Select the PCOWEB/PCONET settings next� The next menu 

will allow you to choose the most appropriate selection based 

on the type of BMS you are using� WEB for IP or Ethernet 

and NET for rs-485 applications� The pCO web application 

is more complicated to initially start up� The CAREL manual 

specifically for the pCO web can be found here. 

http://www�

carelusa�com/product/pcoweb-card/

Sometimes it is difficult to get the changes to save. If this 

happens revert the settings back to factory and then try to 

save� Factory settings usually save then go back to your 

settings� It saves with a higher percentage when the wiring 

is OFF of the controller’s BMS card� Continue to try to save 

the information in the rare case of saving trouble repeat the 

steps above it will eventually save your settings�

PCONET adjustable parameters for Bacnet 

protocol. Bacnet MS/TP setup.

You can setup various aspects of the Bacnet protocol for 

your network in this page� You can adjust options such as the 

Bacnet ID, the Bacnet Baud, The Bacnet MAC address, the 

max masters and the max frames� The last menu option is 

the update current info option� You simply have to select NO 

to restart at the top or YES to save the information entered 

on this page�

PCOWEB adjustable parameters for Bacnet 

protocol. Bacnet IP setup.

For Bacnet WEB applications you can set up options like 

your DHCP MODE, IP address, and Net mask, Gateway, 

DNS1, DNS2, Bacnet ID and Bacnet Type of IP or Ethernet� 

The last menu option is the update current info option� You 

simply have to select NO to restart at the top or YES to save 

the information entered on this page�

LonWorks setup

LonWorks requires factory setup of the LonWorks cards� 

The  cards  firstly  must  all  have  the  same  SPID  number  to 

communicate on the same network� This is crucial� UCA 

facility’s handle the setup and configuration of the LonWorks 

card itself. Some field adjustment will likely be required.

Modbus setup

Modbus only requires the setup as shown in 

Connection 

Setup from Marvel to Serial Card

, once the protocol is set 

to Modbus, it will be ready to communicate�

Summary of Contents for Marvel BMS

Page 1: ...Marvel BMS communications Installation Operation and Maintenance Manual Effective April 2019 Interactive PDF DISCONTINUED For Reference Only ...

Page 2: ...d Installation 6 Initial installation 6 Connection Setup from Marvel to Serial Card 6 Network Connection Settings and Access 6 Accessing Bacnet network settings 6 PCONET adjustable parameters for Bacnet protocol Bacnet MS TP setup 7 PCOWEB adjustable parameters for Bacnet protocol Bacnet IP setup 7 LonWorks setup 7 Modbus setup 7 Points list s referencing 7 CSV Files 8 Troubleshooting 9 ...

Page 3: ...e existing Marvel controllers and although some may have more ability than others they all have ability s that are most commonly associated with a BMS management system such as system on off Alarm monitoring status monitoring conditions monitoring and set points access All Marvel equipment can communicate via Bacnet Modbus andLonWorks Allcontrollersrequireaserialcommunications card which is not a ...

Page 4: ...vel BMS 4 Subject to change without notice 120 5 IM 0419 There are several different types of communication cards available to communicate via BMS LonWorks FIG1 Bacnet mstp FIG2 Bacnet Modbus IP FIG3 Modbus mstp FIG4 Fig 1 Fig 3 Fig 2 Fig 4 Components ...

Page 5: ...Installation Operation and Maintenance Manual Marvel BMS 5 Subject to change without notice 120 5 IM 0419 Architectural Layout ...

Page 6: ...nto the bay properly Connection Setup from Marvel to Serial Card Once your serial card is in the Marvel Controller you will need to setup the communication between the Marvel Controller and the Serial card that was installed Boot the controller and use the keypad provided to access the main menu list Scroll down to the BMS setup Inside the BMS setup there are only 3 options to setup These settings...

Page 7: ...aspects of the Bacnet protocol for your network in this page You can adjust options such as the Bacnet ID the Bacnet Baud The Bacnet MAC address the max masters and the max frames The last menu option is the update current info option You simply have to select NO to restart at the top or YES to save the information entered on this page PCOWEB adjustable parameters for Bacnet protocol Bacnet IP set...

Page 8: ...ed by the factory There is a vast amount of manual control points that can be controlled by a BMS system Their main function is for testing of equipment not for operating them on a daily bases It is a must to read and understand the computer controller IOM for your unit prior to attempting to control monitor anything other than your system on off and occupied unoccupied control Points list s refer...

Page 9: ...te is setup as prescribed Failure to communicate to board entirely Attempt3 Bacnet protocols only Pco net web may not be properly setup in the field configuration area Verify the Pcoweb Pconet settings were configured properly as specified in the Network Connection Settings And Access section BMS communication is connected but no values or points can be pulled BMS setup is not properly set for the...

Page 10: ...or All Indoor HVAC Projects Authorized Distributor LIMITED WARRANTY United CoolAir Units are backed by a 1 year limited warranty on parts and a 5 year limited warranty on the compressor labor not included Maintenance items such as filters and belts are excluded under this limited warranty FACTORY TESTED All units are functionally run tested before shipment to ensure a trouble free start up and uni...

Reviews: