Installation, Operation and Maintenance Manual
Marvel BMS
7
Subject to change without notice.
120.5-IM (0419)
Select the PCOWEB/PCONET settings next� The next menu
will allow you to choose the most appropriate selection based
on the type of BMS you are using� WEB for IP or Ethernet
and NET for rs-485 applications� The pCO web application
is more complicated to initially start up� The CAREL manual
specifically for the pCO web can be found here.
http://www�
carelusa�com/product/pcoweb-card/
�
Sometimes it is difficult to get the changes to save. If this
happens revert the settings back to factory and then try to
save� Factory settings usually save then go back to your
settings� It saves with a higher percentage when the wiring
is OFF of the controller’s BMS card� Continue to try to save
the information in the rare case of saving trouble repeat the
steps above it will eventually save your settings�
PCONET adjustable parameters for Bacnet
protocol. Bacnet MS/TP setup.
You can setup various aspects of the Bacnet protocol for
your network in this page� You can adjust options such as the
Bacnet ID, the Bacnet Baud, The Bacnet MAC address, the
max masters and the max frames� The last menu option is
the update current info option� You simply have to select NO
to restart at the top or YES to save the information entered
on this page�
PCOWEB adjustable parameters for Bacnet
protocol. Bacnet IP setup.
For Bacnet WEB applications you can set up options like
your DHCP MODE, IP address, and Net mask, Gateway,
DNS1, DNS2, Bacnet ID and Bacnet Type of IP or Ethernet�
The last menu option is the update current info option� You
simply have to select NO to restart at the top or YES to save
the information entered on this page�
LonWorks setup
LonWorks requires factory setup of the LonWorks cards�
The cards firstly must all have the same SPID number to
communicate on the same network� This is crucial� UCA
facility’s handle the setup and configuration of the LonWorks
card itself. Some field adjustment will likely be required.
Modbus setup
Modbus only requires the setup as shown in
Connection
Setup from Marvel to Serial Card
, once the protocol is set
to Modbus, it will be ready to communicate�