background image

035-17438-001 Rev. A (901)

16

Unitary Products Group

Increase the blower speed to decrease the temperature rise;
decrease the blower speed to increase the rise.

All direct-drive blowers have multi-speed motors. The blower
motor speed taps are located in the control box in the blower
compartment.

You may select a heating speed and a cooling speed. They
may be the same speed or a different speed.

To use the same speed tap for heating and cooling, the heat
terminal and cool terminal must be connected using a jumper
wire and connected to the desired motor lead. Place all
unused motor leads on Park terminals. Two Park terminals
are provided.

Variable Speed Motors

The temperature rise, or temperature difference between the
return air and the heated air from the furnace, must be within
the range shown on the furnace rating plate and within the
application limitations shown in Table 3 on page 7.

HEATING AIRFLOW

The heating airflow has been preset at the factory to provide
maximum CFM. If a lesser CFM is required for a specific
HVAC system the “JUMPER” on the HEAT selection pins on
the CFM-Timer Board may be moved to tap “B” or “C”, or “D”.
Pins “A” will provide the highest CFM and “D” the lowest
CFM. Refer to Table 6 on page 17 for CFM options. 

NOTE:  

Power to the blower must be removed for at least 4

seconds after a heat or cool tap selection change, in order for
the motor to recognize an adjustment.

The fixed blower on delay and adjustable blower-off delay will
function as described in the “OPERATION AND
MAINTENANCE" Section on page 18  of this instruction.

NOTE:  

When changing jumper positions, make sure that

the jumper is pushed all the way on the pins. If the jumper is
not making good contact or is left off completely, the blower
will operate as if the jumper were in the “A” position.

COOLING AIRFLOW

The Cooling airflow is preset at the factory to provide approx-
imately 90% of the maximum CFM and must be adjusted in
the field to match the HVAC system at installation. Refer to
the outdoor unit installation instruction for the recommended
airflow and Table 6 on page 17.

The "DELAY" Tap should be set in the "B" position for a two-
stage condenser. This results in a 45 second off delay at 82%
of the programmed cooling airflow with a 15-second coast to
stop. It should be set in the "C" position for a system with a
TXV or solenoid valve. This results in a 45 second off delay at
75% of the programmed cooing airflow with a 15-second
coast to stop. It should be set in the "D" position for a system

without a TXV or solenoid valve. This results in a 60 second
off delay at 82% of the programmed cooling airflow with a 15-
second coast to stop. The "A" position is the factory setting
and is used for test purposes. With the delay set in the “A”
position, the blower will operate at 100% of the programmed
cooling air flow for 60 seconds, with a 15 second coast to
stop.

NOTE:  

When changing jumper positions, make sure that

the jumper is pushed all the way on the pins. If the jumper is
not making good contact or is left off completely, the blower
will operate as if the jumper were in the “A” position.

ADJUSTMENT OF FAN-OFF CONTROL SETTINGS

This furnace is equipped with a time-on/time-off heating fan
control. The fan-on is fixed at 30 seconds. The fan-off delay is
factory set to 60 seconds, however, it is field adjustable to 90,
120, or 180 seconds. The fan-off setting must be long enough
to adequately cool the furnace, but not so long that cold air is
blown into the heated space.

The continuous fan speed and the fan-off timing may be
adjusted by setting the DIP switches located on the control
board as follows: (See Figure 12 and Table 5).

This continuous fan speed dip switch (switch 3) on the igni-
tion control has no effect on setting and should be left in the
“OFF” position, as continuous fan speed is determined by the
variable speed motor program.  

 

Do not energize more than one motor speed at a
time or damage to the motor will result.

Table 5: 

FAN CONTROL SETTINGS

IGNITION CONTROL

To Delay Fan-Off By:

Set Switch

1-2

60 Sec.

On-On

90 Sec.

Off-On

120 Sec.

On-Off

180 Sec.

Off-Off

 FIGURE 12 : 

Typical Heat/Cool Speed Tap 

Connections

OFF

ON

SWITCH 3 SHOULD
BE LEFT IN “OFF”
POSITION

COOL
HEAT LO
HEAT HI
LINE

WI

W2

Y

R

G

B

FAN OFF
ADJUSTMENT
SWITCHES

Summary of Contents for PxDUA12V06401 series

Page 1: ...035 17438 001 Rev A 901 EFFICIENCY RATING CERTIFIED CAUTION READ ALL SAFETY GUIDES BEFORE YOU START TO INSTALL YOUR FURNACE SAVE THIS MANUAL TABLE OF CONTENTS GENERAL INFORMATION 2 UNIT INSTALLATION 3...

Page 2: ...PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE REFER TO THIS MANUAL FOR ASSISTANCE OR AD...

Page 3: ...ptable heat loss calculation for the structure ACCA Manual J or other approved methods may be used The furnace should be located using these guidelines 1 Where a minimum amount of vent piping and elbo...

Page 4: ...the total input rating of all equipment located in the enclosure b Not less than the sum of the areas of all vent con nectors in the confined space 3 Louvers Grilles and Screens a In calculating free...

Page 5: ...nds in a general vertical direction and does not con tain offsets exceeding 45 degrees except that a vent system having not more than one 60 degree offset is permitted NOTE This appliance may be commo...

Page 6: ...nce being operated in operation Adjust thermostat so appli ance will operate continuously 5 Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main bur...

Page 7: ...V UH INPUT MBH H L OUTPUT MBH H L NOM CFM CABINET WIDTH IN AFUE1 LOW FIRE TEMP RISE F HIGH FIRE TEMP RISE MAX OUTLE AIR TEMP F BLOWER TOTAL UNIT AMPS MAX OVER CURRENT PROPECT2 MIN WIRE SIZE AWG 75 FT...

Page 8: ...removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi cate the presence of leaks in the heat exchanger This access...

Page 9: ...and notes on blower perfor mance tables in this manual Where the return duct system is not complete the return con nection must run full size to a location outside the utility room or basement For fur...

Page 10: ...s is recommended Refer to Fig ure 6 on page 10 NOTE See crawl space installation for suspending the fur nace in attic installations CRAWL SPACE INSTALLATION The furnace can be hung from floor hoists o...

Page 11: ...cordance with instructions Specific electrical data is given on the furnace rating plate Provide a power supply separate from all other circuits Install overcurrent protection and disconnect switch pe...

Page 12: ...OFF position and the main electrical source disconnected complete the low voltage wiring from the ther mostat to the terminal board on the CFM programmable board Connect Class 2 control wiring see Fig...

Page 13: ...nt 1 Blockage of internal flue gas passage ways 2 Blockage of vent piping 3 Failure of combustion air blower motor Limit Control The high temperature limit control is located on the furnace vestibule...

Page 14: ...increment find the cubic feet of gas consumed per hour from Table 4 on page 15 NOTE To find the Btuh input multiply the number of cubic feet of gas consumed per hour by the BTU content of the gas in y...

Page 15: ...cement The temperature rise or temperature difference between the return air and the heated air from the furnace must be within the range shown on the furnace rating plate Application limi tations are...

Page 16: ...uction for the recommended airflow and Table 6 on page 17 The DELAY Tap should be set in the B position for a two stage condenser This results in a 45 second off delay at 82 of the programmed cooling...

Page 17: ...002UHC11 L8V1002UHC11 P DUC20V09601 G8V12020UHC11 L8V12020UHC11 COOL TAP ADJ TAP High Low High Low High Low High Low 1340 740 1675 920 2050 1135 2020 1130 A B 1155 635 1555 850 1860 980 1855 960 B B 1...

Page 18: ...is fixed at 60 seconds for SEER enhance ment HEATING OPERATIONAL SEQUENCE Two Stage Thermostat The ignition control in this furnace is unique to this product The control allows for a 24 volt or a 115...

Page 19: ...gas valve When power is restored the gas valve will remain deener gized and a restart of the ignition sequence will begin imme diately A momentary loss of gas supply flame blowout or a shorted or open...

Page 20: ...LOW INDUCER LOW STAGE PRESSURE SWITCH HSI 1ST STAGE MAIN VALVE FLAME SENSE LOW CIRCULATOR HEAT SPEED 1ST STAGE LOW PRESSURE SWITCH CLOSE RECOGNITION HSI WARM UP 17 SEC IGNITION ACTIVATION PERIOD 4 SE...

Page 21: ...bly for cleaning is as follows 1 Disconnect the power supplied to the furnace 2 Remove the vest and blower panels 3 Disconnect the motor control harness and the power har ness from the motor 4 Remove...

Page 22: ...including the flue baffle plate rear may be vacuumed or cleaned with hot water if necessary 6 The upper portion of the heat exchanger is now accessi ble With a long flexible wire brush clean inside ea...

Page 23: ...R REMOVAL FOR CONTROLLER REPLACEMENT Refer to BLOWER CARE on page 21 of this manual for blower removal instructions Rest the blower on its side so the end of the motor is accessible and facing up Wait...

Page 24: ...ehind a clear view port in the blower compartment door DO NOT remove the furnace blower compartment panel OR turn off furnace power as either action will clear the control s memory of the fault The co...

Page 25: ...y low gas pressure faulty gas valve faulty hot surface ignitor reversed line polarity or burner problem 8 FLASH This fault is indicated if the flame is lost 5 times during the heating cycle This could...

Page 26: ...NTROL BOARD P3 S3 2 PIN PLUG SOCKET AT HOT SURFACE IGNITOR P4 S4 3 PIN PLUG SOCKET AT INDUCER MOTOR P5 S5 3 PIN PLUG SOCKET ON VALVE P6 S6 6 PIN PLUG SOCKET ON CFM TIMER BOARD P7 S7 16 PIN PLUG SOCKET...

Page 27: ...035 17438 001 Rev A 901 Unitary Products Group 27 SERVICE RECORDS...

Page 28: ...hange without notice Printed in U S A 035 17438 001 Rev A 901 Copyright by York International Corp 2001 All rights reserved Supersedes 035 17438 001 Rev A 801 Unitary 5005 Norman Product York OK Group...

Reviews: