background image

CLEARANCES

All units require certain clearances for proper operation and
service. Refer to Figure 6 for the clearances required for
combustion, construction, servicing and proper unit operation.

WARNING: Do not permit overhanging structures or shrubs to

obstruct the condenser air discharge outlet.

DUCT WORK

These units are adaptable to downflow use as well as rear
supply and return air duct openings. To convert to downflow,
use the following steps:

1. Remove the duct covers found in the bottom return and

supply air duct openings. There are four (4) screws securing
each duct cover (save these screws to use later).

2. Install the duct covers, removed in step one, to the rear

supply and return air duct openings. Secure with the four
(4) screws used in step one.

3. Seal the duct covers with silicone caulking.

Downflow units must have an L-shaped supply duct without any
outlets or registers located directly below the supply outlet of
the unit.

Duct work should be designed and sized according to the
methods of the Air Conditioning Contractors of America
(ACCA), as set forth in their Manual D.

A closed return duct system shall be used. This shall not
preclude use of economizers or ventilation air intake. Flexible
joints may be used in the supply and return duct work to
minimize the transmission of noise.

CAUTION: When fastening duct work to the side duct flanges on

the unit, insert the screws through the duct flanges only.
DO NOT insert the screws through the casing. Outdoor
duct work must be insulated and waterproofed.

NOTE: Be sure to note supply and return openings.

Refer to Figure 6 for information concerning rear and bottom
supply and return air duct openings.

FILTERS

Single phase units are shipped without a filter and is the respon-
sibility of the installer to secure a filter in the return air ductwork
or install a Filter/Frame Kit
 (1FF0114).

A filter rack and a filters are standard on three phase units.

Filters must always be used and must be kept clean. When
filters become dirt laden, insufficient air will be delivered by the
blower, decreasing your units efficiency and increasing operat-
ing costs and wear-and-tear on the unit and controls.

Filters should be checked monthly especially since this unit
may be used for both heating and cooling.

CONDENSATE DRAIN

A condensate trap is required to be installed in the condensate
drain. The plumbing must conform to local codes. Use a sealing
compound on male pipe threads. Install the condensate drain
line (

3

4

“ NPTF) to spill into an open drain.

SERVICE ACCESS

Access to all serviceable components is provided by the follow-
ing removable panels:

Blower service access

Electrical/filter access

Compressor service access

Refer to Figure 6 for location of these access panels and
minimum clearance.

THERMOSTAT

The room thermostat should be located on an inside wall
approximately 56" above the floor where it will not be subject
to drafts, sun exposure or heat from electrical fixtures or
appliances. Follow manufacturer’s instructions enclosed with
the thermostat for general installation procedure. Four, five or
six color coded insulated wires (minimum #18 AWG) should be
used to connect thermostat to unit. See Figure 3.

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the current
N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances.
The unit must be electrically grounded in accordance with local
codes or, in their absence, with the N.E.C./C.E.C. Voltage
tolerances which must be maintained at the compressor termi-
nals during starting and running conditions are indicated on the
unit Rating Plate and Table 1.

The wiring entering the cabinet must be provided with mechani-
cal strain relief.

A fused or HACR breaker disconnect switch should be field
provided for the unit.  If any of the wire supplied with the unit must
be replaced, replacement wire must be of the type shown on the
wiring diagram.

Electrical line must be sized properly to carry the load. Each
unit must be wired with a separate branch circuit fed directly
from the meter panel and properly fused.

Refer to Figure 2 for typical field wiring and to the appropriate unit
wiring diagram for control circuit and power wiring information.

COMPRESSORS

Units are shipped with compressor mountings factory-adjusted
and ready for operation.

CAUTION: Do Not loosen compressor mounting bolts.

530.46-N2Z

Unitary Products Group

3

Summary of Contents for DAPH Series

Page 1: ...forms 55 70 N1 General Installation 55 70 N2 Pre start Post start Check List 511 26 N1 1V Electric Heater Accessory REPLACEMENT PARTS Refer to Replacement Parts Manual for complete listing of replace...

Page 2: ...n Rig unit with slings placed under the unit Spreader bars of sufficient length should be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE...

Page 3: ...easing operat ing costs and wear and tear on the unit and controls Filters should be checked monthly especially since this unit may be used for both heating and cooling CONDENSATE DRAIN A condensate t...

Page 4: ...1 800 2 400 3 000 3 000 CONDENSER COIL ROWS DEEP 1 1 1 1 1 1 1 FINS PER INCH 20 20 20 20 20 20 20 FACE AREA Sq Ft 12 9 12 9 12 9 12 9 12 9 16 4 16 4 CHARGE REFRIGERANT 22 lbs oz 5 5 5 3 4 7 4 11 5 10...

Page 5: ...253 20 0 104 0 1 1 3 5 29 6 40 40 96 40 030 208 230 3 60 187 253 10 0 63 0 1 1 2 6 16 2 25 25 96 75 036 208 230 3 60 187 253 11 4 77 0 1 1 3 5 18 9 25 25 96 75 042 208 230 3 60 187 253 13 9 88 0 1 1 3...

Page 6: ...36 1 29 3 33 3 42 3 48 4 30 35 45 50 30 35 45 50 036 208 230 3 60 10 9 78 0 1 1 3 5 2NH04501025 2NH04501525 1 1 7 5 10 0 11 3 15 0 20 8 24 1 31 3 36 1 30 4 34 4 43 5 49 5 35 35 45 50 35 35 45 50 042...

Page 7: ...1 105 6 2 10 4 14 6 18 7 22 9 110 8 2 12 7 17 2 21 7 115 6 0 10 8 15 7 20 5 OUTDOOR TEMPERATURE F SUPERHEAT AT COMPRESSOR SUCTION F AIRFLOW 400 CFM TON INDOOR WB TEMPERATURE F 55 57 59 61 63 65 67 69...

Page 8: ...5 9 6 6 9 8 12 9 16 1 19 3 110 5 1 7 8 10 5 13 1 15 8 115 5 8 8 0 10 2 12 3 TABLE 11 SUPERHEAT CHARGING TABLE FOR MODEL DAPH048 OUTDOOR TEMPERATURE F SUPERHEAT AT COMPRESSOR SUCTION F AIRFLOW 400 CFM...

Page 9: ...R A T U R E 5 5 0 6 0 0 6 5 0 7 0 0 7 5 0 8 0 0 8 5 0 9 0 0 9 5 0 S U C T I O N P R E S S U R E 1 5 0 0 C F M 1 2 0 1 2 5 6 7 W B 7 2 W B 6 2 W B 5 7 W B FIG 4 DAPH060 SUCTION PRESSURE TEMPERATURE ut...

Page 10: ...nsions will be provided upon request UNIT CONDENSATE CONNECTION 3 4 NPTI TRAP REQUIRED 491 8 OVERALL SIDE SUPPLY AIR OPENING SIDE RETURN AIR OPENING COMPRESSOR SERVICE ACCESS COMPARTMENT PANEL 221 4 1...

Page 11: ...OLT SEQUENCE OF OPERATION FOR 048 AND 060 MODELS WITH 208 230 460 VOLT Cooling The following sequences of operation are based on using a standard single stage cooling thermostat WITH POWER TO UNIT AND...

Page 12: ...onnect switches and the thermostat Teach him how to start and stop the unit and how to adjust temperature settings within the limitations of the system SIGNAL STATE BOARD FUNCTION SIGNAL STATE BOARD F...

Page 13: ...r to the unit is shut off prior to cleaning CAUTION Exercise care when cleaning the coil so that the coil fins are not damaged Do not permit the hot condenser air discharge to be obstructed by overhan...

Page 14: ...NOTES FOR WIRING DIAGRAMS ON PAGES 14 15 16 17 18 AND 19 LEGEND FOR WIRING DIAGRAMS ON PAGES 14 15 16 17 18 AND 19 530 46 N2Z 14 Unitary Products Group...

Page 15: ...FIG 7 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY DPH018 THRU 042 MODELS 530 46 N2Z Unitary Products Group 15...

Page 16: ...FIG 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY DPH048 AND 060 MODELS 530 46 N2Z 16 Unitary Products Group...

Page 17: ...FIG 9 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY DPH018 THRU 042 MODELS 530 46 N2Z Unitary Products Group 17...

Page 18: ...FIG 10 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY DPH048 AND 060 MODELS 530 46 N2Z 18 Unitary Products Group...

Page 19: ...FIG 11 TYPICAL WIRING DIAGRAM 460 3 60 AND 575 3 60 POWER SUPPLY DPH018 THRU 042 MODELS DETAIL A 530 46 N2Z Unitary Products Group 19...

Page 20: ...FIG 12 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY DPH048 AND 060MODELS 530 46 N2Z 20 Unitary Products Group...

Page 21: ...530 46 N2Z Unitary Products Group 21...

Page 22: ...530 46 N2Z 22 Unitary Products Group...

Page 23: ...530 46 N2Z Unitary Products Group 23...

Page 24: ...Subject to change without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved 530 46 N2Z 799 5005 York Drive Norman Oklahoma 73069 Unitary Products Group...

Reviews: