OpTIONAL KIT

to  a  near  closed  position  -  but  leave  the  ash 

pit  damper  at  least  partially  open  to  prevent 

the  fire  from  going  out.  Adjust  the  stove  pipe 

damper to reduce the draft on the fire. With an-

thracite there will be short blue flames above 

the  coal,  except  when  the  fire  is  started  or  a 

new charge is added. If, however, there is no 

flame then the fire needs more air from the bot-

tom (unless it is near the end of its burn cycle 

and needs to be recharged).
Only when the coal is burned down to half its 

original depth it is time to add fresh coal. When 

doing so, open the stove pipe damper and turn 

the  thermostat  damper  to  high,  which  will  al-

low the fire to burn off any accumulated gases. 

Open  the  feed  door,  and  with  a  small  rake, 

hoe,  or  hooked  poker  pull  the  glowing  coals 

to  the  front  of  the  firebox.  Try  not  to  disturb 

the  fire  too  much.  Next,  add  a  fresh  charge 

to  the  back  being  careful  not  to  seal  off  the 

top.  Close  the  feed  door,  but  leave  the  spin 

damper (or thermostat) open for a few minutes 

until the volatile gases have burned off. It is not 

necessary to shake down the ashes each time 

you refuel the furnace. Experience will be your 

best teacher.

BANKING THE FIRE:

For extended operation, such as overnight, the 

fire will need to be banked. To do so heap coal 

up along the sides and back of the firebox so 

that  the  fire  gradually  burns  it  over  a  longer 

period of time. The intensity of the fire will also 

be reduced without letting it go out. Follow the 

same  procedure  as  for  refueling.  If  possible, 

avoid  shaking,  as  a  heavier  layer  of  ash  will 

help reduce the intensity of the fire during this 

time. After loading, let the fire establish itself for 

about 30 minutes. Then close your damper and 

automatic control to the point where the house 

does not become too cold. It is important that 

you begin banking early enough before retiring 

or leaving that you can make necessary adjust-

ments after the fire is well established.
To revive a coal fire that is almost out, (1) open 

the ash door and stove pipe damper and close 

the spin damper under the door to get a good 

draft through the grate. (2) place a thin layer of 

dry coal over the entire top of the fire. DO NOT 

POKE OR SHAKE THE FIRE AT THIS TIME! (3) after 

the fresh coal has become well ignited shake 

the grate (just a little), refuel.

9

16

b36TK - THERMODISC KIT FOR b36 bLOWER - OpTIONAL

Wish  your  blower  would  turn  ON  and  OFF  as 

the  heater  gets  warm  and  cold?  It  can  with 

this  optional  kit  from  U.S.  Stove.  It  connects in 

line  with  your  power  supply  cord  and  mounts 

to the back of the heater. When the snap disc 

reaches 120 degrees, the blower automatically 

turns ON and turns itself OFF if it reaches 90 de-

grees.  See  your  Dealer  for  details  or  call  U.S. 

Stove directly.

Summary of Contents for Wonderluxe B2350B

Page 1: ...OPERATION REPAIR PARTS Tested To UL 1482 06 ULC S627 00 851884 United States Stove Company 227 Industrial Park Rd P O Box 151 South Pittsburg TN 37380 423 837 2100 www USSTOVE com CAUTION Please read...

Page 2: ...in good repair Have the chimney inspected by the Fire Department or a qualified inspector such as a Chimney sweep Your insurance company may be able to recommend a qualified inspector 6 Inspect chimn...

Page 3: ...ector However therearelimits tohowclose theheater and chimney connector can be installed to combustible surfaces protected by a clearance reduction system Acorrectlyinstalledclearancereductionsystem p...

Page 4: ...ou have the clearances shown from the heater and the connector pipe to combustible surfaces If you have a solid brick or stone wall behind your heater you can place the heater as close as you wish to...

Page 5: ...metal screws and seal each joint with furnace cement The pipe must be short and straight All sections installed horizontally must slope at least 1 4 inch per foot with the upper end of the section to...

Page 6: ...e house Therefore the gas which circulates will cool more slowly thus reducing the build up of creosote and the risk of chimney fires 4 The draft caused by the tendency for hot air to rise will be inc...

Page 7: ...age firestops where needed FACTORY BUILT CHIMNEY insulation shield roof flashing chimney cap etc Maintain proper clearance to the structure as recommended by the manufacturer The chimney must be the r...

Page 8: ...ace with refractory mortar The thimble should be surrounded on all sides with 8 inches of brickwork solid masonry units or 24 inches of stone Install the stovepipe as far as possible into the thimble...

Page 9: ...onjunction with its height or some other factor of an indeterminate cause In this event you should install a barometric draft regulator Such installation will preclude any over firing and or any hazar...

Page 10: ...x The first flames will be long and generally orange or yellow and produce quite a bit of smoke As the gases burn off the flames become shorter change color and produce less smoke Once the fire is WEL...

Page 11: ...n 2 5 16 and 4 3 8 Note that it is important to the life of your stove to buy coal which has been sized and cleaned Cleaning insures removal of rocks and other materials DO NOT burn coke charcoal high...

Page 12: ...r speed reduces 3 Rotate the knob counter clock wise to turn OFF A B C D Follow these instructions to operate you unit safely when operating the feed door NOTE DURING OPENING AND CLOSING OF THE FEED A...

Reviews: