United CoolAir Marvel BMS Installation, Operation And Maintenance Manual Download Page 9

Installation, Operation and Maintenance Manual

Marvel BMS

9

Subject to change without notice.

120.5-IM (0419)

Troubleshooting

It is very important to eliminate possibility of field errors before adjusting the controller. No field 

wiring, network, or BMS server programming are addressed here.

Issue

Possible cause

Remedy

Failure to communicate to the board 

entirely Attempt1

BMS connection placed on the control 

board’s communication ports and not 

the serial card communication ports

Verify the bms cable is landed ONLY on 

the serial card ports and not the Rxtx 

on the CAREL board or the Ethernet 

port on the control board�

Failure to communicate to the board 

entirely Attempt2

BMS setup is not properly set for the 

protocol in the controller

Enter the BMS setup in the programs 

main menu and verify the protocol and 

baud rate is setup as prescribed�

Failure to communicate to board 

entirely Attempt3 Bacnet protocols only

Pco net/web may not be properly setup 

in the field configuration area.

Verify the Pcoweb/Pconet settings 

were  configured  properly  as  specified 

in the Network Connection Settings 

And Access section

BMS communication is connected but 

no values or points can be pulled

BMS setup is not properly set for the 

protocol in the controller because the 

serial card can’t read the boards output

Enter the BMS setup in the programs 

main menu and verify the protocol and 

baud rate is setup as prescribed�

BMS cannot read certain units in the 

network

The individual addresses may be setup 

improperly or not at all�
For Bacnet mstp, the termination 

jumpers on the serial card are not 

installed properly for the installation of 

the field setup.

Verify the Pcoweb/Pconet settings 

were  configured  properly  as  specified 

in the Network Connection Settings 

And Access section
Adjust jumpers on Bacnet mstp cards 

correctly per field requirements

Summary of Contents for Marvel BMS

Page 1: ...Marvel BMS communications Installation Operation and Maintenance Manual Effective April 2019 Interactive PDF DISCONTINUED For Reference Only ...

Page 2: ...d Installation 6 Initial installation 6 Connection Setup from Marvel to Serial Card 6 Network Connection Settings and Access 6 Accessing Bacnet network settings 6 PCONET adjustable parameters for Bacnet protocol Bacnet MS TP setup 7 PCOWEB adjustable parameters for Bacnet protocol Bacnet IP setup 7 LonWorks setup 7 Modbus setup 7 Points list s referencing 7 CSV Files 8 Troubleshooting 9 ...

Page 3: ...e existing Marvel controllers and although some may have more ability than others they all have ability s that are most commonly associated with a BMS management system such as system on off Alarm monitoring status monitoring conditions monitoring and set points access All Marvel equipment can communicate via Bacnet Modbus andLonWorks Allcontrollersrequireaserialcommunications card which is not a ...

Page 4: ...vel BMS 4 Subject to change without notice 120 5 IM 0419 There are several different types of communication cards available to communicate via BMS LonWorks FIG1 Bacnet mstp FIG2 Bacnet Modbus IP FIG3 Modbus mstp FIG4 Fig 1 Fig 3 Fig 2 Fig 4 Components ...

Page 5: ...Installation Operation and Maintenance Manual Marvel BMS 5 Subject to change without notice 120 5 IM 0419 Architectural Layout ...

Page 6: ...nto the bay properly Connection Setup from Marvel to Serial Card Once your serial card is in the Marvel Controller you will need to setup the communication between the Marvel Controller and the Serial card that was installed Boot the controller and use the keypad provided to access the main menu list Scroll down to the BMS setup Inside the BMS setup there are only 3 options to setup These settings...

Page 7: ...aspects of the Bacnet protocol for your network in this page You can adjust options such as the Bacnet ID the Bacnet Baud The Bacnet MAC address the max masters and the max frames The last menu option is the update current info option You simply have to select NO to restart at the top or YES to save the information entered on this page PCOWEB adjustable parameters for Bacnet protocol Bacnet IP set...

Page 8: ...ed by the factory There is a vast amount of manual control points that can be controlled by a BMS system Their main function is for testing of equipment not for operating them on a daily bases It is a must to read and understand the computer controller IOM for your unit prior to attempting to control monitor anything other than your system on off and occupied unoccupied control Points list s refer...

Page 9: ...te is setup as prescribed Failure to communicate to board entirely Attempt3 Bacnet protocols only Pco net web may not be properly setup in the field configuration area Verify the Pcoweb Pconet settings were configured properly as specified in the Network Connection Settings And Access section BMS communication is connected but no values or points can be pulled BMS setup is not properly set for the...

Page 10: ...or All Indoor HVAC Projects Authorized Distributor LIMITED WARRANTY United CoolAir Units are backed by a 1 year limited warranty on parts and a 5 year limited warranty on the compressor labor not included Maintenance items such as filters and belts are excluded under this limited warranty FACTORY TESTED All units are functionally run tested before shipment to ensure a trouble free start up and uni...

Reviews: