Unitary Products Group

7.

These units should be installed in accordance with:

a.

Regulations of National Board of Fire Underwriters,
local utility or other authorities having jurisdiction.

b.

Standards for air conditioning systems, National Fire
Association Pamphlet # 90.

c.

National Warm Air Heating and Air Conditioning
Association Manuals, which ever is applicable.

d.

Wiring must conform to provisions of National Elec-
trical Code (NFPE Pamphlet # 70) and local ordi-
nances.

INSTALLATION

ACCESSORIES

Refer to the following instructions for installation of accesso-
ries:

Form 550.13-N10.1U Electric Heat

Form 550.13-N10.2U Supply Air Plenum

Form 550.13-N10.3U Return Air Grille

Form 550.12-N10.7U Hot Water Coil and Non-Freeze 
Steam Coil

Form 560.20-N1.5  Water Regulating Valve

TABLE 1: APPLICATION DATA

LIMITATION

MINIMUM

1

MAXIMUM

1

P

OWER

 S

UPPLY

, V

OLTS

208/230-1-60

187

252

208/230-3-60

187

252

460-3-60

432

504

S

UPPLY

 A

IR

, CFM

C2ED060

1600

2400

C2ED090

2400

3600

C2ED120

3200

4800

C2ED180

4800

7200

A

IR

 T

EMPERATURE

 E

NTERING

 

C

OOLING

 C

OIL

 °F

Wet Bulb

57

72

Dry Bulb

65

95

C

ONDENSER

 W

ATER

, GPM

C2ED060

4

20

C2ED090

6

30

C2ED120

8

40

C2ED180

12

60

C

ONDENSER

 W

ATER

-S

IDE

 W

ORKING

 P

RESSURE

, PSIG

20

2

150

3

L

EAVING

 C

ONDENSER

 W

ATER

 T

EMPERATURE

4

, °F

60

115

1.

Utilization Range “A” in accordance with ARI Standard 110.

2.

The water pressure must be great enough to overcome the pressure drop of the condenser and the condenser water piping.

3.

Although the water side is only leak tested for 150psig, the maximum water-side working pressure of the condenser is 450 psig.  
Class 150 fittings in the unit’s condenser water piping are good for 300 psig.  For 300 psig applications, a sealing material (Lock-
tite or equivalent) must be applied to all threaded connections to assure a leak-tight installation.  The water regulating valve acces-
sories are limited to a maximum 150 psig.

4.

The limitation for entering condenser water temperature will vary with condenser water GPM.

THIS PRODUCT MUST BE INSTALLED IN 
STRICT COMPLIANCE WITH THE ENCLOSED 
INSTALLATION INSTRUCTIONS AND ANY 
APPLICABLE LOCAL, STATE, AND NATIONAL 
CODES INCLUDING BUT NOT LIMITED TO, 
BUILDING, ELECTRICAL AND MECHANICAL 
CODES.

Summary of Contents for C*ED060A Series

Page 1: ...N 3 LIMITATIONS 3 INSTALLATION 4 OPERATION 23 A Complete Table of Contents on Following Page INSTALLATION INSTRUCTION SAVE THIS MANUAL SINGLE PACKAGE WATER COOLED AIR CONDITIONERS EMBASSSY SERIES MODE...

Page 2: ...ANGE CED060 090 120 15 6 BLOWER ARRANGE CED180 1 15 7 BLOWER ARRANGE CED180 2 3 4 15 8 TYPICAL MOTOR MOUNTING ASSEMBLY 16 9 PROBE LOCATIONS 17 10 CFM CURVE 17 11 SUPPLY AIR DUCT CONNECTION 18 12 COILS...

Page 3: ...utions are given to prevent equipment damage Warnings are given to alert the installer that personal injury and or equipment damage may result if the installation procedure is not handled properly INS...

Page 4: ...00 4800 C2ED180 4800 7200 AIR TEMPERATURE ENTERING COOLING COIL F Wet Bulb 57 72 Dry Bulb 65 95 CONDENSER WATER GPM C2ED060 4 20 C2ED090 6 30 C2ED120 8 40 C2ED180 12 60 CONDENSER WATER SIDE WORKING PR...

Page 5: ...ned with sound absorbing material c Support the unit on a separate floor structure form that of the conditioned space d Place a non deteriorating sound isolation pad under the entire unit base CLEARAN...

Page 6: ...8 3 8 1 2 Fins Aluminum per inch 13 13 13 12 CENTRIFUGAL BLOWER FORWARD CURVE Diameter x Width inches 10 x 10 15 x 15 15 x 15 18 x 18 MOTORS 2 Nominal HP Rating 3 4 1 460 3 60 1 1 2 2 3 FILTERS THROWA...

Page 7: ...67 94 65 6 0 10 2 89 63 6 4 9 9 74 62 86 62 5 8 9 4 81 61 6 2 9 1 68 57 77 60 5 7 8 6 73 59 6 1 8 4 120 3000 86 72 30 139 93 8 4 11 2 132 90 9 0 10 8 80 67 128 90 8 2 10 5 121 87 8 8 10 1 74 62 118 8...

Page 8: ...80 67 84 61 6 8 9 5 78 58 7 3 9 1 74 62 76 59 6 6 8 8 71 56 7 1 8 4 68 57 68 57 6 5 8 1 64 55 7 0 7 8 120 3000 86 72 30 124 87 9 6 10 4 116 85 10 3 10 0 80 67 114 84 9 4 9 7 106 81 10 0 9 3 74 62 103...

Page 9: ...1 00 1 03 1 05 Sensible Capacity 0 85 0 94 1 00 1 04 1 07 0 95 0 98 1 00 1 01 1 02 Compressor kW 0 97 0 99 1 00 1 01 1 02 1 10 1 04 1 00 0 97 0 95 TABLE 7 CONDENSER WATER PRESSURE DROP MODEL CONDENSE...

Page 10: ...0 34 1 17 1 09 0 14 1 33 1 24 800 0 84 1 25 1 16 0 71 1 42 1 32 0 53 1 60 1 48 0 30 1 80 1 64 900 1 18 1 48 1 38 1 06 1 70 1 57 0 91 1 92 1 75 0 70 2 18 1 99 0 43 2 45 2 24 950 1 37 1 61 1 50 1 26 1...

Page 11: ...i n a l b l o c k 2 2 2 3 2 2 1 3 8 A C C E S S P A N E L T O C O M P R E S S O R A N D E L E C T R I C A L B O X 2 1 3 8 1 2 0 D U C T F L A N G E 2 1 4 1 1 5 8 1 3 3 2 K N O C K O U T P O W E R W I...

Page 12: ...B O X 1 3 3 2 K N O C K O U T P O W E R S U P P L Y B o t h S i d e s o f U n i t 1 1 4 N P T I W A T E R O U T L E T 1 1 4 N P T I W A T E R I N L E T 2 K N O C K O U T S B o t h S i d e s o f U n i...

Page 13: ...4 1 3 3 2 K N O C K O U T P O W E R W I R I N G 1 1 2 N P T I W A T E R I N L E T 2 5 8 K N O C K O U T S B o t h S i d e s o f U n i t 1 1 2 N P T I W A T E R O U T L E T A C C E S S P A N E L T O C...

Page 14: ...2 3 Bottom 4 1 Overall dimension of the unit will vary if an electric heater or a supply air plenum is used 2 Although no clearance is required for service and operation some clearance may be required...

Page 15: ...nd on the required CFM the unit accessories and the static resistances of both the supply and the return air duct systems With this informa tion the RPM for supply air blower can be determined from th...

Page 16: ...he supply air CFM after the initial balancing has been completed 1 Drill two 5 16 inch holes in the side panel as shown in Figure 9 2 Insert at least 8 of 1 4 inch tubing into each of these holes for...

Page 17: ...LOCATIONS MODEL DIMENSION A B C D CED060 9 1 2 2 1 4 19 10 1 4 CED090 3 3 14 12 CED120 3 3 14 12 CED180 7 1 3 4 18 13 3 4 5 1 6 H O L E A B C D 5 1 6 H O L E C O I L S E C T I O N F I L T E R S E V A...

Page 18: ...46 1 1 2 208 230 3 60 460 3 60 655 880 2 8 3 8 7 8 7 5 1 A36 37 3 CED120 25 46 2 208 230 3 60 460 3 60 700 950 2 8 3 8 7 8 7 0 1 A36 37 3 CED180 25 46 3 208 230 3 60 625 810 3 4 4 4 7 8 9 5 1 A57 58...

Page 19: ...connections if desired Supply and return elbow connections may be rotated to provide for left hand connections Inlet water must always enter at the lower connection of the con denser See Figure 12 3 W...

Page 20: ...and are equipped with crankcase heaters 6 Schrader type access valves are provided in the suction and discharge lines for field use 7 The inlet joints or the liquid line strainer dryers are sol dered...

Page 21: ...er is not plentiful an out door or indoor forced or induced draft cooling tower is recom mend for condenser water Typical piping and wiring arrangements for installing one or more units with pump and...

Page 22: ...I T C 2 E D 0 6 0 u n i t s o n l y h a v e o n e c o o l i n g s t a g e a n d c a n u s e t h e f o l l o w i n g T h e r m o s t a t S u b B a s e 2 T H 1 3 7 0 0 4 2 4 2 T B 0 8 7 0 0 1 2 4 U N I...

Page 23: ...removed for unit installation and operation check 10 Set room thermostat at desired space temperature Unit will continue to cycle as required to maintain conditions 11 If electric heat is installed o...

Page 24: ...n the power spring FIGURE 17 COOLING TOWER WATER PIPING T O D R A I N B L E E D V A L V E S T R A I N E R O V E R F L O W C O O L I N G T O W E R M A K E U P S U P P L Y P U M P B Y P A S S T O A D D...

Reviews: