Unitary products group GY8S*UH Installation Manual Download Page 6

166753-UIM-C-0706

6

Unitary Products Group

RESIDENTIAL AND NON HUD MODULAR HOME 

RESIDENTIAL AND NON HUD MODULAR HOME 

RESIDENTIAL AND NON HUD MODULAR HOME 

RESIDENTIAL AND NON HUD MODULAR HOME 
UPFLOW RETURN PLENUM CONNECTION

UPFLOW RETURN PLENUM CONNECTION

UPFLOW RETURN PLENUM CONNECTION

UPFLOW RETURN PLENUM CONNECTION

Return air may enter the furnace through the side(s) or bottom depend-
ing on the type of application. Return air may not be connected into the
rear panel of the unit. In order to achieve the airflow indicated, it is rec-
ommended  those  applications  over  1800  CFM  (57  m³/min)  use  return
air from two sides, one side and the bottom or bottom only. For single
return  application,  see  data  and  notes  on  blower  performance  data
tables in this manual.

BOTTOM RETURN AND ATTIC INSTALLATIONS

BOTTOM RETURN AND ATTIC INSTALLATIONS

BOTTOM RETURN AND ATTIC INSTALLATIONS

BOTTOM RETURN AND ATTIC INSTALLATIONS

Bottom return applications normally pull return air through a base plat-
form or return air plenum. Be sure the return platform structure or return
air plenum is suitable to support the weight of the furnace.
The  furnace  base  is  equipped  with  a  rectangular  panel  that  can  be
removed by performing the following steps:

1.

Lay the furnace on its back.

2.

Remove the screws from the toe plate.

3.

Remove the toe plate.

4.

Pull the base plate out of the furnace base.

5.

Reinstall  the  toe  plate  and  secure  with  the  screws  that  were
removed.

Attic  installations  must  meet  all  minimum  clearances  to  combustibles
and have floor support with required service accessibility.

IMPORTANT: 

If  an  external  mounted  filter  rack  is  being  used  see  the

instructions provided with that accessory for proper hole cut size.

HORIZONTAL

HORIZONTAL

HORIZONTAL

HORIZONTAL MODELS

 MODELS

 MODELS

 MODELS

Horizontal Installations With a Cooling Coil Cabinet

The  furnace  should  be  installed  with  coil  cabinet  part  number  specifi-
cally  intended  for  Horizontal  application.  If  a  matching  cooling  coil  is
used, it may be placed directly on the furnace outlet and sealed to pre-
vent  leakage.  Follow  the  coil  instructions  for  installing  the  supply  ple-
num.  For  details  of  the  coil  cabinet  dimensions  and  installation
requirements, refer to the installation instructions supplied with the coil
cabinet 
Attach the supply plenum to the air conditioning coil cabinet outlet duct
flanges  through  the  use  of  S  cleat  material  when  a  metal  plenum  is
used. The use of an approved flexible duct connector is recommended
on all installations. The connection to the furnace, air conditioning coil
cabinet and the supply plenum should be sealed to prevent air leakage.
The  sheet  metal  should  be  crosshatched  to  eliminate  any  popping  of
the sheet metal when the indoor fan is energized.
The minimum plenum height is 12” (30.5 cm). If the plenum is shorter
than 12” (30.5 cm) the turbulent air flow may cause the limit controls not
to operate as designed, or the limit controls may not operate at all. Also
the plastic drain pan in the air conditioning coil can overheat and melt.
Refer  to  the  installation  instructions  supplied  with  the  air  conditioning
coil for additional information.

Horizontal Installations Without a Cooling Coil Cabinet

When  installing  this  appliance,  the  furnace  must  be  installed  so  as  to
create  a  closed  duct  system,  the  supply  duct  system  must  be  con-
nected to the furnace outlet and the supply duct system must terminate
outside  the  space  containing  the  furnace.  When  replacing  an  existing
furnace, if the existing plenum is not the same size as the new furnace
then the existing plenum must be removed and a new plenum installed
that is the proper size for the new furnace.
Attach the supply plenum to the furnace outlet duct flanges through the
use  of  S  cleat  material  when  a  metal  plenum  is  used.  The  use  of  an
approved  flexible  duct  connector  is  recommended  on  all  installations.
This  connection  should  be  sealed  to  prevent  air  leakage.  The  sheet
metal  should  be  crosshatched  to  eliminate  any  popping  of  the  sheet
metal  when  the  indoor  fan  is  energized.  On  all  installations  without  a
coil, a removable access panel is recommended in the outlet duct such
that smoke  or reflected light  would be observable inside  the  casing to
indicate the presence of leaks in the heat exchanger. This access cover
shall be attached in such a manner as to prevent leaks.

Residential and Non Hud Modular Home Horizontal Return 
Plenum Connections

The return duct system must be connected to the furnace inlet and the
return duct system must terminate outside the space containing the fur-
nace. When replacing an existing furnace, if the existing plenum is not
the  same  size  as  the  new  furnace  then  the  existing  plenum  must  be
removed and a new plenum installed that is the proper size for the new
furnace.
Attach the return plenum to the furnace inlet duct flanges. This is typi-
cally through the use of S cleat material when a metal plenum is used.
The use of an approved flexible duct connector is recommended on all
installations.  The  connection  of  the  plenum  to  the  furnace  and  all  the
ducts connecting to the plenum must be sealed to prevent air leakage.
The  sheet  metal  should  be  crosshatched  to  eliminate  any  popping  of
the sheet metal when the indoor fan is energized.
The duct system is a very important part of the installation. If the duct
system  is  improperly  sized  the  furnace  will  not  operate  properly.  The
ducts attached to the furnace must be of sufficient size so that the fur-
nace operates at the specified external static pressure and within the air
temperature rise specified on the nameplate.
Attic  installations  must  meet  all  minimum  clearances  to  combustibles
and have floor support with required service accessibility.

IMPORTANT: 

if  an  external  mounted  filter  rack  is  being  used  see  the

instructions provided with that accessory for proper hole cut size.

ATTIC INSTALLATION

ATTIC INSTALLATION

ATTIC INSTALLATION

ATTIC INSTALLATION

 FIGURE 2:  

Typical Attic Installation

RETURN AIR

SEDIMENT

TRAP

GAS PIPING

SUPPLY AIR

VENT (Maintain
required clearances
to combustibles)

SHEET METAL
IN FRONT OF
FURNACE
COMBUSTION AIR
OPENINGS IS
RECOMMENDED

LINE CONTACT ONLY PERMISSIBLE
BETWEEN LINES FORMED BY THE
INTERSECTION OF FURNACE TOP
AND TWO SIDES AND BUILDING
JOISTS, STUDS OR FRAMING

12”

30” MIN.
WORK AREA

FILTER RACK
MUST BE A MINIMUM
DISTANCE
OF 18” (45.7 cm)
FROM THE
FURNACE

Summary of Contents for GY8S*UH

Page 1: ...PIPING 8 ELECTRICAL POWER 9 TWINNING AND STAGING 12 VENT SYSTEM 14 SAFETY CONTROLS 19 START UP AND ADJUSTMENTS 20 WIRING DIAGRAM SAFETY 1 LIST OF FIGURES Dimensions 5 Typical Attic Installation 6 Typical Suspended Furnace Crawl Space Installation 7 Side Return Cutout Markings 7 Gas Valve All Except GR Models 8 Gas Valve GR Models Only 8 Upflow Gas Piping 8 Horizontal Gas Piping 8 Electrical Wiring...

Page 2: ...y to be sure that the elec trical characteristics match All models use nominal 115 VAC 1 Phase 60 Hertz power supply DO NOT CONNECT THIS APPLI ANCE TO A 50 HZ POWER SUPPLY OR A VOLTAGE ABOVE 130 VOLTS Furnace shall be installed so the electrical components are pro tected from water Installing and servicing heating equipment can be hazardous due to the electrical components and the gas fired compon...

Page 3: ...clearances shall take precedence over clear ances for combustible materials where accessibility clearances are greater Installation in a residential garage A gas fired furnace for installation in a residential garage must be installed so the burner s and the ignition source are located not less than 18 inches 46 cm above the floor and the furnace must be located or protected to avoid physical dama...

Page 4: ...by subtracting the Return Air Temperature Reading from the Supply Air Temperature Read ing 2 The External Static Pressure is determined by adding the Supply Duct Static Pressure reading to the Return Duct Static Pressure reading adding the pressure across any applied a coil and the drop across the return air filter TABLES 2 3 are to be used as a guide only to help the installer deter mine if the d...

Page 5: ...gas orifice and or a faulty limit switch can cause the furnace to operate above the maximum supply air temperature Refer to sections II III and IX for additional informa tion on correcting the problem FIGURE 1 Dimensions FRONT LEFT SIDE RIGHT SIDE B 20 40 A 28 1 2 3 4 14 3 4 5 3 8 VENT CONNECTIONS POWER WIRING 7 8 HOLE 2 1 2 ACCESS WIRING 7 8 K O 16 8 3 4 T STAT WIRING 7 8 K O 1 1 8 2 1 4 14 23 1 ...

Page 6: ...d with the air conditioning coil for additional information Horizontal Installations Without a Cooling Coil Cabinet When installing this appliance the furnace must be installed so as to create a closed duct system the supply duct system must be con nected to the furnace outlet and the supply duct system must terminate outside the space containing the furnace When replacing an existing furnace if t...

Page 7: ...ilter rack following the instructions provided with that accessory If a filter s is provided at another location in the return air system the ductwork may be directly attached to the furnace side panel An accessory filter rack is available for mounting the filter exter nal to the cabinet IMPORTANT Some accessories such as electronic air cleaners and pleated media may require a larger side opening ...

Page 8: ...e factory for natural gas fired operation at 0 8 000 feet 0 m 2 438 m above sea level The manifold pressure must be changed in order to manitain proper and safe operation when the furnace is installed in a location where the altitude is greater than 8 000 feet 2 438 m above sea level Refer to to Table 6 for proper manifold pressure settings HIGH ALTITUDE PRESSURE SWITCH CONVERSION HIGH ALTITUDE PR...

Page 9: ...cy using factory specified and or approved parts must perform the conversion The installer must take every precaution to insure that the furnace has been converted to the proper gas orifice size when the furnace is installed Do not attempt to drill out any orifices to obtain the proper orifice size Drilling out a gas orifice will cause misalignment of the burner flames causing premature heat excha...

Page 10: ...d cut wire tie holding excess wiring Reposition on the left side of the furnace and fas ten using holes provided LOW VOLTAGE CONTROL WIRING CONNECTIONS LOW VOLTAGE CONTROL WIRING CONNECTIONS LOW VOLTAGE CONTROL WIRING CONNECTIONS LOW VOLTAGE CONTROL WIRING CONNECTIONS Install the field supplied thermostat by following the instructions that come with the thermostat With the thermostat set in the OF...

Page 11: ...mmon C 24 Volt Common Optional w Batteries BN11C01124 DP11C40124 PSC FURNACE CONTROL SINGLE STAGE AIR CONDITIONING BN11C00124 BP11C50124 PP11C70224 THERMOSTAT THERMOSTAT THERMOSTAT HP1 W 031 01975 Series Demand Control Single Stage H P E RD E BD ERHS HPX13 w Single Stage Furnace 1 Stage Cooling Ready G L 8 9S XYF80 U XYF80 U L XYF90 U SINGLE STAGE HEAT PUMP DN22U00124 BP21H50124 PP32H70124 THERMOS...

Page 12: ... s Separate plenums and supply ducts systems cannot be utilized A sin gle return air plenum common to both furnaces must be used It is sug gested that a return platform be utilized with bottom air entrance into each furnace If a side entrance return system is used the common return duct must be divided equally so as to supply each furnace with an equal amount of return air Both furnaces must be id...

Page 13: ...a single two stage furnace This allows only one furnace to supply heat during times when the heat output from one furnace is sufficient to satisfy the demand When one duct system is used for two furnaces it is necessary that the two blowers operate in unison The twinning func tion of this board ensures that both blowers turn on and off simulta neously and operate on the same blower speed Even when...

Page 14: ...res the maximum allowable vent pipe length the furnace must be converted for high altitude operation Refer to SECTION IV GAS PIP ING of these instructions and the proper high altitude application instruction for details VENTING INTO AN EXISTING CHIMNEY VENTING INTO AN EXISTING CHIMNEY VENTING INTO AN EXISTING CHIMNEY VENTING INTO AN EXISTING CHIMNEY For Category I installations the furnace shall b...

Page 15: ... to the proper length beginning at the furnace 2 Deburr the piping inside and outside 3 Dry fit the vent piping assembly from the furnace to the termination checking for proper fit support and slope Piping should be sup ported with pipe hangers to prevent sagging The maximum spac ing between hangers is 5 feet 1 5 m 4 Assemble the vent piping from the furnace to the termination securing the pipe co...

Page 16: ...tionable 6 Horizontal portions of the vent system must slope upwards and be supported to prevent sagging The vent system may be supported by the use of clamps or hangers secured to a permanent part of the structure every 4 ft 1 22 m FAN ASSISTED COMBUSTION SYSTEM FAN ASSISTED COMBUSTION SYSTEM FAN ASSISTED COMBUSTION SYSTEM FAN ASSISTED COMBUSTION SYSTEM An appliance equipped with an integral mech...

Page 17: ...ed for use 4 A automatically operated damper or automatically adjustable lou vers shall be interlocked so that the main burner cannot operate unless either the damper or the louver is in the fully open position FIGURE 20 Combustion Airflow Path Through The Furnace Casing to the Burner Box This type of installation requires that the supply air to the appli ance s be of a sufficient amount to suppor...

Page 18: ...rizontally from the burner level of the appliance Refer to AIR SOURCE FROM OUTDOORS AND VENT AND SUPPLY AIR SAFETY CHECK in these instructions for additional information and safety check procedure 2 The duct shall be either metal or a material meeting the class 1 requirements of CAN4 S110 Standard for Air Ducts 3 The duct shall be least the same cross sectional area as the free area of the air sup...

Page 19: ...ction Corrective action is required These are manual reset controls that must be reset before operation can continue PRESSURE SWITCHES PRESSURE SWITCHES PRESSURE SWITCHES PRESSURE SWITCHES This furnace is supplied with a pressure switch which monitors the flow through the combustion air vent piping system This switch de ener gizes the ignition control module and the gas valve if any of the follow ...

Page 20: ...ng 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 3 175 mm reducing coupling 1 1 8 0 3 cm adapter There is a accessory kit 1PK0602 available from Source 1 which has the following items 12 30 cm length x 1 8 0 3 cm diameter tubing 2 pieces of 4 10 cm length x 1 8 0 3 cm diameter tubing 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 0 3 cm reducing coupling 1 1 8 0 3 cm adapter 1 Dwyer Manometer These items are requi...

Page 21: ...ter times a barometric pressure and temperature correction factor of 0 960 times 3600 then divided by the time it took to measure 2 cubic ft 0 0566 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 14 times 0 00283 m3 of gas measured at the gas meter times a barometric pressure and temperature correction factor of 0 960 times 3600 then divided...

Page 22: ...gure 30 for connection details IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or tightening the cap does not adjust the flow of gas NOTE The regulated outlet pressures both low and high have been calibrated at the factory Additional pressure adjustment should not be necessary If adjustment is necessary set to the following spe...

Page 23: ...ssure regulator adjustment cap and adjustment screws on main gas valve 7 After the manifold pressure has been adjusted re calculate the furnace input to make sure you have not exceeded the specified input on the rating plate Refer to CALCULATING THE FURNACE INPUT NATURAL GAS 8 Once the correct BTU kW input has been established turn the gas valve to OFF and turn the electrical supply switch to OFF ...

Page 24: ...lter pressure drop values in Table 15 are typical values for the type of filter listed and should only be used as a guideline Actual pres sure drop ratings for each filter type vary between filter manufacturers MANIFOLD PRESSURE U TUBE CONNECTION FIGURE 29 Reading Gas Pressure The temperature rise or temperature difference between the return air and the supply heated air from the furnace must be w...

Page 25: ...c is 0 58 w c To determine the system airflow complete the following steps Obtain the airflow values at 0 50 w c 125 Pa 0 60 w c 150 Pa ESP Airflow 0 50 1250 CFM 35 4 m3 min Airflow 0 60 1180 CFM 33 4 m3 min Subtract the airflow 0 50 w c 125 Pa from the airflow 0 60 w c 150 Pa to obtain airflow difference 1180 1250 70 CFM 12 m3 min Subtract the total system static from 0 50 w c 125 Pa and divide t...

Page 26: ... 35 7 Medium Low 1720 1700 1670 1620 1570 1500 1430 1310 1160 1000 48 7 48 1 47 3 45 9 44 5 42 5 40 5 37 1 32 8 28 3 Low 1410 1390 1360 1330 1280 1220 1170 1060 930 840 39 9 39 4 38 5 37 7 36 2 34 5 33 1 30 0 26 3 23 8 100 1200 B High 1700 1620 1560 1480 1390 1300 1210 1110 970 820 48 1 45 9 44 2 41 9 39 4 36 8 34 3 31 4 27 5 23 2 Medium High 1430 1400 1350 1300 1230 1160 1080 980 870 710 40 5 39 ...

Page 27: ...2030 1980 1910 1850 1710 1570 1300 59 7 59 7 58 6 57 5 56 1 54 1 52 4 48 4 44 5 36 8 Medium Low 1690 1690 1650 1610 1540 1480 1410 1280 1170 1030 47 9 47 9 46 7 45 6 43 6 41 9 39 9 36 2 33 1 29 2 Low 1350 1330 1310 1290 1260 1220 1150 1050 970 860 38 2 37 7 37 1 36 5 35 7 34 5 32 6 29 7 27 5 24 4 100 1200 B High 1780 1710 1640 1560 1490 1390 1290 1180 1030 820 50 4 48 4 46 4 44 2 42 2 39 4 36 5 33...

Page 28: ...Copyright by York International Corp 2006 All rights reserved Supersedes 166753 UIM B 0306 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION X WIRING DIAGRAM SECTION X WIRING DIAGRAM SECTION X WIRING DIAGRAM SECTION X WIRING DIAGRAM FIGURE 31 Wiring Diagram ...

Reviews: