8.Setting Procedure
18
■
Set value reading in the general-purpose data area
(using request flag 2)
Turn ON R/W for reading out Setting value.
The WORK data of selected WORK No. is output.
Read out General purpose data area (response) after confirming Request flag 2 response ON.
①
Input Work No. to read to the Work No. area.
Range: 0 to 15
②
Input the command of the set value to be read in the Command area in the general-purpose data area.
③
Set R/W of the remote output to 1.
④
Make request flag 2 of the remote output 0
→
1.
⑤
After confirming response flag 2 of the remote input 0
→
1, make request flag 2 of the remote output 1
→
0.
⑥
Responses are stored in R/W (response) of the remote input and general-purpose data area (response).
Confirm the contents of the general-purpose data area (response).
Request flag 2
(RY0002)
Request flag 2 response
(RX0002)
(The Upper row of signal level is ON. The Lower row of signal level is OFF.)
R/W
(RY0003)
General purpose data area
(RWw000C)
(RWw000D)
WORK No.
(RWw000F)
Command No.
(RWw000E)
R/W response
(RX0003)
Command No. response
(RWr000E)
ex.) When 4 stations occupied (writing in Setting value)
Request flag 2
(RY0002)
Request flag 2 response
(RX0002)
ex.) When 4 stations occupied (Reading out Setting value)
(The Upper row of signal level is ON. The Lower row of signal level is OFF.)
R/W
(RY0003)
WORK No.
(RWw000F)
R/W response
Command No.
(RWw000E)
(RX0003)
General purpose data area
(RWr000C)
(RWr000D)
Command No. response
(RWr000E)
response