background image

CHIMNEY CONNECTION

Two basic types of chimneys are approved 

for use with solid fuel: Factory-built and ma-

sonry. Factory-built chimney must comply 

with UL 103 type “HT” standard.
Do  not  expect  your  stove  or  furnace  to 

create draft. Draft is not a function of the 

appliance.  It  is  purely  a  function  of  the 

chimney.  Modern  stoves  and  furnaces 

are  much  more  air-tight  and  efficient 

than those of the past and, therefore re-

quire greater draft. A 

minimum of .05 w.c. 

(12.45Pa)

,  is  required  for  proper  drafting 

to prevent back-puffing, smoke spillage, 

and to maximize performance. Gauges to 

measure chimney draft are readily avail-

able at stove shops and are economical 

to purchase or rent.
Chimneys perform two functions - one of 

which is apparent: The chimney provides 

a  means  for  exhausting  smoke  and  flue 

gases resulting from combustion of the fuel. 

Secondarily, though, the chimney provides 

“Draft” which allows oxygen to be continu-

ously introduced into the appliance, so that 

proper combustion is possible. 

IMpORTANT

Your chimney connector and chimney must 

have the same diameter as the stove outlet 

(6”). If this is not the case, we recommend 

you contact your dealer in order to insure 

there will be no problem with the draft.
The stove pipe must be made of aluminized 

or cold roll steel with a minimum thickness 

of 0.021” or 0.53 mm. It is strictly forbidden 

to use galvanized steel.

To Stove

Your smoke pipe should be assembled in 

such a way that the male section (crimped 

end) of the pipe faces down. This will allow 

condensation in the flue to run back into the 

heater. Attach each of the sections to one 

another with three equidistant metal screws 

and seal each joint with furnace cement.
The  pipe  must  be  short  and  straight.  All 

sections installed horizontally must slope at 

least 1/4 inch per foot, with the upper end 

of the section toward the chimney.
To insure a good draft, the total length of 

the coupling pipe should never exceed 8’ 

to 10’ (2.4m to 3.04 m). (Except for cases 

of vertical installation, cathedral-roof style 

where  the  smoke  exhaust  system  can 

be  much  longer  and  connected  without 

problem to the chimney at the ceiling of 

the room).
It is recommended that no more than two 

90 degree bends be used because it may 

reduce the amount of natural draft. The use 

of  corrugated  (non-adjustable)  elbows  is 

preferred as they are much more airtight.
You  must  have  at  least  18  inches  of 

clearance between any horizontal piping 

and the ceiling.
The pipe cannot extend into the chimney 

flue.
The  chimney  connector  must  not  pass 

through  an  attic,  roof  space,  closet,  any 

concealed  space,  floor,  ceiling,  wall  or 

combustible construction. Where passage 

through a wall or partition of combustible 

construction, the installation must conform 

to  CAN/CSA-B365,  Installation  Code  for 

Solid-Fuel-Burning Appliances & Equipment.

ExTERNAL pARTS DIAgRAM/LIST

10

12

14

13

3

2

17

18

1

15

11

6

4

6

5

8

9

9

7

16

Key

part No.

Description

Qty.

1

67725P

Panel, Cabinet Front - Pewter

1

2

23477

Shield, Top Thermo

1

3

67967B

Cabinet, Left

1

4

67968B

Frame, Door

1

5

67969B

Door, Cabinet

1

6

89065

Hinge, Door

4

7

89635

Knob, Door

1

8

83093

Latch, Spring

1

9

83005

#10-24 x 1/2 Machine Screw, PH HD

2

10

69557B

Back, Cabinet

1

11

21063

Brace, Back

2

12

67966B

Top, Cabinet

1

13

21593

Support, Hinge

1

14

83833

Clip, Hinge

1

15

67743

Assy., Thermostat

1

16

69271

Chain & Hook Assembly

1

17

851886

Plate, Control Panel - Wonderluxe

1

18

89687

Knob, Thermostat

1

5

20

Summary of Contents for Wonderluxe B2350B

Page 1: ...OPERATION REPAIR PARTS Tested To UL 1482 06 ULC S627 00 851884 United States Stove Company 227 Industrial Park Rd P O Box 151 South Pittsburg TN 37380 423 837 2100 www USSTOVE com CAUTION Please read...

Page 2: ...in good repair Have the chimney inspected by the Fire Department or a qualified inspector such as a Chimney sweep Your insurance company may be able to recommend a qualified inspector 6 Inspect chimn...

Page 3: ...ector However therearelimits tohowclose theheater and chimney connector can be installed to combustible surfaces protected by a clearance reduction system Acorrectlyinstalledclearancereductionsystem p...

Page 4: ...ou have the clearances shown from the heater and the connector pipe to combustible surfaces If you have a solid brick or stone wall behind your heater you can place the heater as close as you wish to...

Page 5: ...metal screws and seal each joint with furnace cement The pipe must be short and straight All sections installed horizontally must slope at least 1 4 inch per foot with the upper end of the section to...

Page 6: ...e house Therefore the gas which circulates will cool more slowly thus reducing the build up of creosote and the risk of chimney fires 4 The draft caused by the tendency for hot air to rise will be inc...

Page 7: ...age firestops where needed FACTORY BUILT CHIMNEY insulation shield roof flashing chimney cap etc Maintain proper clearance to the structure as recommended by the manufacturer The chimney must be the r...

Page 8: ...ace with refractory mortar The thimble should be surrounded on all sides with 8 inches of brickwork solid masonry units or 24 inches of stone Install the stovepipe as far as possible into the thimble...

Page 9: ...onjunction with its height or some other factor of an indeterminate cause In this event you should install a barometric draft regulator Such installation will preclude any over firing and or any hazar...

Page 10: ...x The first flames will be long and generally orange or yellow and produce quite a bit of smoke As the gases burn off the flames become shorter change color and produce less smoke Once the fire is WEL...

Page 11: ...n 2 5 16 and 4 3 8 Note that it is important to the life of your stove to buy coal which has been sized and cleaned Cleaning insures removal of rocks and other materials DO NOT burn coke charcoal high...

Page 12: ...r speed reduces 3 Rotate the knob counter clock wise to turn OFF A B C D Follow these instructions to operate you unit safely when operating the feed door NOTE DURING OPENING AND CLOSING OF THE FEED A...

Reviews: