background image

035-14519-002 Rev. B (1204)

Unitary Products Group

5

DUCT CONNECTORS

NOTE: 

The electric heat accessory should be installed before the sup-

ply air duct is attached to the supply air openings. Refer to the
electric heater kit instructions for proper installation.

Air supply and return may be handled in one of several ways best
suited to the installation. See Figure 4 for dimensions for duct inlet and
outlet connections.

The vast majority of problems encountered with combination heating
and cooling systems can be linked to improperly designed or installed
duct systems. It is therefore highly important to the success of an instal-
lation that the duct system be properly designed and installed.

Use flexible duct collars to minimize the transmission of vibration/noise
into the conditioned space. If electric heat is used, non-flammable
material must be used.

Where return air duct is short, or where sound may be a problem,
sound absorbing glass fiber should be used inside the duct. Insulation
of duct work is a must where it runs through an unheated space during
the heating season or through an uncooled space during the cooling
season. The use of a vapor barrier is recommended to prevent absorp-
tion of moisture from the surrounding air into the insulation.

The supply air duct should be properly sized by use of a transition to
match unit opening. All ducts should be suspended using flexible hang-
ers and never fastened directly to the structure. This unit is not
designed for non-ducted (freeblow) applications. Size outlet plenum or
transition to discharge opening sizes shown in Figure 4.

Duct work should be fabricated and installed in accordance with local
and/or national codes. This includes the standards of the National Fire
Protection Association for Installation of Air-Conditioning and Ventilat-
ing Systems, NFPA No. 90B.

AIR FILTERS

Air filters must be field supplied. A 1" filter access rack has been built
into the unit. See Figure 4. Remove filter access cover shown. Install
proper size filter. Standard 1" size permanent or throw away filter may
be used, or, permanent washable filters are available using model num-
ber: 1PF603BK only. See Table 4 for filter size.

SUSPENSION KITS

A suspension kit is available. Models 1BH0601 (unit sizes 018-060) is
designed specifically for the units contained in this instruction (upflow
application only). For installation of these accessory kits, see the
instructions packed with the kit.

For suspension of these units in horizontal applications, it is recom-
mended to use angle steel support brackets with threaded rods, sup-
porting the units from the bottom, at the locations shown in Figure 5.

COIL METERING DEVICES

The coil in this Air Handler unit will have a metering device installed at
the factory. 

If the model number is of the following format:

 

F3FVH06T - The coil will have a Thermal Expansion Valve (TXV)
installed. Please refer to the TXV Metering Device section for installa-
tion notes.

If the model number is of the following model series:

 

F2FV  - The coil will have an orifice installed in the distributor housing.
Please refer to the Orifice Metering Device section for selection &
installation notes.

TXV Metering Device

Please refer to Table 2 to verify which TXV is installed in this Air Han-
dler unit and that this AHU is a valid system match for the AC or HP unit
installed.

The TXV is fully brazed into the coil assembly of this Air Handler unit at
the factory. The temperature sensing bulb will need to be attached to
the coil suction header line after the line set is brazed to the coil.

Use 1/2" screws to connect ductwork to bottom of unit. Longer
screws will pierce the drain pan and cause leakage. If pilot holes
are drilled, drill only though field duct and unit bottom flange.

Equipment should never be operated without filters.

Units

(Nominal Tons)

Dimension

WW

XX

060

19-1/2”

50-3/4”

 FIGURE 5:  

Typical Horizontal Installation

TABLE 2: 

Installed Orifice or TXV Sizes

Indoor Coil Model

Metering Device

F2FV060

Orifice - 90

F3FV060(T)

TXV 0703

 FIGURE 6:  

TXV Bulb Installation

SUSPENSION SUPPORT LOCATIONS FOR HORIZONTAL APPLICATIONS

2

WW

XX

1-1/2

NOTE:

USE SUPPORTS UNDER UNIT.

INSULATION
ROLL

EXPANSION
BULB

EXPANSION
BULB
CLAMP

EXPANSION
LINE

Summary of Contents for F2FV060

Page 1: ...s including but not limited to building electrical and mechanical codes TABLE OF CONTENTS SAFETY 1 SPECIFIC SAFETY RULES AND PRECAUTIONS 2 SAFETY REQUIREMENTS 2 GENERAL INFORMATION 2 INSPECTION 2 LIMI...

Page 2: ...INFORMATION This Single Piece Air Handler provides the flexibility for installation in any upflow or horizontal application These versatile models may be used for cooling or heat pump operation with...

Page 3: ...n to remove pan from position 4A if factory installed 3 Position horizontal pan as required in either A or B position locking it into the vertical drain pan as shown 4 Horizontal drain pans have 4 plu...

Page 4: ...THE SIDES AND REAR OF UNIT SUPPORT BRACKET 060 COIL BAFFLE SHOWN IN RIGHT HORIZONTAL POSITION FIGURE 4 Dimensions Duct Sizes SHIPPING BRACKET REMOVE PRIOR TO INSTALLATION 2 SCREWS 10 3 8 J DRAIN CONNE...

Page 5: ...size filter Standard 1 size permanent or throw away filter may be used or permanent washable filters are available using model num ber 1PF603BK only See Table 4 for filter size SUSPENSION KITS A suspe...

Page 6: ...fitting hand tight and turn an additional 1 8 turn to seal NOTE This procedure should be done within 2 minutes to keep air and contaminates from entering the coil If the orifice cannot be replaced an...

Page 7: ...y with local and national electrical code requirements Read and heed all unit caution labels NOTE It is possible to vary the amount of electric heat turned on during the defrost cycle of a heat pump S...

Page 8: ...d Remove for Heat Pump for heat pump operation See Figure 12 To Set Electric Heat CFM The blower speed required for the Electric Heat is different than cooling Refer to the label in the bag attached t...

Page 9: ...240V F2FV060H06 F3FV060H06T 2HK 6500806B 0 5 1335 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0...

Page 10: ...60 8 6 2HK06501525B 48 6 52 9 50 60 8 6 1 May be 0 or 1 No Breaker or Breaker 2 O C P Over Current Protection device must be HACR type Circuit Breaker or Time Delay fuse TABLE 11 Electrical Data for...

Page 11: ...HEAT 3 4 THERMOSTAT OUTDOOR UNIT DEFROST CONTROL GND SCREW TERMINAL NOT AVAILABLE ON ALL THERMOSTATS IMPORTANT NOTE HEAT PUMP JUMPER ON THE CFM SELECTION BOARD MUST BE REMOVED WHEN AIR HANDLER IS USED...

Page 12: ...nd the local atmospheric conditions Clean filters keep unit efficiency high COIL CLEANING If the coil needs to be cleaned or replaced it should be washed with Calgon coilclean mix one part Coilclean t...

Reviews: