General Information
Inspection Of Equipment
Upon receipt of the unit, inspect for visible or concealed
interior / exterior damage� Report any damage to the carrier,
and file a damage claim.
Inspect the unit data plate to verify the model unit that was
ordered is what has been received�
Some options / accessory items may have been shipped
loose in one or more boxes� These may have been delivered
to another location, or possibly within the unit� If shipped with
the unit there will be a sticker that identifies where in the
unit the shipped loose items are located. Confirm that all of
these options / accessory items are also available and that
no damage has occurred�
Handling
To facilitate handling, the unit is set on a wooden skid so
that it may be picked up with a two-wheel hand truck or fork
lift� Under no circumstances should the unit or the skid be
“walked” on the corners� Use dolly trucks, pipe rollers or
suitable means to move the unit to its proper location�
If a crane, cables or slings are used to move a unit or module,
spreader bars must be used to protect each section’s
cabinet structure� Some units or modules will be provided
with either lifting eyelets or brackets that should be used to
lift the sections�
When vertical style units are shipped split, or will be split in
the field and then reassembled in the space, the condensing
section has refrigerant lines that extend above the top of the
cabinet�
When the unit is assembled these fittings are recessed into
the evaporator section . These fittings extend approximately
5” for all models (Figure 1)�
The space height needs to be sufficient to handle not only
the combined unit height, but also the refrigerant fitting
clearance height�
Figure 1
Mounting And Setting In Place
CAUTION
Unit should not be located in space subject
to freezing temperatures�
The VertiCool Classic has been designed to be installed as
a single package floor mounted unit.
Unit is to be mounted on a solid floor or supported on a
full 100% perimeter frame. Attention must be given to floor
loading limitations� Floor should be level in both horizontal
planes�
Before the unit is installed, a thorough study should be made
of the structure and proposed installation location� Careful
consideration must be given to location of wiring, condensate
disposal, ductwork and accessibility for maintenance
or service� It is necessary that a minimum clearance of
36” be allowed on the front of the cabinet� Some air path
configurations will also require side access to the evaporator
section. Sufficient clearance must be provided to slide the
air filter(s) out, either the left or right side.
Consideration must be made for condensate removal, either
with a trap or condensate pump�
The units might be shipped as a single package or they
might be shipped split� Units that have been ordered with
the optional resealable refrigerant fittings can be split in the
field to accommodate moving into position. Sections are
also bolted together�
When re-assembling the evaporator section to the
condensing section, use a sling or other suitable means that
is sufficient to hold the weight of the section. Use spreader
bars to keep the cabinet from being deformed�
Make sure that the evaporator section is positioned correctly
for the desired air pattern� Care must be taken when lowering
the evaporator section that the refrigerant resealable fittings
are lined up properly and that they are not damaged in this
process� Re-install the fasteners if removed prior�
5"