background image

035-16734-000

560.20-N1Y

Unitary Products Group

21

ACCESSORY WIRING

If the unit includes an electric heat accessory, separate power
wiring must be provided.  Refer to electric heat instruction,
Form 550.13-N10.1U, for additional installation instructions.

Refer to Figure 15 and 16 for field wiring diagrams.  Refer to
Table 17 to size the disconnect switch, the power wiring and
the fuses.

NOTE:Three phase motor rotations may be incorrect when
unit is first started.  Reverse phase (leads L1 and L2) at
blower motor contactor to obtain correct rotation.

WATER REGULATING VALVES

Water regulating valves provide control of quantity of con-
denser water supplied to the unit under varying load condi-
tions by sensing compressor discharge pressure.  This
feature is required in some areas where water conservation is
mandated.

Water regulating valves are shipped separately for field
installation.

Accessory kits 1WR0413, 1WR0402, and 1WR0403 are
used on the CED060, CED090 and CED120, and CED180
respectively.

Installation of water control valves is accomplished by remov-
ing front panel of condenser section, breaking water line
unions to condenser coils and removing water inlet piping.

Factory installed nipples are removed and replaced with the
nipples and water valve furnished for each condenser, unit is
repiped and capillary is attached to proper discharge line.

Valves are designed to operate between 25 and 150 psig.  A
water pressure-reducing valve must be installed in condenser
water inlet line if pressure exceeds 150 psig.

COOLING TOWER

Where water costs are high, or water is not plentiful, an out-
door or indoor forced or induced draft-cooling tower is recom-
mend for condenser water.

Typical piping and wiring arrangements for installing one or
more units with pump and cooling tower as shown in Figures
17, 18 and 19.

1.

Figure 17 illustrates the piping including a bleed-off valve 
and strainer in the suction line to the pump.  The bleed-
off is needed to keep the concentration of salts down, 
especially in areas having hard water.

The by-pass is used to permit circulation of a larger 
quantity of water over the tower than through the con-
denser.  This allows the tower to operate at greater effi-
ciency without suffering the pressure drip through the 
condenser.

2.

Figure 18 shows the suggested wiring arrangement nec-
essary to interconnect the units pump and tower fan 
motor.  The entire system starts and stops automatically

3.

Figure 19 shows an alternate wiring arrangement.  Its 
room thermostat individually controls each unit.  The 
conditioner control circuit is energized by the pump 
motor also starts the tower fan.  After the pump is started 
annually it will continue to operate until the stop button is 
pushed.  This arrangement is suggested where there will 
be a long run of condenser water piping exposed so that 
it might be heated excessively during the off periods with 
automatic operation.

In each case, the wiring is such that there is water circulation
through the condenser when units are running.

Cooling towers must be selected for the specific conditions of
each application.  Local representatives of cooling tower
manufacturers will assist in the selection of proper size tower
for each CED installation.

 FIGURE 14 : ELECTRICAL CONTROL BOX 

(CED090 SHOWN)

POWER WIRING
KNOCKOUTS

TERMINAL
BLOCK
(1TB)

TERMINAL
BLOCK
(2TB)

CONTROL BOX

Summary of Contents for C*ED060A Series

Page 1: ...N 3 LIMITATIONS 3 INSTALLATION 4 OPERATION 23 A Complete Table of Contents on Following Page INSTALLATION INSTRUCTION SAVE THIS MANUAL SINGLE PACKAGE WATER COOLED AIR CONDITIONERS EMBASSSY SERIES MODE...

Page 2: ...ANGE CED060 090 120 15 6 BLOWER ARRANGE CED180 1 15 7 BLOWER ARRANGE CED180 2 3 4 15 8 TYPICAL MOTOR MOUNTING ASSEMBLY 16 9 PROBE LOCATIONS 17 10 CFM CURVE 17 11 SUPPLY AIR DUCT CONNECTION 18 12 COILS...

Page 3: ...utions are given to prevent equipment damage Warnings are given to alert the installer that personal injury and or equipment damage may result if the installation procedure is not handled properly INS...

Page 4: ...00 4800 C2ED180 4800 7200 AIR TEMPERATURE ENTERING COOLING COIL F Wet Bulb 57 72 Dry Bulb 65 95 CONDENSER WATER GPM C2ED060 4 20 C2ED090 6 30 C2ED120 8 40 C2ED180 12 60 CONDENSER WATER SIDE WORKING PR...

Page 5: ...ned with sound absorbing material c Support the unit on a separate floor structure form that of the conditioned space d Place a non deteriorating sound isolation pad under the entire unit base CLEARAN...

Page 6: ...8 3 8 1 2 Fins Aluminum per inch 13 13 13 12 CENTRIFUGAL BLOWER FORWARD CURVE Diameter x Width inches 10 x 10 15 x 15 15 x 15 18 x 18 MOTORS 2 Nominal HP Rating 3 4 1 460 3 60 1 1 2 2 3 FILTERS THROWA...

Page 7: ...67 94 65 6 0 10 2 89 63 6 4 9 9 74 62 86 62 5 8 9 4 81 61 6 2 9 1 68 57 77 60 5 7 8 6 73 59 6 1 8 4 120 3000 86 72 30 139 93 8 4 11 2 132 90 9 0 10 8 80 67 128 90 8 2 10 5 121 87 8 8 10 1 74 62 118 8...

Page 8: ...80 67 84 61 6 8 9 5 78 58 7 3 9 1 74 62 76 59 6 6 8 8 71 56 7 1 8 4 68 57 68 57 6 5 8 1 64 55 7 0 7 8 120 3000 86 72 30 124 87 9 6 10 4 116 85 10 3 10 0 80 67 114 84 9 4 9 7 106 81 10 0 9 3 74 62 103...

Page 9: ...1 00 1 03 1 05 Sensible Capacity 0 85 0 94 1 00 1 04 1 07 0 95 0 98 1 00 1 01 1 02 Compressor kW 0 97 0 99 1 00 1 01 1 02 1 10 1 04 1 00 0 97 0 95 TABLE 7 CONDENSER WATER PRESSURE DROP MODEL CONDENSE...

Page 10: ...0 34 1 17 1 09 0 14 1 33 1 24 800 0 84 1 25 1 16 0 71 1 42 1 32 0 53 1 60 1 48 0 30 1 80 1 64 900 1 18 1 48 1 38 1 06 1 70 1 57 0 91 1 92 1 75 0 70 2 18 1 99 0 43 2 45 2 24 950 1 37 1 61 1 50 1 26 1...

Page 11: ...i n a l b l o c k 2 2 2 3 2 2 1 3 8 A C C E S S P A N E L T O C O M P R E S S O R A N D E L E C T R I C A L B O X 2 1 3 8 1 2 0 D U C T F L A N G E 2 1 4 1 1 5 8 1 3 3 2 K N O C K O U T P O W E R W I...

Page 12: ...B O X 1 3 3 2 K N O C K O U T P O W E R S U P P L Y B o t h S i d e s o f U n i t 1 1 4 N P T I W A T E R O U T L E T 1 1 4 N P T I W A T E R I N L E T 2 K N O C K O U T S B o t h S i d e s o f U n i...

Page 13: ...4 1 3 3 2 K N O C K O U T P O W E R W I R I N G 1 1 2 N P T I W A T E R I N L E T 2 5 8 K N O C K O U T S B o t h S i d e s o f U n i t 1 1 2 N P T I W A T E R O U T L E T A C C E S S P A N E L T O C...

Page 14: ...2 3 Bottom 4 1 Overall dimension of the unit will vary if an electric heater or a supply air plenum is used 2 Although no clearance is required for service and operation some clearance may be required...

Page 15: ...nd on the required CFM the unit accessories and the static resistances of both the supply and the return air duct systems With this informa tion the RPM for supply air blower can be determined from th...

Page 16: ...he supply air CFM after the initial balancing has been completed 1 Drill two 5 16 inch holes in the side panel as shown in Figure 9 2 Insert at least 8 of 1 4 inch tubing into each of these holes for...

Page 17: ...LOCATIONS MODEL DIMENSION A B C D CED060 9 1 2 2 1 4 19 10 1 4 CED090 3 3 14 12 CED120 3 3 14 12 CED180 7 1 3 4 18 13 3 4 5 1 6 H O L E A B C D 5 1 6 H O L E C O I L S E C T I O N F I L T E R S E V A...

Page 18: ...46 1 1 2 208 230 3 60 460 3 60 655 880 2 8 3 8 7 8 7 5 1 A36 37 3 CED120 25 46 2 208 230 3 60 460 3 60 700 950 2 8 3 8 7 8 7 0 1 A36 37 3 CED180 25 46 3 208 230 3 60 625 810 3 4 4 4 7 8 9 5 1 A57 58...

Page 19: ...connections if desired Supply and return elbow connections may be rotated to provide for left hand connections Inlet water must always enter at the lower connection of the con denser See Figure 12 3 W...

Page 20: ...and are equipped with crankcase heaters 6 Schrader type access valves are provided in the suction and discharge lines for field use 7 The inlet joints or the liquid line strainer dryers are sol dered...

Page 21: ...er is not plentiful an out door or indoor forced or induced draft cooling tower is recom mend for condenser water Typical piping and wiring arrangements for installing one or more units with pump and...

Page 22: ...I T C 2 E D 0 6 0 u n i t s o n l y h a v e o n e c o o l i n g s t a g e a n d c a n u s e t h e f o l l o w i n g T h e r m o s t a t S u b B a s e 2 T H 1 3 7 0 0 4 2 4 2 T B 0 8 7 0 0 1 2 4 U N I...

Page 23: ...removed for unit installation and operation check 10 Set room thermostat at desired space temperature Unit will continue to cycle as required to maintain conditions 11 If electric heat is installed o...

Page 24: ...n the power spring FIGURE 17 COOLING TOWER WATER PIPING T O D R A I N B L E E D V A L V E S T R A I N E R O V E R F L O W C O O L I N G T O W E R M A K E U P S U P P L Y P U M P B Y P A S S T O A D D...

Reviews: