background image

035-17438-001 Rev. A (901)

Unitary Products Group

21

Hot Surface Ignition System

MAINTENANCE

Air Filters

The filters should be checked periodically for dirt accumula-
tion. Dirty filters greatly restrict the flow of air and overburden
the system.

Clean the filters at least every three months. On new con-
struction, check the filters every week for the first four weeks.
Inspect the filters every three weeks after that, especially if
the system is running constantly.

All filters used with the furnace are the high velocity, clean-
able type. Clean these filters by washing in warm water.
Make sure to shake all the water out of the filter and have it
reasonably dry before installing it in the furnace. When
replacing filters, be sure to use the same size and type as
originally supplied.

Upflow Filter Removal and Replacement

1.

Turn off electrical power supply to the furnace at discon-
nect switch. Remove access doors.

2.

In the blower compartment disengage the looped end of 
the filter retainer wire from the front edge of the cabinet. 
The wire will now pivot on the hinged ends at the rear of 
the cabinet. Refer to Figure  3 on page 9.

3.

Remove the filter and follow the cleaning instructions 
above. DO NOT remove the filter stiffener rods, if pro-
vided.

4.

When reinstalling the filter, be sure the filter completely 
covers the cabinet opening and is secured in place by 
the wire retainer.

Lubrication

Blower and ventor motors in these furnaces are permanently
lubricated and do not require periodic oiling.

BLOWER CARE

Even with good filters properly in place, blower wheels and
motors will become dust laden after long months of operation.
The entire blower assembly should be inspected annually. If
the motor and wheel are heavily coated with dust, they can
be brushed and cleaned with a vacuum cleaner.

The procedure for removing the direct drive blower assembly
for cleaning is as follows:

Upflow Blower Removal/Cleaning

The procedure for removing the variable speed blower
assembly for cleaning is as follows:

1.

Disconnect the power supplied to the furnace.

2.

Remove the vest and blower panels.

3.

Disconnect the motor control harness and the power har-
ness from the motor.

4.

Remove the 2 screws fastening the electrical panel to 
the blower housing, remove the panel from the blower 
housing and swing the assembly out of the way.

5.

Disconnect the auxiliary switch harness from the 
switches.

6.

Remove the 5 blower assembly mounting screws and 
pull the blower assembly forward and out of the slots in 
the deck.

7.

Clean and or service the blower assembly being careful 
not to remove tor relocate the balance clips on the 
blower wheel.

8.

To reassemble, reverse the procedure, restore power to 
the furnace and verify operation.

9.

Two vertical screws do not need to be reinstalled.

NOTE:  

DO NOT Remove or Relocate the Balance Clips

on the blower wheel when cleaning the blower assembly.
An unbalanced wheel will cause noise and vibrations.

Burner and Flame Sensor Removal/Cleaning

The main burners should be checked periodically for dirt
accumulation.

If cleaning is required, follow this procedure:

1.

Turn off the electrical power to the unit and turn off gas 
supply at the shutoff valve.

2.

Remove the blower and burner compartment access 
doors.

3.

Unplug ignitor from the wire harness and remove the 
ignitor/bracket assembly from the burner air shield. Han-
dle the ignitor carefully as it is fragile and easily broken.

4.

Note the location and then disconnect the sensor and 
rollout switch wires located on the top of the air shield 
and remove the shield.

5.

Remove the two screws securing each burner to the 
burner assembly. Note the orientation of the burner 
(flanged side down) before removing. Burners may be 
cleaned by rinsing in hot water or by using a vacuum 
cleaner.

6.

Remove the retaining screw to the flame sensor and 
remove the sensor from the burner box. Clean the flame 
sense rod with steel wool and replace.

Do not attempt to light this furnace by hand (with a
match or any other means). There may be a poten-
tial shock hazard from the components of the hot
surface ignition system. The furnace can only be lit
automatically by its hot surface ignition system.

Summary of Contents for PxDUA12V06401 series

Page 1: ...035 17438 001 Rev A 901 EFFICIENCY RATING CERTIFIED CAUTION READ ALL SAFETY GUIDES BEFORE YOU START TO INSTALL YOUR FURNACE SAVE THIS MANUAL TABLE OF CONTENTS GENERAL INFORMATION 2 UNIT INSTALLATION 3...

Page 2: ...PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE REFER TO THIS MANUAL FOR ASSISTANCE OR AD...

Page 3: ...ptable heat loss calculation for the structure ACCA Manual J or other approved methods may be used The furnace should be located using these guidelines 1 Where a minimum amount of vent piping and elbo...

Page 4: ...the total input rating of all equipment located in the enclosure b Not less than the sum of the areas of all vent con nectors in the confined space 3 Louvers Grilles and Screens a In calculating free...

Page 5: ...nds in a general vertical direction and does not con tain offsets exceeding 45 degrees except that a vent system having not more than one 60 degree offset is permitted NOTE This appliance may be commo...

Page 6: ...nce being operated in operation Adjust thermostat so appli ance will operate continuously 5 Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main bur...

Page 7: ...V UH INPUT MBH H L OUTPUT MBH H L NOM CFM CABINET WIDTH IN AFUE1 LOW FIRE TEMP RISE F HIGH FIRE TEMP RISE MAX OUTLE AIR TEMP F BLOWER TOTAL UNIT AMPS MAX OVER CURRENT PROPECT2 MIN WIRE SIZE AWG 75 FT...

Page 8: ...removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi cate the presence of leaks in the heat exchanger This access...

Page 9: ...and notes on blower perfor mance tables in this manual Where the return duct system is not complete the return con nection must run full size to a location outside the utility room or basement For fur...

Page 10: ...s is recommended Refer to Fig ure 6 on page 10 NOTE See crawl space installation for suspending the fur nace in attic installations CRAWL SPACE INSTALLATION The furnace can be hung from floor hoists o...

Page 11: ...cordance with instructions Specific electrical data is given on the furnace rating plate Provide a power supply separate from all other circuits Install overcurrent protection and disconnect switch pe...

Page 12: ...OFF position and the main electrical source disconnected complete the low voltage wiring from the ther mostat to the terminal board on the CFM programmable board Connect Class 2 control wiring see Fig...

Page 13: ...nt 1 Blockage of internal flue gas passage ways 2 Blockage of vent piping 3 Failure of combustion air blower motor Limit Control The high temperature limit control is located on the furnace vestibule...

Page 14: ...increment find the cubic feet of gas consumed per hour from Table 4 on page 15 NOTE To find the Btuh input multiply the number of cubic feet of gas consumed per hour by the BTU content of the gas in y...

Page 15: ...cement The temperature rise or temperature difference between the return air and the heated air from the furnace must be within the range shown on the furnace rating plate Application limi tations are...

Page 16: ...uction for the recommended airflow and Table 6 on page 17 The DELAY Tap should be set in the B position for a two stage condenser This results in a 45 second off delay at 82 of the programmed cooling...

Page 17: ...002UHC11 L8V1002UHC11 P DUC20V09601 G8V12020UHC11 L8V12020UHC11 COOL TAP ADJ TAP High Low High Low High Low High Low 1340 740 1675 920 2050 1135 2020 1130 A B 1155 635 1555 850 1860 980 1855 960 B B 1...

Page 18: ...is fixed at 60 seconds for SEER enhance ment HEATING OPERATIONAL SEQUENCE Two Stage Thermostat The ignition control in this furnace is unique to this product The control allows for a 24 volt or a 115...

Page 19: ...gas valve When power is restored the gas valve will remain deener gized and a restart of the ignition sequence will begin imme diately A momentary loss of gas supply flame blowout or a shorted or open...

Page 20: ...LOW INDUCER LOW STAGE PRESSURE SWITCH HSI 1ST STAGE MAIN VALVE FLAME SENSE LOW CIRCULATOR HEAT SPEED 1ST STAGE LOW PRESSURE SWITCH CLOSE RECOGNITION HSI WARM UP 17 SEC IGNITION ACTIVATION PERIOD 4 SE...

Page 21: ...bly for cleaning is as follows 1 Disconnect the power supplied to the furnace 2 Remove the vest and blower panels 3 Disconnect the motor control harness and the power har ness from the motor 4 Remove...

Page 22: ...including the flue baffle plate rear may be vacuumed or cleaned with hot water if necessary 6 The upper portion of the heat exchanger is now accessi ble With a long flexible wire brush clean inside ea...

Page 23: ...R REMOVAL FOR CONTROLLER REPLACEMENT Refer to BLOWER CARE on page 21 of this manual for blower removal instructions Rest the blower on its side so the end of the motor is accessible and facing up Wait...

Page 24: ...ehind a clear view port in the blower compartment door DO NOT remove the furnace blower compartment panel OR turn off furnace power as either action will clear the control s memory of the fault The co...

Page 25: ...y low gas pressure faulty gas valve faulty hot surface ignitor reversed line polarity or burner problem 8 FLASH This fault is indicated if the flame is lost 5 times during the heating cycle This could...

Page 26: ...NTROL BOARD P3 S3 2 PIN PLUG SOCKET AT HOT SURFACE IGNITOR P4 S4 3 PIN PLUG SOCKET AT INDUCER MOTOR P5 S5 3 PIN PLUG SOCKET ON VALVE P6 S6 6 PIN PLUG SOCKET ON CFM TIMER BOARD P7 S7 16 PIN PLUG SOCKET...

Page 27: ...035 17438 001 Rev A 901 Unitary Products Group 27 SERVICE RECORDS...

Page 28: ...hange without notice Printed in U S A 035 17438 001 Rev A 901 Copyright by York International Corp 2001 All rights reserved Supersedes 035 17438 001 Rev A 801 Unitary 5005 Norman Product York OK Group...

Reviews: