G. The display reads: OVERRANGE!
Intent: Determine correctness of One Series Measurement/Message
H. The display reads: OUT OF RANGE!
Intent: Determine correctness of One Series Measurement/Message
This indicates that the measured process variable has exceeded the maximum
range value and is out of measurement range.
Verify process variable
measurements. If the process
variable is not over the range
limits, contact United Electric
Controls or their authorized
Distributor for further assis-
tance.
You have attempted to set the product Set Point and/or Deadband beyond the cal-
ibrated range of the product.
Verify the range of the One
Series product on the name-
plate. Verify desired Set Point
and Deadband values to ensure
that they do not exceed the
maximum or minimum range
values
Table 1 Switch Output Modes:
Mode
Output Closed
Deadband is
Status & IAW Flash
High Limit Alarm
above set point
below set point
above set point
High Limit Shutdown
below set point
below set point
above set point
Low Limit Alarm
below set point
above set point
below set point
Low Limit Shutdown
above set point
above set point
below set point
Example
:
For High Limit Alarm, when the pressure goes above Set Point the output closes. Both
the local and remote status indicators flash, signaling a tripped output. The switch resets once
the pressure has dropped below the set point value minus the deadband, and both the Output
Status LED and IAW output signals return to steady ON.
I. The display reads: CALL FOR SERVICE
Intent: Determine correctness of One Series Measurement/Message
The One Series self-diagnostics has determined that there is a problem with one
of the componets or the system needs factory re-calibration.
Your One Series requires serv-
ice. Call UE Customer Service at
(617)926-1000 or your local
distributor.