Installation, Operation and Maintenance Manual
Marvel Plus
22
Subject to change without notice.
120.5-IM (1018)
U01
Air Econo
Action Direct
Minimum 00.0vdc
Maximum 10.0vdc
U01
WSE Valve
Action Direct
Minimum 00.0vdc
Maximum 10.0vdc
Digital Inputs
All digital input active states may be viewed by these
screens� Act are the Active states� The Alarms On is the
state where the input will signal the Marvel Plus to initiate
an alarm condition� The Alarms On state can be changed to
activate either on Open or Close depending on the device
being connected to its particular input�
U01
Digital Inputs
Alarms ON: Actual
C1 HP
OPEN
CLOSE
C1 LP
OPEN
CLOSE
C2 HP
OPEN
CLOSE
C2 LP
OPEN
CLOSE
Airflow OPEN
CLOSE
Mrn Wrn CLOSE
OPEN
U01
Digital Inputs
Alarms ON: Actual
WF/DP OPEN CLOSE
C3 HP
OPEN
CLOSE
C3 LP
OPEN
CLOSE
C4 HP
OPEN
CLOSE
U01
Digital Inputs
Alarms ON: Actual
Filter OPEN CLOSE
Hi-Heat OPEN CLOSE
Freeze OPEN CLOSE
Fan Ovld2 OPEN
CLOSE
Alarm Logic Manual Reset Screen
U01
Alarm Logic
Manual Reset
Fire Alarm > NO
The Alarm Logic Manual Reset allows each listed function to
be set up as either automatic or manual reset type� In either
case, the alarm still appears on the display screen�
Economizer Setup Screen
U01 Economizer
Type: Enthalpy
Assist Mode:
On
Damper Minimum:
010%
Compressor-
Assist Delay:
000min
The Economizer setup screens allow setup of economizer
related functions�
The economizer screen is used to set the type of economizer
control (off, chilled water, free-cool, enthalpy, or dew point)�
Assist Mode allows compressors to assist the economizer
mode of operation� Damper Minimum is the minimum
position set point for the Outdoor Air Economizer Damper
to be open for minimum fresh air requirements during the
occupied mode� Compressor Assist Delay is the time delay
in minutes before the compressor is allowed to assist the
Economizer function�