UP-2210R/P Hardware installation and configuration manual
63
In the example above, Figure 60, the primary voltage is 11 kV and the secondary 110 V.
The meter calculates the ratio to 100.
The current transformer ratio is 400:5 and is entered as in the picture above.
Tip! You can use if you for example want to start over again.
Press next and select your reference and trig levels, see Figure 61 below and then press next and you
will get a summary of your measure configuration, see Figure 63 below.
Enter measurement
transformer
nominal level.
Advanced settings
are described in
chapter 0
Additional
constants. Can be
used for turning
current reference by
entering -1.
Figure 60
Figure 61