Unitary products group GM8S*UH Installation Manual Download Page 7

166753-UIM-C-0706

Unitary Products Group

7

This  appliance  is  design  certified  for  line  contact  when  the  furnace  is
installed  in  the  horizontal left  or  right position. The  line  contact  is  only
permissible between lines that are formed by the intersection of the top
and  two  sides of  the  furnace  and  the  building  joists,  studs  or  framing.
This line may be in contact with combustible material. Refer to Figure 3.

SUSPENDED FURNACE / CRAWL SPACE 

SUSPENDED FURNACE / CRAWL SPACE 

SUSPENDED FURNACE / CRAWL SPACE 

SUSPENDED FURNACE / CRAWL SPACE 
INSTALLATION

INSTALLATION

INSTALLATION

INSTALLATION

The furnace can be hung from floor joists or installed on suitable blocks
or  pad.  Blocks  or  pad  installations  shall  provide  adequate  height  to
ensure the unit will not be subject to water damage. Units may also be
suspended from rafters or floor joists using rods, pipe angle supports or
straps. Angle supports should be placed at the supply air end and near
the  blower deck. Do not support at return air  end of unit. All  four sus-
pension points must be level to ensure quite furnace operation. When
suspending the furnace use a secure platform constructed of plywood
or other  building  material secured  to  the floor joists. Refer to Figure  4
for typical crawl space installation.

SECTION III: FILTERS

SECTION III: FILTERS

SECTION III: FILTERS

SECTION III: FILTERS

FILTER INSTALLATION

FILTER INSTALLATION

FILTER INSTALLATION

FILTER INSTALLATION

All applications require the use of a field installed accessory filter. All fil-
ters and mounting provision must be field supplied. Refer to Tables 5 &
16 for accessory external filter kit options. 

NOTES: 

1. Air velocity through throwaway type filters may not exceed 300 feet per minute (91.4 m/min). All velocities over this require the use of high velocity filters.
2. Air flows above 1800 CFM require either return from two sides or one side plus bottom.

SIDE RETURN - EXTERNAL INSTALLATION

SIDE RETURN - EXTERNAL INSTALLATION

SIDE RETURN - EXTERNAL INSTALLATION

SIDE RETURN - EXTERNAL INSTALLATION

Locate  and  knock  out  the  square  corner  locators.  These  indicate  the
size of the cutout to be made in the furnace side panel. Refer to Figure 5.

Install  the  side  filter  rack  following  the  instructions  provided  with  that
accessory.  If  a  filter(s)  is  provided  at  another  location  in  the  return  air
system,  the  ductwork  may  be  directly  attached  to  the  furnace  side
panel. An accessory filter rack is available for mounting the filter exter-
nal to the cabinet. 

IMPORTANT: 

Some  accessories  such  as  electronic  air  cleaners  and

pleated  media  may  require  a  larger  side  opening.  Follow  the  instruc-
tions  supplied  with  that  accessory  for  side  opening  requirements.  Do
not cut the opening larger than the dimensions shown in Figure 1.

HORIZONTAL APPLICATION

HORIZONTAL APPLICATION

HORIZONTAL APPLICATION

HORIZONTAL APPLICATION

Horizontal Filters

All filters and mounting provision must be field supplied. Filters(s) may
be located in the duct system external to the furnace or in a return filter
grille(s). Filters(s) may be located in the duct system using an external
duct filter box attached to the furnace plenum. Any branch duct (rectan-
gular or round duct) attached to the plenum must attach to the vertical
plenum  above  the  filter  height.  The  use  of  straps  and  /  or  supports  is
required to support the weight of the external filter box.

IMPORTANT: 

Air  velocity  through  throwaway  type  filters  must  not

exceed 300 feet per minute (1.52 m/m). All velocities over this require
the use of high velocity filters. Refer to Table 15.

When  a  furnace  is  installed  in  an  attic  or  other  insulated  space,
keep all insulating materials at least 12 inches (30.5 cm) away from
furnace and burner combustion air openings.

 FIGURE 3:  

Typical Suspended Furnace / Crawl Space Installation

In any application where temperatures below freezing are possible,
see “BELOW FREEZING LOCATIONS”.

1” MAX. BETWEEN
ROD & FURNACE

SUPPORT
ROD

6” MIN BETWEEN
ROD & FURNACE

1” MAX. BETWEEN
ROD & FURNACE

ANGLE IRON
BRACKET

TABLE 5: 

Filter Sizes

CFM

(m³/min)

Cabinet

Size

Side

(in)

Side

 (cm)

Bottom

(in)

Bottom

 (cm)

1200 (33.98)

A

16 x 25

40.6 x 63.5

14 x 25

35.6 x 63.5

1200 (33.98)

B

16 x 25

40.6 x 63.5

16 x 25

40.6 x 63.5

1600 (45.31)

B

16 x 25

40.6 x 63.5

16 x 25

40.6 x 63.5

1600 (45.31)

C

16 x 25

40.6 x 63.5

20 x 25

50.8 x 63.5

2000 (56.63)

C

(2) 16 x 25

(2) 40.6 x 63.5

20 x 25

50.8 x 63.5

2200 (62.30)

C

(2) 16 x 25

(2) 40.6 x 63.5

20 x 25

50.8 x 63.5

2000 (56.63)

D

(2) 16 x 25

(2) 40.6 x 63.5

22 x 25

55.9 x 63.5

 FIGURE 4:  

Side Return Cutout Markings

FRONT OF

FURNACE

CORNER

MARKINGS

All installations must have a filter installed.

Summary of Contents for GM8S*UH

Page 1: ...IPING 8 ELECTRICAL POWER 9 TWINNING AND STAGING 12 VENT SYSTEM 14 SAFETY CONTROLS 19 START UP AND ADJUSTMENTS 20 WIRING DIAGRAM SAFETY 1 LIST OF FIGURES Dimensions 5 Typical Attic Installation 6 Typic...

Page 2: ...to be sure that the elec trical characteristics match All models use nominal 115 VAC 1 Phase 60 Hertz power supply DO NOT CONNECT THIS APPLI ANCE TO A 50 HZ POWER SUPPLY OR A VOLTAGE ABOVE 130 VOLTS...

Page 3: ...earances shall take precedence over clear ances for combustible materials where accessibility clearances are greater Installation in a residential garage A gas fired furnace for installation in a resi...

Page 4: ...y subtracting the Return Air Temperature Reading from the Supply Air Temperature Read ing 2 The External Static Pressure is determined by adding the Supply Duct Static Pressure reading to the Return D...

Page 5: ...as orifice and or a faulty limit switch can cause the furnace to operate above the maximum supply air temperature Refer to sections II III and IX for additional informa tion on correcting the problem...

Page 6: ...with the air conditioning coil for additional information Horizontal Installations Without a Cooling Coil Cabinet When installing this appliance the furnace must be installed so as to create a closed...

Page 7: ...lter rack following the instructions provided with that accessory If a filter s is provided at another location in the return air system the ductwork may be directly attached to the furnace side panel...

Page 8: ...factory for natural gas fired operation at 0 8 000 feet 0 m 2 438 m above sea level The manifold pressure must be changed in order to manitain proper and safe operation when the furnace is installed...

Page 9: ...y using factory specified and or approved parts must perform the conversion The installer must take every precaution to insure that the furnace has been converted to the proper gas orifice size when t...

Page 10: ...cut wire tie holding excess wiring Reposition on the left side of the furnace and fas ten using holes provided LOW VOLTAGE CONTROL WIRING CONNECTIONS LOW VOLTAGE CONTROL WIRING CONNECTIONS LOW VOLTAG...

Page 11: ...mon C 24 Volt Common Optional w Batteries BN11C01124 DP11C40124 PSC FURNACE CONTROL SINGLE STAGE AIR CONDITIONING BN11C00124 BP11C50124 PP11C70224 THERMOSTAT THERMOSTAT THERMOSTAT HP1 W 031 01975 Seri...

Page 12: ...s Separate plenums and supply ducts systems cannot be utilized A sin gle return air plenum common to both furnaces must be used It is sug gested that a return platform be utilized with bottom air entr...

Page 13: ...single two stage furnace This allows only one furnace to supply heat during times when the heat output from one furnace is sufficient to satisfy the demand When one duct system is used for two furnac...

Page 14: ...es the maximum allowable vent pipe length the furnace must be converted for high altitude operation Refer to SECTION IV GAS PIP ING of these instructions and the proper high altitude application instr...

Page 15: ...to the proper length beginning at the furnace 2 Deburr the piping inside and outside 3 Dry fit the vent piping assembly from the furnace to the termination checking for proper fit support and slope Pi...

Page 16: ...ionable 6 Horizontal portions of the vent system must slope upwards and be supported to prevent sagging The vent system may be supported by the use of clamps or hangers secured to a permanent part of...

Page 17: ...d for use 4 A automatically operated damper or automatically adjustable lou vers shall be interlocked so that the main burner cannot operate unless either the damper or the louver is in the fully open...

Page 18: ...izontally from the burner level of the appliance Refer to AIR SOURCE FROM OUTDOORS AND VENT AND SUPPLY AIR SAFETY CHECK in these instructions for additional information and safety check procedure 2 Th...

Page 19: ...tion Corrective action is required These are manual reset controls that must be reset before operation can continue PRESSURE SWITCHES PRESSURE SWITCHES PRESSURE SWITCHES PRESSURE SWITCHES This furnace...

Page 20: ...g 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 3 175 mm reducing coupling 1 1 8 0 3 cm adapter There is a accessory kit 1PK0602 available from Source 1 which has the following items 12 30 cm length x 1 8 0 3...

Page 21: ...er times a barometric pressure and temperature correction factor of 0 960 times 3600 then divided by the time it took to measure 2 cubic ft 0 0566 m3 of gas from the gas meter For Propane LP Gas multi...

Page 22: ...ure 30 for connection details IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or tightening the cap does not adjust the flow of g...

Page 23: ...sure regulator adjustment cap and adjustment screws on main gas valve 7 After the manifold pressure has been adjusted re calculate the furnace input to make sure you have not exceeded the specified in...

Page 24: ...ter pressure drop values in Table 15 are typical values for the type of filter listed and should only be used as a guideline Actual pres sure drop ratings for each filter type vary between filter manu...

Page 25: ...is 0 58 w c To determine the system airflow complete the following steps Obtain the airflow values at 0 50 w c 125 Pa 0 60 w c 150 Pa ESP Airflow 0 50 1250 CFM 35 4 m3 min Airflow 0 60 1180 CFM 33 4...

Page 26: ...35 7 Medium Low 1720 1700 1670 1620 1570 1500 1430 1310 1160 1000 48 7 48 1 47 3 45 9 44 5 42 5 40 5 37 1 32 8 28 3 Low 1410 1390 1360 1330 1280 1220 1170 1060 930 840 39 9 39 4 38 5 37 7 36 2 34 5 33...

Page 27: ...030 1980 1910 1850 1710 1570 1300 59 7 59 7 58 6 57 5 56 1 54 1 52 4 48 4 44 5 36 8 Medium Low 1690 1690 1650 1610 1540 1480 1410 1280 1170 1030 47 9 47 9 46 7 45 6 43 6 41 9 39 9 36 2 33 1 29 2 Low 1...

Page 28: ...opyright by York International Corp 2006 All rights reserved Supersedes 166753 UIM B 0306 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION X WIRING DIAGRAM SECTION X WIRING DIAGRAM SECTIO...

Reviews: