Unitary products group PS9 Installation Manual Download Page 26

035-20646-001 Rev. A (1004)

26

Unitary Products Group

For altitudes above 2,000 ft. (610 m) the furnace input MUST BE DER-
ATED. Refer to the GAS CONVERSION FOR PROPANE (LP) AND
HIGH ALTITUDES IN SECTION IV for information on high altitude con-
versions.

IMPORTANT: 

The inlet gas pressure operating range table specifies

what the minimum and maximum gas line pressures must be for the fur-
nace to operate safely. The gas line pressure 

MUST BE

7” W.C. (1.74 kPA) for Natural Gas

11” W.C. (2.74 kPA) for Propane (LP) Gas

in order to obtain the BTU input specified on the rating plate and/or the
nominal manifold pressure specified in these instructions and on the
rating plate.

ADJUSTMENT OF MANIFOLD GAS PRESSURE

Manifold gas pressure may be measured by two different procedures. It
may be measured with the burner box cover in place or it may be mea-
sured with the burner box cover removed. Follow the appropriate sec-
tion in the instructions below. Refer to Figure 38 for a drawing of the
locations of the pressure ports on the gas valve.

Turn gas off at the ball valve or gas cock on gas supply line 
before the gas valve. Find the pressure ports on the gas 
valve marked OUT P and IN P.

1.

The manifold pressure must be taken at the port marked OUT P. 

2.

The gas line pressure must be taken at the port marked IN P.

3.

Using a 3/32” (2.4 mm) Allen wrench, loosen the setscrew by turn-
ing it 1 turn counter clockwise. DO NOT REMOVE THE SET
SCREW FROM THE PRESSURE PORT.

Read the inlet gas pressure using either of the two meth-
ods below.

Reading the gas pressure with the burner box cover in place:

A.

Disconnect the pressure reference hose from the right side of
the burner box. Using a tee fitting and a short piece of hose,
connect the negative side of the manometer to the burner
box as described in below.

B.

Remove one end the 5/16” (0.8 cm) ID flexible tubing over
the pressure port on the burner box. 

C.

Insert the end of the 5/16” (0.8 cm) tubing, that has the 1/8”
(0.3 cm) adapter at the end of the tube, in to the 1/8” (0.3 cm)
tee.

D.

Connect the 1/8” (0.3 cm) tee to the burner box adapter and
to the negative side of a U-tube manometer or digital pres-
sure measuring equipment with 2 – 1/8” (0.3 cm) tubes.

E.

Use the 5/16” (0.8 cm x 1/8” (0.3 cm) reducing coupling and a
4” (10.2 cm) piece of 1/8” (0.3 cm) tubing to connect the posi-
tive side of the manometer to the gas valve pressure refer-
ence port. Refer to Figure 36 for connection details.

Reading the gas pressure with the burner box cover removed -

Remove the screws securing the burner box front cover plate. Remove
the cover. The gasket and may stick in place. Connect the positive side
of the manometer to the gas valve as described in E above. There will
be no second connection to the manometer, as it will reference atmo-
spheric pressure. Refer to Figure 36 for connection details.

IMPORTANT: 

The cap for the pressure regulator must be removed

entirely to gain access to the adjustment screw. Loosening or tightening
the cap does not adjust the flow of gas.  

1.

Refer to Figure 35 for location of pressure regulator adjustment
cap and adjustment screw on main gas valve.

2.

Turn gas and electrical supplies on and follow the operating
instructions to place the unit back in operation.

3.

Adjust manifold pressure by adjusting gas valve regulator screw
for the appropriate gas per the following:

IMPORTANT: 

If gas valve regulator is turned in (clockwise), manifold

pressure is increased. If screw is turned out (counterclockwise), mani-
fold pressure will decrease.

4.

After the manifold pressure has been adjusted, re-calculate the
furnace input to make sure you have not exceeded the specified
input on the rating plate. Refer to “CALCULATING THE FURNACE
INPUT (NATURAL GAS)”.

5.

Once the correct BTU (kW) input has been established, turn the
gas valve to OFF and turn the electrical supply switch to OFF; then
remove the flexible tubing and fittings from the gas valve pressure
tap and the pressure reference hose from the right side of the
burner box and tighten the pressure tap plug using the 3/32”
Allen wrench. Replace the burner box front cover (if it was
removed) and place the pressure reference hose back on the gas
valve.

6.

Turn the electrical and gas supplies back on, and with the burners
in operation, check for gas leakage around the gas valve pressure
port for leakage using an approved gas detector, a non-corrosive
leak detection fluid, or other leak detection methods.

Be sure to relight any gas appliances that were turned off at the
start of this input check.

TABLE 15: 

Inlet Gas Pressure Range

INLET GAS PRESSURE RANGE

Natural Gas

Propane (LP)

Minimum

4.5” W.C. (1.12 kPa)

8.0” W.C. (1.99 kPa)

Maximum

10.5” W.C. (2.61 kPa)

13.0” (3.24 kPa) W.C.

TABLE 16: 

Nominal Manifold Pressure

NOMINAL MANIFOLD PRESSURE

Natural Gas

3.5" w.c. (0.87 kPa)

Propane (LP) Gas

10.0" w.c. (2.488 kPa)

 FIGURE 36:  

Gas Valve

The manifold pressure must be checked with the screw-off cap for
the gas valve pressure regulator in place. If not, the manifold pres-
sure setting could result in an over-fire condition. A high manifold
pressure will cause an over-fire condition, which could cause pre-
mature heat exchanger failure. If the manifold pressure is too low,
sooting and eventual clogging of the heat exchanger could occur.
Be sure that gas valve regulator cap is in place and burner box to
gas valve pressure reference hose is connected.

INLET

WRENCH
BOSS

INLET
PRESSURE
PORT

ON

OFF

ON/OFF SWITCH
(Shown in ON position)

MAIN REGULATOR
ADJUSTMENT

OUTLET

OUTLET
PRESSURE
PORT

VENT PORT

Summary of Contents for PS9

Page 1: ...n Kit Assembly 5 Dimensions 6 Accessory Downflow Filter Rack 7 Return Filter Grill and Return Duct Installation 7 Typical Attic Installation 8 Typical Suspended Furnace Crawl Space Installation 8 Gas...

Page 2: ...ational vehicles Failure to carefully read and follow all instructions in this manual can result in furnace malfunction death personal injury and or property damage Furnaces for installation on combus...

Page 3: ...nd repairs are performed Clearances for access Ample clearances should be provided to permit easy access to the unit The following minimum clearances are recommended 1 Twenty four 24 inches 61 cm betw...

Page 4: ...proper fur nace operation Use the Example below to help you in calculating the duct area to deter mine whether the ducts have sufficient area so that the furnace oper ates at the specified external s...

Page 5: ...T The furnace transition kit and the cooling coil cabinet MUST BE SEALED as needed to prevent leaks AND SECURED Refer to the assembly drawing in Figures 2 IMPORTANT On all installations without a coil...

Page 6: ...recommended on all installations The connection of the plenum to the furnace and all the ducts connecting to the plenum must be sealed to prevent air leakage The sheet metal should be crosshatched to...

Page 7: ...allation 1 Install the return filter rack on the top of the furnace return air opening Secure the filter rack to the front and back flanges with screws The return air plenum can be placed over the fil...

Page 8: ...RAMING FILTER RACK MUST BE A MINIMUM DISTANCE OF 18 45 7 cm FROM THE FURANCE COMBUSTION AIR GAS PIPING VENT PIPE maintain required clearances to combustible RETURN AIR SUPPLY AIR 12 CLEARANCE FOR SERV...

Page 9: ...ere the altitude is greater than 2 000 ft 610 m above sea level on natural gas or the altitude is greater than 4 000 ft 1219 m above sea level on propane LP gas Refer to Table 7 or the instructions in...

Page 10: ...ion leads and wiring box may be relo cated to the left side of the furnace Remove the screws and cut wire tie holding excess wiring Reposition on the left side of the furnace and fas ten using holes p...

Page 11: ...an what one furnace can deliver twinning can be used to make two furnaces operate in tandem When two furnaces are installed using the same duct system it is very important that the two furnace cir cul...

Page 12: ...Cooling On a call for cooling Y signal from the wall thermostat both furnace blowers will come on at the same time in cooling speed When the thermostat is satisfied both blowers will stay on for 60 se...

Page 13: ...5 elbows in the combustion air piping and a maximum of 5 elbows in the vent piping 4 Three vent terminal elbows two for vent pipe and one for air intake pipe are already accounted for as vent terminat...

Page 14: ...cement must conform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent airtight and watertight seal 8 Support the combustion air and vent piping such that it is a...

Page 15: ...ion2 A Clearance above grade veranda porch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearance to window or door that may be opened 6 inches 15 cm for applications 10 000 Btuh 3kW 12 inches 30...

Page 16: ...eet elbow on the vent connec tion 2 Place the 2 5 08 cm PVC WYE Y assembly on the 2 5 08 cm 45 PVC street elbow 3 Locate the rubber condensate hose in front of the blower access panel 4 Slide the hose...

Page 17: ...TION AIR This is a sealed combustion air configuration where the combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated...

Page 18: ...ea of a specific louver or grille is not known refer to Table 10 to estimate free area Do not use less than 1 4 0 635 cm mesh Free area or louvers and grilles varies widely the installer should follow...

Page 19: ...materials in the SEALED COM BUSTION AIR SUPPLY section in these instructions when installing the combustion air pipe from the unit and into a ventilated attic space or crawl space DO NOT terminate ven...

Page 20: ...w the heat tape manufacturer s recommendations CONDENSATE DRAIN HOSE PART NUMBERS DOWNFLOW HORIZONTAL CONDENSATE INTERNAL DRAIN CONFIGURATIONS Downflow Furnace is shipped with one end of condensate ho...

Page 21: ...all hose 6 between the top drain of the rain gutter of the inducer and the remaining open end of 3 8 barbed tee 13 Ensure that all hoses are properly installed have no kinks and are draining properly...

Page 22: ...er smaller dogleg end of hose 10 should be installed into the large recessed drain in the condensate trap 7 Install the condensate trap bracket with the condensate trap on to the front side of the fur...

Page 23: ...n air blower heat exchanger or a blocked vent pipe connection Corrective action is required These are manual reset controls that must be reset before operation can continue PRESSURE SWITCHES This furn...

Page 24: ...will start and come up to speed Shortly after inducer start up the hot surface igniter will glow for about 17 seconds b After this warm up the ignition module will energize open the main gas valve c...

Page 25: ...ivided by the time it took to measure 2 cubic ft 0 0566 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 14 times 0 00283 m3 of gas measured at...

Page 26: ...gas valve as described in E above There will be no second connection to the manometer as it will reference atmo spheric pressure Refer to Figure 36 for connection details IMPORTANT The cap for the pre...

Page 27: ...by positioning the jumper on two of the four positions as shown in Figure 38 The furnace control board also allows user selection of the blower speed that is energized during continuous fan operation...

Page 28: ...4 1554 44 1532 43 1502 43 1457 41 1409 40 1327 38 1221 35 Medium Low 1256 36 1275 36 1275 36 1288 36 1275 36 1265 36 1232 35 1187 34 1126 32 1023 29 Low 937 27 939 27 936 26 945 27 942 27 936 26 912 2...

Page 29: ...peed blower it is found that total system static is 0 58 w c To determine the system airflow complete the following steps 1 Obtain the airflow values at 0 50 0 60 ESP Airflow 0 50 2125 CFM Airflow 0 6...

Page 30: ...035 20646 001 Rev A 1004 30 Unitary Products Group SECTION XII WIRING DIAGRAM FIGURE 39 Wiring Diagram...

Page 31: ...035 20646 001 Rev A 1004 Unitary Products Group 31 NOTES...

Page 32: ...to change without notice Printed in U S A 035 20646 001 Rev A 1004 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7306...

Reviews: