![Unipower INVC4850H Operating Manual Download Page 17](http://html1.mh-extra.com/html/unipower/invc4850h/invc4850h_operating-manual_3920258017.webp)
INVO SERIES INVERTER/CHARGER
INSTALLATION & OPERATING MANUAL
Manual No. INVO-1
Page
17
08/11 invo-man
Table 8 - General Specifications
Safety Certification
CE(EN60950)
EMI Classification
EN62040-2, CLASS A
Operating Temperature Range
0°C to 45°C
Storage temperature
-15°C ~ 60°C
Altitude, operational
Elevation: 0 ~ 1500 Meters
Relative humidity
5% to 95% non-condensing
Audible Noise
60dB max.
Cooling
Forced air, variable speed fan
Dimension
350mm (w) x 110mm (h) x 407mm (d)
Net Weight
9Kg
Table 9 Fault code/ Audible alarm
Fault
Code
Protect
Function
Active
Mode
Condition
Warning
(O/P=ON)
Fault
(O/P=OFF)
Restart
Operate Condition
--
Low DC
Voltage
Alarm
Inverter
DC Voltage
<Low
DC Alarm
1beep/2s -- -- --
0
Low DC
Voltage
Protection
Inverter
DC Voltage
<Low
DC Shut-down
--
Beep
continuous
Auto Mains
is
normal
1
Over Charge
Protection
Line
DC Voltage
>High DC input
Shut-down
Beep continuous
--
Manual
--
1
Over Voltage
Protection
Standby
DC Voltage
>High DC input
Shut-down
--
Beep
continuous
Auto
DC
Voltage<High
DC input Shut-
down Recovery
2
Over Load
Protection
Line/
Inverter
110%~150% load
1beep/0.5s,and
continuous 10s
Beep
continuous
Manual --
>150% load
1beep/0.5s,and
continuous 5s
Beep
continuous
Manual --
3
Output Short
Circuit
Protection
Inverter
Output
Voltage<20Vrms
--
Beep
continuous
Manual --
4
Fan Fault
Protection
Line/
Inverter
Fan Locked
Fan Defected
2beep/2s,and
continuous 1min
Beep
continuous
Manual --
5
Over Temp
Protection
Line/
Inverter
HEAT SINK
Temp
≥
100
℃
--
Beep
continuous
Auto
HEAT SINK
Temp
≤
55
℃
6
Back-EMF
Protection
Standby
Reverse input and
output
--
Beep
continuous
Manual --
9
Output
Abnormal
Inverter
(Output Voltage
<170Vrms and
output current
under 32Arms) or
Output Voltage
>280Vrms
--
Beep
continuous
Manual --