P O W E R I N G   T E C H N O L O G Y

SCIMITAR 3000 SERIES

INSTALLATION & OPERATING MANUAL

Manual No. SCIMITAR3000-1 

Page 9 

scimitar3000-man-rev1-0219.indd

 

 

2.2.7  Frame Ground.

 

 

 

Connect to the frame ground of the cabinet or rack in which the unit is installed using 8AWG wire.

  

 

 

 

 

WARNING!

 

 

 

 

 

 

Operation of this inverter without a proper ground

 

 

 

 

 

 

connection may result in an electrical safety hazard.

 

2.3 Installation

 

 

   

WARNING!

  

 

 

 

Shock Hazard. Before proceeding further, carefully check that

  

 

 

 

the unit is NOT connected to any batteries and that all wiring is

  

 

 

 

disconnected from any electrical sources.

  

 

 

 

Do not connect the output sockets to an incoming AC source.

 This power inverter should be installed in a restricted access location such as a Telecommunications room or IT room, 

where access is limited to service and other qualified personnel and which can only be entered by use of a tool lock or 

key which is controlled by the authority that is responsible for the location.  Bare parts of any terminals that present a 
hazardous energy level shall be located or guarded so that unintentional bridging by conductive materials that might be 
present is unlikely.  A readily accessible disconnect device shall be incorporated in the building installation wiring prior to 
connection to the inverter.  These locations should additionally meet the following requirements:

 

 

2.3.1  Dry - Do not allow water to drip or splash on the inverter.

 

 

2.3.2 

Elevated Operating Ambient - if the inverter is installed in a closed or multi-unit rack assembly the operating 
ambient temperature of the rack environment may be greater than the room ambient.  consideration should 
be given to installing the inverter in an environment compatible with the maximum ambient temperature of 
60°C.

   

2.3.3  Safe - Do not install the inverter in a battery compartment or other areas where flammable fumes may exist, 

such as fuel storage areas or engine compartments.

   

2.3.4  Reduced Airflow - Installation of the inverter in a rack should be such that the amount of airflow required for 

safe operation is not compromised.

 

 

2.3.5  Dust Free - Do not install the inverter in a dusty environment as dust and other particles such as wood 

shavings, filings can be pulled into the unit when the cooling fans are operating.

 

 

2.3.6  Close to Batteries - Avoid excessive cable lengths but do not install the inverter in the same compartment 

as the batteries.  Use the recommended wire lengths and sizes (see section 2.6).  Also, do not mount the 
inverter where it will be exposed to gasses produced by the battery as these gasses are highly corrosive 
and prolonged exposure will damage the inverter.

 

 

2.3.7  Mechanical Loading - Mounting of inverter in the rack should be such that a hazardous condition is not 

achieved due to uneven mechanical loading.

 

 

2.3.8  Circuit Overload - Consideration should be given to the connection of the inverter to the supply circuit and 

the effect that overloading of these circuits might have on over current protection devices and supply wiring.  

Appropriate consideration of equipment nameplate ratings should be used when addressing this concern.

 

 

2.3.9 

Reliable Earthing - Reliable earthing of rack-mounted equipment should be maintained.  Particular attention 
should be given to supply connections other than direct connections to the branch circuit (e.g. use of power 
strips).

Summary of Contents for Scimitar 3000 Series

Page 1: ...a 33065 USA sales unipowerco com NORTH AMERICA CALA CALL 1 954 346 2442 EMEA CALL 1 561 990 3830 INSTALLATION OPERATING MANUAL Scimitar 3000 Series 3000W 2RU RACK MOUNT INVERTERS WWW UNIPOWERCO COM Ma...

Page 2: ......

Page 3: ...Rear Panel Description 7 2 3 Installation 9 2 4 Quick Hook up and Testing 10 2 5 Safety Grounding 11 2 6 Making DC Connections 12 2 7 Alarm Connection 13 2 8 Inverter Operation 13 2 9 Cooling Fan Oper...

Page 4: ...ncy 50 60Hz switch RS 232 interface Remote controls port Wire connection to PC Wired Remote control Loading and Temperature controlled cooling fan Advanced microprocessor Protection Input Undervoltage...

Page 5: ...32C Baud Rates 2400 4800 9600 19200 switch selectable SNMP Option Operates in conjunction with NetAgent UPS SNMP Agent STS Section By Pass AC Input Range 90 130VAC 110VAC nominal 180 260VAC 230VAC nom...

Page 6: ...ITAR 3000 L N FG ON OFF 1 97 50 0mm 1 14 29 0mm 1 54 39 0 1 10 28 0mm 1 22 31 0mm 3 46 40 0mm 0 87 22 0mm 17 52 445 0mm 3 94 100 0mm 3 46 1 77 0 12 3 0mm 88 0mm 45 0mm 0 12 3 0mm 19 06 484 0mm 18 23 4...

Page 7: ...ted with the actual parameter indicated by the top row of LEDs in the sequence VAC AMP WATT VDC TEMP Hz In the event of a fault condition this will be indicated on the display See section 2 8 The ONLI...

Page 8: ...ircuit NC and COM are shorted When the inverter is switched on and there is no AC supply available to the by pass circuit NO and COM are shorted When the inverter is switched off NC and COM are shorte...

Page 9: ...environment may be greater than the room ambient consideration should be given to installing the inverter in an environment compatible with the maximum ambient temperature of 60 C 2 3 3 Safe Do not i...

Page 10: ...correctly fitted after installation or when any maintenance has taken place 2 3 16 Protection in PRIMARY CIRCUITS against over currents short circuits and earth faults shall be provided either as an i...

Page 11: ...power switch to the OFF position The unit should shut down completely 2 4 7 To accurately measure the true output R M S voltage of inverter connect to one of the outlet sockets and then set the power...

Page 12: ...thed elsewhere The DC supply source is to be located within the same premises as the equipment Switching or disconnecting devices shall not be in the earthed circuit conductor between the DC source an...

Page 13: ...y to any SELV or other safety connected circuit and any cables or wiring used for such connections must be double insulated 2 8 Inverter Operation To operate the power inverter turn it on using the ON...

Page 14: ...V Models 20 0 to 32 0VDC 48V Models 42 0 to 62 0VDC High and low DC input voltage conditions are handled per the following table and described in more detail below Model Type DC input OVP shut down DC...

Page 15: ...erature to a safe operating level Once this has been achieved the unit will turn on automatically 3 Maintenance Scimitar 3000 Series inverters require only minimal maintenance for reliable operation T...

Page 16: ...e request a copy from your local Sales Office 6 Important Safety Instructions WARNING Before installing and using this inverter be sure to read these safety instructions Keep them in a safe place for...

Page 17: ...power to the Inverter to allow the internal microprocessor to read the new settings 7 1 110V units S1 FREQ Hz S2 S3 BAUD RATE ACV ADJ ON 60 OFF OFF 2400 SCIMITAR 3000 OFF 50 OFF ON 4800 ON OFF 9600 ON...

Page 18: ...integer number ranging from 0 to 9 The unit is Volts d O P voltage PPP P P is an integer number ranging form 0 to 9 The unit is Volts e O P current QQQ QQQ is a percent of maximum current not an absol...

Page 19: ...erco com This document is believed to be correct at time of publication and UNIPOWER LLC accepts no responsibility for consequences from printing errors or inaccuracies Specifications are subject to c...

Reviews: