background image

035-14519-002 Rev. B (1204)

Unitary Products Group

7

Mark the unit nameplate with the appropriate heater selection on the
space provided or NONE to indicate cooling only. To operate these units
with electric heat, it is necessary to field install an electric heater kit
(2HK). See Electric Heater Kit Accessory Installation instructions for
proper installation procedure. Prior to installing electric heat, it is neces-
sary to perform the following procedure:

1.

1.   Remove the 4-pin power plug from the control board (See Fig-
ure 9).

NOTE: 

This pin must not be used when electric heaters are installed.

2.

Remove the four (4) screws from the duct cover and remove the
duct cover from the air handler.

Right-hand Airflow Application Only - Models with Circuit 
Breakers - See Figure 10

If unit is to be installed for right hand air flow, the circuit breakers in the
heat kit will need to be removed and rotated 180°, so the OFF position
will be down when the cabinet is positioned on the right side. This is an
NEC requirement. 

Do One Set Of Breakers At A Time - to make sure

wires are reconnected properly

. Loosen terminal screws on the wires

and gently pull the wires back from the breaker.   Remove screws
securing the breaker plate and rotate 180°, then secure the breaker
plate and reconnect the wires to the breaker. Proper torque for terminal
screws is 35 in/lbs.

LOW VOLTAGE CONTROL CONNECTION

The 24 volt power supply is provided by an internally wired low voltage
transformer which is standard on all models. However, if the unit is con-
nected to a 208 volt power supply the low voltage transformer must be
rewired to the 208 volt tap. See the unit wiring label.

Field supplied low voltage wiring can exit the unit on the top right hand
corner or the right hand side panel (See Figure 4, item K).

Install a 7/8" plastic bushing in the selected hole and keep low voltage
wiring as short as possible inside the control box.

The field wiring is to be connected at the screw terminals of the control
board. Refer to Figures 14, 15 & 16. 

NOTE: 

All wiring must comply with local and national electrical code

requirements. Read and heed all unit caution labels.

NOTE: 

It is possible to vary the amount of electric heat turned on during

the defrost cycle of a heat pump. Standard wiring will only bring
on 5 KW of electric heat during defrost. See Table 6 and Figures
14, 15 and 16 for alternate staging.

LINE POWER CONNECTIONS

Power may be brought into the unit through the supply air end of the
unit (top when unit is vertical) or the left side panel. Use the hole appro-
priate to the unit's orientation in each installation to bring conduit from
the disconnect. The power lead conduit should be terminated at the
electrical control box. Refer to Tables 8, 9 & 11 for wire requirements.
Also see Figure 11.

 FIGURE 9:  

Control Board

R

Y

G

W2

W1

O

C

2
4
V
A
C

BREAK TAB FOR
VARIABLE SPEED MOTOR

L
2

F
A
N

L
1

L
2

L
1

L2

H

L

L

1

2

3

4

K2

T9A

K1

T9A

5
A
M
P

M
A
X

2

SPEED

L

TRIP

ECM

FAN

&

LIM

PWR

LIM

&

HEAT

COM

TEST

HEAT 2

DRV

HEAT 4

DRV

HEAT 3

DRV

FAN RELAY

FAN CONNECTIONS

TRANSFORMER
CONNECTIONS
(HIGH VOLTAGE)

4-PIN POWER
CONNECTOR

1 STAGE
HEAT RELAY

24 VOLT R

5 AMP
CONTROL
VOLTAGE
FUSE

6-PIN CONNECTOR
(LIMIT, 2ND, 3RD
& 4TH HEAT RELAY
DRIVER)

24 VOLT
COMMON

 FIGURE 10:  

Electric Heaters in Horizontal Configuration - Right Hand 

Air Flow

HEAT KIT ASSEMBLY

REMOVE 3 SCREWS TO
REMOVE THE CIRCUIT
BREAKER BRACKET
FROM HEAT KIT ASSEMBLY

JUMPER BAR

JUMPER BAR COVER

FIELD SUPPLY WIRING
WILL BE ATTACHED TO
THIS SIDE OF THE
CIRCUIT BREAKER(S)

CIRCUIT BREAKER(S) - THERE
MAY BE ONE, TWO OR THREE

CIRCUIT
BREAKER
BRACKET

HEAT KIT WIRING WILL BE
ATTACHED TO THIS SIDE OF
THE CIRCUIT BREAKER(S)

AIR

FLOW

 FIGURE 11:  

Line Power Connections

ELECTRIC HEAT

WITHOUT CIRCUIT BREAKER

SINGLE SOURCE (2.5 - 10 KW)

GND. LUG

POWER
SUPPLY

GND.
LUG

ELECTRIC HEAT

WITHOUT CIRCUIT BREAKER

3 PHASE (10 - 15 KW)

GND. LUG

POWER
SUPPLY

GND.
LUG

1 PHASE ELECTRIC HEAT

WITH CIRCUIT BREAKER

AS SHIPPED FROM FACTORY

SINGLE SOURCE

(2.5 - 25 KW) - 25 KW SHOWN

GND. LUG

POWER
SUPPLY

GND.
LUG

1 PHASE ELECTRIC HEAT

WITH CIRCUIT BREAKER

& BREAKER BAR REMOVED

MULTI-SOURCE (15 - 25 KW) - 25 KW SHOWN

GND. LUG

POWER
SUPPLY 1

GND.
LUG

POWER
SUPPLY 2

POWER
SUPPLY 3

TYPICAL WIRING WITHOUT ELECTRIC HEAT

GND. LUG

POWER
SUPPLY

GND.
LUG

POWER WIRING (208/230-1-60)

NOTE:

USE ONLY COPPER CONDUCTORS

Summary of Contents for F2FV060

Page 1: ...s including but not limited to building electrical and mechanical codes TABLE OF CONTENTS SAFETY 1 SPECIFIC SAFETY RULES AND PRECAUTIONS 2 SAFETY REQUIREMENTS 2 GENERAL INFORMATION 2 INSPECTION 2 LIMI...

Page 2: ...INFORMATION This Single Piece Air Handler provides the flexibility for installation in any upflow or horizontal application These versatile models may be used for cooling or heat pump operation with...

Page 3: ...n to remove pan from position 4A if factory installed 3 Position horizontal pan as required in either A or B position locking it into the vertical drain pan as shown 4 Horizontal drain pans have 4 plu...

Page 4: ...THE SIDES AND REAR OF UNIT SUPPORT BRACKET 060 COIL BAFFLE SHOWN IN RIGHT HORIZONTAL POSITION FIGURE 4 Dimensions Duct Sizes SHIPPING BRACKET REMOVE PRIOR TO INSTALLATION 2 SCREWS 10 3 8 J DRAIN CONNE...

Page 5: ...size filter Standard 1 size permanent or throw away filter may be used or permanent washable filters are available using model num ber 1PF603BK only See Table 4 for filter size SUSPENSION KITS A suspe...

Page 6: ...fitting hand tight and turn an additional 1 8 turn to seal NOTE This procedure should be done within 2 minutes to keep air and contaminates from entering the coil If the orifice cannot be replaced an...

Page 7: ...y with local and national electrical code requirements Read and heed all unit caution labels NOTE It is possible to vary the amount of electric heat turned on during the defrost cycle of a heat pump S...

Page 8: ...d Remove for Heat Pump for heat pump operation See Figure 12 To Set Electric Heat CFM The blower speed required for the Electric Heat is different than cooling Refer to the label in the bag attached t...

Page 9: ...240V F2FV060H06 F3FV060H06T 2HK 6500806B 0 5 1335 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0...

Page 10: ...60 8 6 2HK06501525B 48 6 52 9 50 60 8 6 1 May be 0 or 1 No Breaker or Breaker 2 O C P Over Current Protection device must be HACR type Circuit Breaker or Time Delay fuse TABLE 11 Electrical Data for...

Page 11: ...HEAT 3 4 THERMOSTAT OUTDOOR UNIT DEFROST CONTROL GND SCREW TERMINAL NOT AVAILABLE ON ALL THERMOSTATS IMPORTANT NOTE HEAT PUMP JUMPER ON THE CFM SELECTION BOARD MUST BE REMOVED WHEN AIR HANDLER IS USED...

Page 12: ...nd the local atmospheric conditions Clean filters keep unit efficiency high COIL CLEANING If the coil needs to be cleaned or replaced it should be washed with Calgon coilclean mix one part Coilclean t...

Reviews: