NOTE:
A 1” clearance must be provided between any combus-
tible material and the supply air ductwork for a distance
of 3 feet from the unit.
NOTE:
The products of combustion must not be allowed to
accumulate within a confined space and recirculate.
NOTE:
Locate unit so that the vent air outlet hood is at least:
• Three (3) feet above any force air inlet located within
10 horizontal feet (excluding those integral to the
unit).
• Four (4) feet below, 4 horizontal feet from, or 1 foot
above any door or gravity air inlet into the building.
• Four (4) feet from electric and gas meters, regulators
and relief equipment.
NOTE:
All entry holes should be field sealed to prevent rain
water entry into building.
FIGURE 13 - UNIT DIMENSIONS & CLEARANCES 15 & 20 TON
RETURN
AIR
SUPPLY
AIR
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
(B)
POWER WIRING
ENTRY
(A)
CONTROL WIRING
ENTRY
NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.
UNIT BASE WITH RAILS
Shown separately to illustrate
Bottom Duct openings, Power
and Gas Piping Connection
locations
12-1/2"
9-1/4"
8-1/8"
9-3/4"
3-3/4"
(B)
POWER WIRING
ENTRY
(A)
CONTROL WIRING
ENTRY
CONDENSER
COILS
OPTIONAL COIL
GUARD KIT
COMPRESSOR
ACCESS
(See detail "X")
ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
BLOWER
ACCESS
BLOWER MOTOR
ACCESS
BLOWER
COMPARTMENT
ACCESS
(Auxiliary)
DOT PLUG
(For pressure
Drop Reading)
FRONT
VIEW
CONTROL BOX
ACCESS
21"
5"
9-3/4"
11-1/2"
2-3/4"
21-1/2"
33"
35"
5-7/8"
46-5/8"
7-1/8"
6-3/8"
VENT AIR
OUTLET
HOODS
COMBUSTION
AIR INLET
HOOD
GAS HEAT
ACCESS
(C)
GAS SUPPLY
ENTRY
46-5/8"
11-1/8"
(D)
GAS SUPPLY
ENTRY
RETURN AIR
SUPPLY AIR
OUTDOOR AIR
OUTDOOR AIR
(Economizer)
92"
24-1/4"
(15
Ton)
35-1/4"
(20
Ton)
125-1/4"
(15
Ton)
136-1/4"
(20
Ton)
48-5/8" (15 Ton)
52-5/8" (20 Ton)
All dimensions are in inches. They are
subject to change without notice. Certi-
fied dimensions will be provided upon
request.
TABLE 11: MINIMUM CLEARANCES
LOCATION
CLEARANCE
Front
36”
Back
24” (Less Economizer)
49” (With Economizer
Left Side (Filter Access)
24” (Less Economizer)
36” (With Economizer)
Right Side (Cond. Coil)
36”
Below Unit
1
1.
Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
0”
Above Unit
2
2.
Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
72” With 36” Maximum
Horizontal Overhang (For
Condenser Air Discharge)
TABLE 12: UTILITIES ENTRY
HOLE
OPENING SIZE (DIA.)
USED FOR
A
1-1/8” KO
Control Wiring
Front
3/4” NPS (Fem.)
Bottom
B
3-5/8” KO
Power Wiring
Front
3” NPS (Fem.)
Bottom
C
2-3/8” KO
Gas Piping (Front)
1
1.
One-inch Gas Piping MPT Required.
D
1-11/16” Hole
Gas Piping (Bottom)
1,2
2.
Opening in the bottom to the unit can be located by the
side in the insulation.