background image

P O W E R I N G   T E C H N O L O G Y

SCIMITAR 3000 SERIES

INSTALLATION & OPERATING MANUAL

Manual No. SCIMITAR3000-1 

Page 13 scimitar3000-man-rev1-0219.indd

UNIPOWER recommends the following cables for optimum inverter performance.

Model NUMBER

Wire

Size

In-line

Fuse

INV1230R-B

#4/0AWG

400A

INV1230RH-B

INV2430R-B

#2/0

200A

INV2430RH-B

INV4830R-B

#1/0

100A

INV4830RH-B

Use only high quality copper wiring and keep cable length from 3-6 feet (~1-2m).

A suitable breaker, at the DC source, for isolation and overload protection is recommend.

 

2.7  Alarm Connection

 It is important to note that the electronic circuits associated with this function are directly connected within the AC output 
circuits of the inverter and that for this reason the relay contact connections that are provided on the rear panel mounted 
wire clamp connector MUST be considered to be at a non-SELV potential and all necessary precautions to protect the 
operator from electric shock hazard must be taken.

These relay contacts must not be connected directly to any SELV or other safety connected circuit and any cables or 
wiring used for such connections must be double insulated.

 

2.8  Inverter Operation

To operate the power inverter, turn it on using the ON/OFF switch on the front panel.  The power inverter is now ready 
to deliver AC power to your loads. 
If you are operating several loads from the power inverter, turn them on separately after the inverter has been turned on.  
This will ensure that the power inverter does not have to deliver the starting currents for all the loads at once.

 

 

   

CAUTION!

  

 

 

 

EXTERNAL SURFACES GET HOT.

  

 

 

 

During the period of the unit running, the case may become very

  

 

 

 

warm. Please do not touch the side marked. “

” directly. 

  

 

 

2.8.1  Controls and indicators: 

        

 

The ON/OFF switch turns the control circuit in the power inverter on and off. 

        

 

 

 

2.8.2  Output Voltage Indication

        

 

When the VDC LED is lit the display shows the Output Voltage

   

When the unit is first switched on the VAC LED is lit and the Output Voltage is displayed as described    

 

 above.

 

 

Selection of the following parameters is achieved by pressing the Function Selector button to the right of   

 

 

the display sequentially.

 

 

2.8.3  Output Current Indicator

        

 

When the AMP LED is lit the display shows the Output Current

Summary of Contents for Scimitar 3000 Series

Page 1: ...a 33065 USA sales unipowerco com NORTH AMERICA CALA CALL 1 954 346 2442 EMEA CALL 1 561 990 3830 INSTALLATION OPERATING MANUAL Scimitar 3000 Series 3000W 2RU RACK MOUNT INVERTERS WWW UNIPOWERCO COM Ma...

Page 2: ......

Page 3: ...Rear Panel Description 7 2 3 Installation 9 2 4 Quick Hook up and Testing 10 2 5 Safety Grounding 11 2 6 Making DC Connections 12 2 7 Alarm Connection 13 2 8 Inverter Operation 13 2 9 Cooling Fan Oper...

Page 4: ...ncy 50 60Hz switch RS 232 interface Remote controls port Wire connection to PC Wired Remote control Loading and Temperature controlled cooling fan Advanced microprocessor Protection Input Undervoltage...

Page 5: ...32C Baud Rates 2400 4800 9600 19200 switch selectable SNMP Option Operates in conjunction with NetAgent UPS SNMP Agent STS Section By Pass AC Input Range 90 130VAC 110VAC nominal 180 260VAC 230VAC nom...

Page 6: ...ITAR 3000 L N FG ON OFF 1 97 50 0mm 1 14 29 0mm 1 54 39 0 1 10 28 0mm 1 22 31 0mm 3 46 40 0mm 0 87 22 0mm 17 52 445 0mm 3 94 100 0mm 3 46 1 77 0 12 3 0mm 88 0mm 45 0mm 0 12 3 0mm 19 06 484 0mm 18 23 4...

Page 7: ...ted with the actual parameter indicated by the top row of LEDs in the sequence VAC AMP WATT VDC TEMP Hz In the event of a fault condition this will be indicated on the display See section 2 8 The ONLI...

Page 8: ...ircuit NC and COM are shorted When the inverter is switched on and there is no AC supply available to the by pass circuit NO and COM are shorted When the inverter is switched off NC and COM are shorte...

Page 9: ...environment may be greater than the room ambient consideration should be given to installing the inverter in an environment compatible with the maximum ambient temperature of 60 C 2 3 3 Safe Do not i...

Page 10: ...correctly fitted after installation or when any maintenance has taken place 2 3 16 Protection in PRIMARY CIRCUITS against over currents short circuits and earth faults shall be provided either as an i...

Page 11: ...power switch to the OFF position The unit should shut down completely 2 4 7 To accurately measure the true output R M S voltage of inverter connect to one of the outlet sockets and then set the power...

Page 12: ...thed elsewhere The DC supply source is to be located within the same premises as the equipment Switching or disconnecting devices shall not be in the earthed circuit conductor between the DC source an...

Page 13: ...y to any SELV or other safety connected circuit and any cables or wiring used for such connections must be double insulated 2 8 Inverter Operation To operate the power inverter turn it on using the ON...

Page 14: ...V Models 20 0 to 32 0VDC 48V Models 42 0 to 62 0VDC High and low DC input voltage conditions are handled per the following table and described in more detail below Model Type DC input OVP shut down DC...

Page 15: ...erature to a safe operating level Once this has been achieved the unit will turn on automatically 3 Maintenance Scimitar 3000 Series inverters require only minimal maintenance for reliable operation T...

Page 16: ...e request a copy from your local Sales Office 6 Important Safety Instructions WARNING Before installing and using this inverter be sure to read these safety instructions Keep them in a safe place for...

Page 17: ...power to the Inverter to allow the internal microprocessor to read the new settings 7 1 110V units S1 FREQ Hz S2 S3 BAUD RATE ACV ADJ ON 60 OFF OFF 2400 SCIMITAR 3000 OFF 50 OFF ON 4800 ON OFF 9600 ON...

Page 18: ...integer number ranging from 0 to 9 The unit is Volts d O P voltage PPP P P is an integer number ranging form 0 to 9 The unit is Volts e O P current QQQ QQQ is a percent of maximum current not an absol...

Page 19: ...erco com This document is believed to be correct at time of publication and UNIPOWER LLC accepts no responsibility for consequences from printing errors or inaccuracies Specifications are subject to c...

Reviews: