background image

166753-UIM-C-0706

24

Unitary Products Group

ADJUSTMENT OF TEMPERATURE RISE

ADJUSTMENT OF TEMPERATURE RISE

ADJUSTMENT OF TEMPERATURE RISE

ADJUSTMENT OF TEMPERATURE RISE

The temperature rise, or temperature difference between the return air
and  the  heated  supply  air  from  the  furnace,  must  be  within  the  range
shown on the furnace rating plate and within the application limitations
as shown in Table 7.

After about 20 minutes of operation, determine the furnace temperature
rise. Take readings of both the return air and the heated air in the ducts,
about six feet (1.83 m) from the furnace where they will not be affected
by radiant heat. Increase the blower speed to decrease the temperature
rise; decrease the blower speed to increase the rise.

All  direct-drive  blowers  have  multi-speed  motors.  The  blower  motor
speed  taps  are  located  in  the  control  box  in  the  blower  compartment.
Refer  to  Figure  31,  and  the  unit-wiring  label  to  change  the  blower
speed. To use the same speed tap for heating and cooling, the heat ter-
minal  and  cool  terminal  must  be  connected  using  a  jumper  wire  and
connected to the desired motor lead. Place all unused motor leads on
Park terminals. Two are provided.

ADJUSTMENT OF FAN CONTROL SETTINGS

ADJUSTMENT OF FAN CONTROL SETTINGS

ADJUSTMENT OF FAN CONTROL SETTINGS

ADJUSTMENT OF FAN CONTROL SETTINGS

This furnace is equipped with a time-on/time-off heating fan control. The
fan on delay is fixed at 30 seconds. The fan off delay has 4 settings (60,
90, 120 and 180 seconds). The fan off delay is factory set to 120 sec-
onds.  The  fan-off  setting  must  be  long  enough  to  adequately  cool  the
furnace, but not so long that cold air is blown into the heated space. The
fan-off timing may be adjusted by positioning the jumper on two of the
four pins as shown in Figure 31.

FILTER PERFORMANCE

FILTER PERFORMANCE

FILTER PERFORMANCE

FILTER PERFORMANCE

The airflow capacity data published in Tables 17 & 18 represents blower
performance  WITHOUT  filters.  To  determine  the  approximate  blower
performance of the system, apply the filter drop value for the filter being
used or select an appropriate value from the Table 15.
The  filter  pressure  drop  values  in  Table  15  are  typical  values  for  the
type of filter listed and should only be used as a guideline. Actual pres-
sure drop ratings for each filter type vary between filter manufacturers.

MANIFOLD PRESSURE “U” TUBE CONNECTION

 FIGURE 29:  

Reading Gas Pressure

The temperature rise, or temperature difference between the return
air and the supply (heated) air from the furnace, must be within the
range shown on the furnace rating plate and within the application
limitations shown in Table 7 “RATINGS & PHYICAL / ELECTRICAL
DATA”.
The supply air temperature cannot exceed the 

“Maximum Supply

Air  Temperature”

  specified  in  these  instructions  and  on  the  fur-

nace  rating  plate.  Under  NO  circumstances  can  the  furnace  be
allowed  to  operate  above  the  Maximum  Supply  Air  Temperature.
Operating the furnace above the Maximum Supply Air Temperature
will cause premature heat exchanger failure, high levels of Carbon
Monoxide,  a  fire  hazard,  personal  injury,  property  damage,  and/or
death.

U-TUBE

MANOMETER

3.5 IN

WATER

COLUMN

GAS

PRESSURE

SHOWN

GAS

BURNERS

OUTLET

PRESSURE TAP

GAS VALVE

FLAME

SENSOR

1/4” TUBING

MAINIFOLD

PIPE

Do not energize more than one motor speed at a time or damage to
the motor will result.

 FIGURE 30:  

Typical Heat/Cool Speed Tap Connections

P

ARK

P

ARK

HI

COOL

HEA

T

EAC

L1

XFMR

HUM

NEUTRALS

RED - LOW SPEED

YELLOW - MED. LOW SPEED

BLACK - HIGH SPEED

BLUE -MED. HIGH SPEED

FAN OFF

ADJUSTMENT

JUMPER

Y/Y2

W

R

G

C

TABLE 15: 

Filter Performance - Pressure Drop Inches W.C. and (kPa)

Airflow Range

Minimum Opening Size

Filter Type

Disposable

Washable Fiber

Pleated

1 Opening

2 Openings

1 Opening

2 Openings

1 Opening

2 Openings

1 Opening

2 Openings

CFM

Cm/m

In³

In³

inwc

kPa

inwc

kPa

inwc

kPa

inwc

kPa

inwc

kPa

inwc

kPa

0 - 750

0 - 21.24

230 0.0038

0.01 0.0025

0.01 0.0025

0.15 0.0374

751 - 1000

21.27 - 28.32

330 0.0054

0.05 0.0125

0.05 0.0125

0.2

0.0498

1001 - 1250

28.35 - 35.40

330 0.0054

0.1

0.0249

0.1

0.0249

0.2

0.0498

1251 - 1500

35.42 - 42.47

330 0.0054

0.1

0.0249

0.1

0.0249

0.25 0.0623

1501 - 1750

42.50 - 49.55

380 0.0062 658 0.0108 0.15 0.0374 0.09 0.0224 0.14 0.0349 0.08 0.0199

0.3

0.0747 0.17 0.0423

1751 - 2000

49.58 - 56.63

380 0.0062 658 0.0108 0.19 0.0473 0.11 0.0274 0.18 0.0448

0.1

0.0249

0.3

0.0747 0.17 0.0423

2001 & Above 56.66 & Above 463 0.0076 658 0.0108 0.19 0.0473 0.11 0.0274 0.18 0.0448

0.1

0.0249

0.3

0.0747 0.17 0.0423

Summary of Contents for GM8S*UH

Page 1: ...IPING 8 ELECTRICAL POWER 9 TWINNING AND STAGING 12 VENT SYSTEM 14 SAFETY CONTROLS 19 START UP AND ADJUSTMENTS 20 WIRING DIAGRAM SAFETY 1 LIST OF FIGURES Dimensions 5 Typical Attic Installation 6 Typic...

Page 2: ...to be sure that the elec trical characteristics match All models use nominal 115 VAC 1 Phase 60 Hertz power supply DO NOT CONNECT THIS APPLI ANCE TO A 50 HZ POWER SUPPLY OR A VOLTAGE ABOVE 130 VOLTS...

Page 3: ...earances shall take precedence over clear ances for combustible materials where accessibility clearances are greater Installation in a residential garage A gas fired furnace for installation in a resi...

Page 4: ...y subtracting the Return Air Temperature Reading from the Supply Air Temperature Read ing 2 The External Static Pressure is determined by adding the Supply Duct Static Pressure reading to the Return D...

Page 5: ...as orifice and or a faulty limit switch can cause the furnace to operate above the maximum supply air temperature Refer to sections II III and IX for additional informa tion on correcting the problem...

Page 6: ...with the air conditioning coil for additional information Horizontal Installations Without a Cooling Coil Cabinet When installing this appliance the furnace must be installed so as to create a closed...

Page 7: ...lter rack following the instructions provided with that accessory If a filter s is provided at another location in the return air system the ductwork may be directly attached to the furnace side panel...

Page 8: ...factory for natural gas fired operation at 0 8 000 feet 0 m 2 438 m above sea level The manifold pressure must be changed in order to manitain proper and safe operation when the furnace is installed...

Page 9: ...y using factory specified and or approved parts must perform the conversion The installer must take every precaution to insure that the furnace has been converted to the proper gas orifice size when t...

Page 10: ...cut wire tie holding excess wiring Reposition on the left side of the furnace and fas ten using holes provided LOW VOLTAGE CONTROL WIRING CONNECTIONS LOW VOLTAGE CONTROL WIRING CONNECTIONS LOW VOLTAG...

Page 11: ...mon C 24 Volt Common Optional w Batteries BN11C01124 DP11C40124 PSC FURNACE CONTROL SINGLE STAGE AIR CONDITIONING BN11C00124 BP11C50124 PP11C70224 THERMOSTAT THERMOSTAT THERMOSTAT HP1 W 031 01975 Seri...

Page 12: ...s Separate plenums and supply ducts systems cannot be utilized A sin gle return air plenum common to both furnaces must be used It is sug gested that a return platform be utilized with bottom air entr...

Page 13: ...single two stage furnace This allows only one furnace to supply heat during times when the heat output from one furnace is sufficient to satisfy the demand When one duct system is used for two furnac...

Page 14: ...es the maximum allowable vent pipe length the furnace must be converted for high altitude operation Refer to SECTION IV GAS PIP ING of these instructions and the proper high altitude application instr...

Page 15: ...to the proper length beginning at the furnace 2 Deburr the piping inside and outside 3 Dry fit the vent piping assembly from the furnace to the termination checking for proper fit support and slope Pi...

Page 16: ...ionable 6 Horizontal portions of the vent system must slope upwards and be supported to prevent sagging The vent system may be supported by the use of clamps or hangers secured to a permanent part of...

Page 17: ...d for use 4 A automatically operated damper or automatically adjustable lou vers shall be interlocked so that the main burner cannot operate unless either the damper or the louver is in the fully open...

Page 18: ...izontally from the burner level of the appliance Refer to AIR SOURCE FROM OUTDOORS AND VENT AND SUPPLY AIR SAFETY CHECK in these instructions for additional information and safety check procedure 2 Th...

Page 19: ...tion Corrective action is required These are manual reset controls that must be reset before operation can continue PRESSURE SWITCHES PRESSURE SWITCHES PRESSURE SWITCHES PRESSURE SWITCHES This furnace...

Page 20: ...g 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 3 175 mm reducing coupling 1 1 8 0 3 cm adapter There is a accessory kit 1PK0602 available from Source 1 which has the following items 12 30 cm length x 1 8 0 3...

Page 21: ...er times a barometric pressure and temperature correction factor of 0 960 times 3600 then divided by the time it took to measure 2 cubic ft 0 0566 m3 of gas from the gas meter For Propane LP Gas multi...

Page 22: ...ure 30 for connection details IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or tightening the cap does not adjust the flow of g...

Page 23: ...sure regulator adjustment cap and adjustment screws on main gas valve 7 After the manifold pressure has been adjusted re calculate the furnace input to make sure you have not exceeded the specified in...

Page 24: ...ter pressure drop values in Table 15 are typical values for the type of filter listed and should only be used as a guideline Actual pres sure drop ratings for each filter type vary between filter manu...

Page 25: ...is 0 58 w c To determine the system airflow complete the following steps Obtain the airflow values at 0 50 w c 125 Pa 0 60 w c 150 Pa ESP Airflow 0 50 1250 CFM 35 4 m3 min Airflow 0 60 1180 CFM 33 4...

Page 26: ...35 7 Medium Low 1720 1700 1670 1620 1570 1500 1430 1310 1160 1000 48 7 48 1 47 3 45 9 44 5 42 5 40 5 37 1 32 8 28 3 Low 1410 1390 1360 1330 1280 1220 1170 1060 930 840 39 9 39 4 38 5 37 7 36 2 34 5 33...

Page 27: ...030 1980 1910 1850 1710 1570 1300 59 7 59 7 58 6 57 5 56 1 54 1 52 4 48 4 44 5 36 8 Medium Low 1690 1690 1650 1610 1540 1480 1410 1280 1170 1030 47 9 47 9 46 7 45 6 43 6 41 9 39 9 36 2 33 1 29 2 Low 1...

Page 28: ...opyright by York International Corp 2006 All rights reserved Supersedes 166753 UIM B 0306 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION X WIRING DIAGRAM SECTION X WIRING DIAGRAM SECTIO...

Reviews: