Installation, Operation and Maintenance Manual
VertiCool Classic
14
Subject to change without notice.
20.10-IM (0617)
System Options
Humidifier
The optional steam humidifier that comes with the unit
functions on the electrode principle. As water fills the plastic
steam generator, it immerses metal electrodes then permits
electrical current flow through the water. This current flow
produces heat which then boils the water into steam� This
steam is then injected on the downstream side of the cooling
coil to provide humidification for the area being served by
the unit� Water is replenished through tubing and the 1/4”
flare located on the evaporator section structure. For further
information refer to the Humidifier Installation Instruction
which accompanies the unit�
INFORMATION
The humidifier should not be subjected
to freezing air conditions� If the unit will
be used for outside air applications an
externally mounted humidifier should be
used�
Auxiliary Coils (Hot Water or Steam)
A hot water coil or steam coil when used as heat will be
located in the return air stream between the filters and the
evaporator coil� These are typically installed at the factory�
Some units will include Jack Stands to support the auxiliary
coil / filter box. If the unit is shipped as a single package the
jack stands will be attached� Care should be taken when
moving the unit from the skid to the installation location so
as not to tear or loosen the jack stand where it is attached
to the cabinet�
If the evaporator section is shipped loose the auxiliary coil
section will be attached to the evaporator� The jack stands,
if required, will be placed inside the auxiliary coil section�
The mounting hard- ware will be attached to the jack stand
flange.
If an optional hot water valve is ordered, this will be shipped
loose for installation in the field.
Control wiring will need to be installed from the hot water
valve back to the unit control panel� Follow all National
Electrical Codes and Local Codes as required�
Any steam valves and other adjunct steam components are
to be field supplied and installed by others.
Control wiring will need to be installed from the steam valve
back to the unit control panel� Follow all National Electrical
Codes and Local Codes as required�
A pan is included under any hot water coil or steam coil� A
condensate trap will need to be installed for this drain pan� A
trap will need to be installed since this line is in a negative air
stream� Follow the same procedures for this line as for the
unit condensate drain line outlined on page 6�
Pipe the hot water coil or steam coil per industry accepted
practices�
Water Side Economizer (Free Cooling Coil)
A water side economizer coil will be located in the return air
stream between the filters and the evaporator coil. These
are typically installed at the factory�
Some units will include Jack Stands to support the water
side economizer / filter box. If the unit is shipped as a single
package the jack stands will be attached� Care should be
taken when moving the unit from the skid to the installation
location so as not to tear or loosen the jack stand where it is
attached to the cabinet�
If the evaporator section is shipped loose the water side
economizer section may or may not be attached to the
evaporator� The jack stands, if required, will be placed inside
the water side economizer section� The mounting hardware
will be attached to the jack stand flange.
If the unit is shipped as a single package, the water piping
from the unit to water side economizer coil will be factory
installed�
If the water side economizer is shipped as a separate section
or if the unit comes with the evaporator and water side
economizer as a section, the water piping will be shipped
loose for field attachment.
Air Side Economizer
The air side economizer option is installed on the rear of the
cabinet�
Some units will include Jack Stands to support the air side
economizer / filter box. If the unit is shipped as a single
package the jack stands will be attached� Care should be
taken when moving the unit from the skid to the installation
location so as not to tear or loosen the jack stand where it is
attached to the cabinet�
If the evaporator section is shipped loose the air side
economizer section may or may not be attached to the
Continued on next page